EN 12483-1999 en Liquid Pumps - Pump Units with Frequency Inverters - Guarantee and Compatibility Tests《液体泵 带频率转换器的泵设备 保证和兼容性试验》.pdf
《EN 12483-1999 en Liquid Pumps - Pump Units with Frequency Inverters - Guarantee and Compatibility Tests《液体泵 带频率转换器的泵设备 保证和兼容性试验》.pdf》由会员分享,可在线阅读,更多相关《EN 12483-1999 en Liquid Pumps - Pump Units with Frequency Inverters - Guarantee and Compatibility Tests《液体泵 带频率转换器的泵设备 保证和兼容性试验》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD Liquid pumps - Pump units with frequency inverters - Guarantee and compatibility tests The European Standard EN 12483:1999 has the status of a British Standard ICs 23.080 BS EN 12483:1999 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW - - STD-BSI BS EN 12483-
2、ENGL 1779 Lb24bb9 077502b 330 direction of the Engineering Amd. No. Date Sector Committee, was published under the authority of the Standards Committee and comes into effect on 15 September 1999 BS EN 12483:1999 Comments National foreword This British Standard is the English hguage version of EN 124
3、83: 1999 The UK participation in its preparation was entrusted to Technical Committee MCW6, Pumps and pump testing, which has the responsibility to: - aid enquirers to understand the text; - present to the responsible European committee any enquiries on the - monitor related international and Europe
4、an developments and promulgate inteipretation, or proposals for change, and keep the UK interests informed; them in the UK. A list of organizations represented on this committee can be obtained on request to its secretary. Cross-references The British Stan - true RMS readings; - crest factor to be n
5、ot less then 3; - frequency range to be not less than 20 ldiz. For tests using the thermodynamic method conforming to IS0 5 198, care shall be taken to ensure that the head generated by the pump falls within the band of accepted accuracy. This is achieved by relating the generated head to the uncert
6、ainties of the differential temperature measurement in mK as set out in the Table 1. Table 1 -The minimum value of total head related to the uncertainties of temperature measurements 5 Test procedures 5.1 The guarantee test The test is carried out in two stages: the first stage establishes the perfo
7、rmance of the pump without the influence of the inverter, and the second stage identifies any modified performance arising from using the inverter, and allows the calculation of the effective efficiency of the inverter. 5.1.1 Testing the pump The pump shall be installed for the test without the inve
8、rter in the electric supply line using either the contract motor or a suitable substitute motor. For rotodynamic pumps, if the specified duty points are at a speed different fiom nominal speed or for liquid characteristics different fiom those of the test liquid, they shall be corrected to duties at
9、 the speed of the test motor and to the characteristics of the test liquid by the application of the Affinity Laws as described in prEN IS0 9906: 1995. Care shall be taken to avoid overloading any element of the test arrangement as a result of operating at the corrected conditions. For positive disp
10、lacement pumps, the correction to a duty at a nominal speed shall be made whilst keeping the load on the motor constant by, for example, changing the outlet pressure. For tests conforming to prEN IS0 9906: 1995, the rate of flow, head, speed, and power absorbed shall be measured and recorded with th
11、e pump operating at (or close to) each specified or corrected duty point, and the motor efficiency obtained from calibration or from the summation of losses method or from consultation with the motor supplier. 8 BSI 09- I999 Page 5 EN 12483:1999 For tests conforming to the thermodynamic method in IS
12、0 5 198 readings of the differential head and temperature rise shall be measured and recorded with the pump operating at (or close to) each specified or corrected duty point. The test values shall be compared with the corrected guarantee values and the pump performance shall be considered to have be
13、en verified if the test values fall within the acceptance limits defined in prEN IS0 9906:1995 or as otherwise agreed between the purchaser and the supplier. The readings and the results shall be recorded. 5.1.2 Testing the inverter If a substitute motor has been used for testing the pump it should
14、be replaced by the contract motor and the ir kmter shall be introduced into the test arrangement without any change to other items of equipment. The pump siiall be operated at or close to each of the specified duty points, and the inverter adjusted to give the same speeds as were achieved for testin
15、g the pump. The flow rate, or if appropriate the liquid temperature rise across the pump, head, and the power absorbed at the electrical input to the inverter, shall be measured and recorded. The overall system efficiency shall be calculated as: x 100 power output from the pump in kW power input to
16、the inventer in kW overall system efficiency, 9 % = l3r The inverter/motor efficiency shall be calculated as: x 100 power output from the motor in kW power input to the inverter in kW inverter/motor efficiency, qnv.mt., % = This method allows the calculation of the effective inverter efficiency as f
17、ollows: x 100 inverter/mtor efficiency motor efficiency effective inverter efficiency, tfinv., % = NOTE I The motor efficiency to be used in this calculation should be the value advised by the motor supplier. NOTE 2 The effective inverter efficiency reached by this method could be different from the
18、 inverter efficiency given by the manufacturer ofthe inverter resulting from different load conditions and the electrical characteristics of other elements of the system. The overall system efficiency derived from the test results shall be compared with the guarantee value overall system efficiency
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- EN124831999ENLIQUIDPUMPSPUMPUNITSWITHFREQUENCYINVERTERSGUARANTEEANDCOMPATIBILITYTESTS 液体 频率 转换器 设备 保证

链接地址:http://www.mydoc123.com/p-706351.html