DLA MIL-DTL-15109 D (1)-2013 RESISTORS AND RHEOSTATS NAVAL SHIPBOARD.pdf
《DLA MIL-DTL-15109 D (1)-2013 RESISTORS AND RHEOSTATS NAVAL SHIPBOARD.pdf》由会员分享,可在线阅读,更多相关《DLA MIL-DTL-15109 D (1)-2013 RESISTORS AND RHEOSTATS NAVAL SHIPBOARD.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Comments, suggestions, or questions on this document should be addressed to: DLA Land and Maritime, ATTN: VAT, Post Office Box 3990, Columbus, Ohio 43218-3990 or by email Resistordla.mil. Since contact information can change, you may want to verify the currency of this address information using the
2、ASSIST Online database at https:/assist.dla.mil/. AMSC N/A FSC 5905 INCH-POUND MIL-DTL-15109D w/Amendment 1 7 November 2013 SUPERSEDING MIL-DTL-15109D 14 June 2001 DETAIL SPECIFICATION RESISTORS AND RHEOSTATS, NAVAL SHIPBOARD This specification is approved for use by all Departments and Agencies of
3、the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers Class III shockproof resistors and rheostats for Naval shipboard service. 1.2 Classification. Resistors and rheostats of the following forms, as specified (see 6.2): Resistors: Form EW - Exposed wire or ribbon Form IW - Embedde
4、d wire or ribbon Form G - Grids or strips Form R - Ribbon Rheostats: Form EW - Exposed wire or ribbon Form P - Plate 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4 and 5 of this specification. This section does not include documents cited in
5、other sections of this specification or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements documents cited in sections 3, 4 and 5 of this specific
6、ation, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards, and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cit
7、ed in the solicitation (see 6.2). DEPARTMENT OF DEFENSE SPECIFICATION MIL-S-901 - Shock Tests, H.I. (High-Impact); Shipboard Machinery, Equipment and Systems, Requirements for MIL-E-917 - Electric Power Equipment Basic Requirements Provided by IHSNot for ResaleNo reproduction or networking permitted
8、 without license from IHS-,-,-MIL-DTL-15109D w/Amendment 1 2 DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1 - Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II - Internally Excited) (Copies of these documents are available online at http:/quicksearch.dla.mil or from the
9、 DLA Document Services, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094). 2.3 Non-Government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of the documents cited in the solicitation or contract (
10、see 6.2). AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) ASTM B117 - Standard Practice for Operating Salt Spray (Fog) Apparatus (DOD adopted) (Copies of these documents can be obtained online at http:/www.astm.org/ or by contacting ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Co
11、nshohocken, PA, 19428-2959). NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) NEMA ICS 1 - Industrial Control and Systems, General Requirements (Copies of this document may be purchased from the National Electrical Manufacturers Association, 1300 North 17th Street, Suite 1847, Rosslyn, Virginia,
12、 United States, 22209. http:/www.nema.org/) 2.4 Order of precedence. Unless otherwise noted herein or in the contract, in the event of a conflict between the text of this document and the references cited herein (except for related specification sheets), the text of this document takes precedence un
13、less otherwise noted. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 Qualification. Resistors and rheostats furnished under this specification shall be products which are authorized by the qualifying ac
14、tivity for listing on the applicable qualified products list at the time of award of contract (see 4.2 and 6.3). 3.2 General requirements. Resistors and rheostats shall conform to MIL-E-917 and NEMA ICS 1 as specified herein. 3.2.1 Total resistance and tolerance. The total resistance of resistors an
15、d rheostats shall not differ from the design value by more than 10 percent. A variation of 20 percent will be permitted from the design values of any step or section. 3.2.2 Resistance value deviations. All maximum deviations as specified in this section are to be considered absolute limits with the
16、exception of the contact resistance adjustment. 3.3 Characteristics. Resistors and rheostats shall have the following characteristics, as specified (see 6.2f). 3.3.1 Voltage. Resistors and rheostats shall be designed for a maximum circuit voltage of 150, 300 or 600 volts alternating current (ac) roo
17、t mean square (rms) or direct current (dc) (see 6.2g). 3.3.2 Mounting. Resistor assemblies and rheostats shall be constructed for bulkhead, deck, or switchboard mounting, as specified. Individual resistor units shall be furnished with mounting brackets, mounting bolts for single-end mounting, or wit
18、hout mounting hardware, as specified (see 6.2h). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-15109D w/Amendment 1 3 3.3.3 Duty. Unless otherwise specified, resistors and rheostats shall be constructed for continuous duty. If other duty, i
19、n the case of resistor applications, is required, NEMA ICS 1 standards for the specified duty shall apply (see 6.2i). 3.3.4 Ambient temperature. Unless otherwise specified (see 6.2), resistors and rheostats shall be constructed for a 50 degrees Celsius (OC) ambient. Where the normal temperature of t
20、he surrounding atmosphere exceeds 50OC, the rating shall be based on the specified ambient (see 6.2j). 3.3.5 Enclosures. Enclosures shall be open or drip proof, as specified (see 6.2k). Enclosures shall be furnished for resistors only when specified. If not specified, drip proof enclosures shall be
21、furnished for bulkhead mounted rheostats and open enclosures for switchboard mounted rheostats. Drip proof enclosures shall meet requirements of NEMA ICS 1 when inclined to any angle not greater than 45 degrees from the normal position and conform to the requirements of 3.5.4. 3.3.6 Temperature rise
22、. Temperature rises shall not exceed the values specified in NEMA ICS 1. 3.4 Construction. 3.4.1 Internal connections. Connections that are embedded in resistors and rheostats shall be soldered, welded, or brazed. Low melting solders that would be adversely affected by the operating temperature of t
23、he resistor or rheostat shall not be used. Connections shall be mechanically secure and electrically continuous. External connections to the resistors or rheostat shall be so that the heat from the resistor will not adversely affect the connection. 3.4.2 Rheostats. Rheostats shall be constructed to
24、ensure reliable operation under severe service. Springs shall not be stressed near or beyond their fatigue limits. Springs shall not carry current. Exposed metallic parts, other than terminals of plate type rheostats, shall be grounded. Two-terminal type rheostats shall be so connected internally th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAMILDTL15109D12013RESISTORSANDRHEOSTATSNAVALSHIPBOARDPDF

链接地址:http://www.mydoc123.com/p-689970.html