1、W -C -596G/GEN 28 April, 1995SUPERSEDING W -C -596F/GEN 24 June, 1983FEDERAL SPECIFICATIONCONNECTOR, ELECTRICAL, POWER, GENERAL SPECIFICATION FORThe General Services Administration has authorized the useof this federal specification by all Federal agencies.1. SCOPE AND CLASSIFICATION1.1 Scope . This
2、 specification covers electrical plugs, receptacles, and cable outlets for service from 120 to 600volts with current ratings up to 60 amperes and a frequency rating of 50/60 hertz. It does not cover devices for usein hazardous locations, as defined in the National Electrical Code. Special plugs, rec
3、eptacles, and cableconnectors for 400 Hz and dc applications are also included. Connectors are to be used with copper or coppercladaluminum wire only.1.2 Connector grade . Connectors furnished in accordance with this specification shall be either the general gradeor the hospital grade as specified;
4、for logistics purposes, hospital grade connectors shall be stocked in lieu ofgeneral grade, (see 3.1 and 6.3).1.2.1 General grade . A class of connector that meets the requirements of Underwriters Laboratories, Inc. (UL)Standard 498 and the additional requirements as specified herein.1.2.2 Hospital
5、grade . A class of connector that meets the more stringent requirements of “hospital grade“connectors as specified in UL Standard 498 and the additional requirements as specified herein. This connector isdesigned to meet the added performance requirements of high abuse areas.2. APPLICABLE DOCUMENTS2
6、.1 Government publications . The following documents, of the issues in effect on the date of invitation for bids orrequest for proposal, form a part of this specification to the extent specified herein.Military SpecificationMIL -C -55330 - Connectors, Electrical and Fiber Optic, Packaging of.Militar
7、y StandardsMIL -STD -1285 - Marking of Electrical and Electronic Parts.MIL -STD -1344 - Test Methods for Electrical Connectors.(Copies of military specifications and st andards required by contractors in connection with specific procurementfunctions are obtained from the Defense Printing Service Det
8、achment Office, Building 4D (Customer Service), 700Robbins Avenue, Philadelphia, PA 19111-5094.)AMSC N/A FSC 59 35DISTRIBUTION STATEMENT A . Approved for public release; distribution is unlimited.INCH-POUNDBeneficial comments, recommendations, additions, deletions, clarification, etc. and any data w
9、hich mayimprove this document should be sent to: Defense Electronics Supply Center, ATTN: DESC-ELDI, 1507Wilmington Pike, Dayton, OH 45444-5765, or telephone (513) 296-5391, facsimile (513) 296-8868.Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C
10、-596G/GEN22.2 Other publications . The following documents form a part of this specification to the extent specified herein. Unless a specific issue is identified, the issue in effect on date of invitation for bids or request for proposal shallapply.Underwriters Laboratories, Inc., (UL) StandardUL 4
11、98 - Standard for Attachment Plugs and Receptacles.(Application for copies should be addressed to the Underwriters Lab oratories, Inc., Publication Stock, 333Pfingsten Road, Northbrook, Illinois 60062.)National Electrical Manufacturers Association (NEMA) Standards PublicationNEMA WD 6 - Wiring Devic
12、es - Dimensional Requirements.(Application for copies should b e addressed to National Electrical Manufacturers Association, 2101 LStreet, N.W., Suite 300, Washington, D.C. 20037.)American National Standards Institute, Inc., (ANSI) StandardANSI/NCSL Z540-1 - General Requirements for Calibration Labo
13、ratori es and Measuring and TestEquipment.(Application for copies should be addressed to the American National Standards Institute, Inc., 1430 Broadway,New York, New York 10018.)3. REQUIREMENTS3.1 Specification sheets . The individual item requirements shall be as specified herein and in accordance
14、with theapplicable specification sheets.3.2 Fire and casualty hazards .3.2.1 UL verified connectors . Each contractor shall submit to the contracting agency proof that the connectorssupplied under this specification conform to the requirements of the Underwriters Laboratories, Inc. (UL) Standard498
15、and applicable bulletins. The UL label or listing mark of the Underwriters Laboratories, Inc., may be acceptedas evidence that the connectors conform to UL requirements for general grade connectors. The label or listingmark and green dot of the Underwriters Laboratories, Inc. may be accepted as evid
16、ence that the connectorsconform to UL requirements for hospital grade connectors.3.2.2 Non -UL verified c onnectors . In lieu of the label, listing mark or listing mark and hospital grade green dot ofUL, the contractor shall submit independent proof, satisfactory to the contracting agency, that the
17、connectorsconform to the applicable requirements of the published standards including methods of tests of the UnderwritersLaboratories, Inc. (UL) Standard 498.3.2.3 Additional requirements . In addition to compliance with 3.2.1 and 3.2.2, the connectors shall comply with theadditional requirements s
18、pecified herein.3.3 Qualification . The connectors furnished under this specification shall be a product which is qualified for listingon the applicable qualified products list.3.4 Materials . Materials shall be as specified in UL Standard 498. All current carrying parts of the connectors shallbe ma
19、de of copper or copper alloy. The terminal screws and pressure plates may be of other materials. Thegrounding contact is considered current carrying; however, the remaining portion of the grounding circuit may be ofother metal.3.5 Design and construction . Connectors shall be of the design, construc
20、tion, and physical dimensions asspecified herein (see 3.1) and in NEMA WD 6. Connectors shall be general grade (see 1.2.1) or hospital grade(see 1.2.2) as specified in 3.1 (see section 6). If the specification sheet does not specify the grade, the connectorshall be of general grade. Plugs shall be o
21、f a solid face “dead -front“ construction with no insulating discs permitted.Plugs and cable outlets shall be of the non -armored type. Exposed metallic cable clamps are not permitted.3.5.1 Mounting flanges and plates . Unless otherwise specified (see 3.1), mounting flanges and plates of ferrousmate
22、rial shall be protected against corrosion by either galvanizing, electrodepositing with cadmium, chromium,copper, nickel, silver, zinc, or chromizing. Painting alone is not acceptable.Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C-596G/GEN33.5.1
23、.1 Mounting screws . Unless otherwise specified (see 3.1), each connector receptacle shall be furnished withscrews for mounting the device to an outlet box or other enclosure. The screws shall be of the length and type asrequired in UL 498.3.5.2 Terminals . All terminals on connectors specified here
24、in are for use with copper or copper clad aluminum wireonly.3.5.2.1 Screw terminals . Terminals shall receive and hold properly the wire required for the current marked on theconnector. Receptacles marked 15 amperes or less shall receive and hold No. 12 American Wire Gauge (AWG)wire. Terminals on re
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAWC596G1995CONNECTORELECTRICALPOWERGENERALSPECIFICATIONFOR 电源 连接器 通用 规格 PDF

链接地址:http://www.mydoc123.com/p-701563.html