1、AMSC N/A FSC 5950 MIL-PRF-27/66E 3 December 2010 SUPERSEDING MIL-PRF-27/66D 18 February 1986 PERFORMANCE SPECIFICATION SHEET TRANSFORMERS, POWER, 250 VOLT AMPERES, 400 HZ, ELECTROSTATIC SHIELDED This specification is approved for use by all Departments and Agencies of the Department of Defense. The
2、requirements for acquiring the transformers described herein shall consist of this specification and MIL-PRF-27. NOTES: 1. Dimensions are in inches. 2. Metric equivalents are given for general information only. 3. Tolerance on terminal position dimensions is .015 (0.38 mm). 4. Marking shall be on th
3、e side of the case. 5. Secondary electrical values shall be marked as specified in table I, as applicable. FIGURE 1. Dimensions and configuration. INCH-POUND Inches mm .031 0.79 .164 4.17 .250 6.35 .344 8.74 .375 9.52 .390 9.91 2.000 50.80 2.250 57.15 2.875 73.02 Provided by IHSNot for ResaleNo repr
4、oduction or networking permitted without license from IHS-,-,-MIL-PRF-27/66E 2 REQUIREMENTS: (When numbers in parentheses i.e. (1-2) are used, they indicate the winding and the extreme terminals of the winding.) Electrical ratings: See table I. Primary voltage (1-2): 115 volts 10 percent, 400 Hz 5 p
5、ercent. Design and construction: Dimensions and configuration: See figure 1. Weight: 30 ounces, maximum. Duty cycle: Continuous. Case: Metal enclosed. Material: Steel. Altitude: 70,000 feet, maximum. Operating temperature range: -55C to +130C maximum. Terminals: Feed thru. Terminal height: .390 inch
6、 (9.91 mm), maximum. Terminal strength: Method 211 of MIL-STD-202, test condition A, 5 pounds. Dielectric withstanding voltage: At sea level: 2.8 times the maximum working voltage specified in table I. At reduced barometric pressure: 1.25 times the maximum working voltage specified in table I. Elect
7、rical characteristics: No load: With 115 volts, 400 Hz across (1-2): Current in (1-2) shall not exceed 125 mA rms. Rated load: With 115 volts, 400 Hz across (1-2) and a resistive load with current as specified in table I in (3-5), the voltage across (3-5) shall be as specified in table I. Efficiency
8、: 95 percent minimum at rated load. Electrostatic shielding: The voltage ratio shall be a minimum of 5 to 1 at 20 kHz. Polarity: Additive with terminals 2 and 3 connected. Regulation: 100)()()(xloadratedVoltageloadratedVoltageloadnoVoltage Shall not exceed 2 percent. Phase shift: 1.0 electrical degr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAMILPRF2766E2010TRANSFORMERSPOWER250VOLTAMPERES400HZELECTROSTATICSHIELDEDPDF

链接地址:http://www.mydoc123.com/p-692784.html