1、Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any data that may improve this document should be sent to: STDZNMGTdla.mil or Defense Supply Center Richmond (DSCR), ATTN: DSCR-VEB, 8000 Jefferson Davis Highway, Richmond, VA 23297-5616. AMSC N/A FSC 5940 INCH-POUN
2、D A-A-59559A 22 March 2007 SUPERSEDING A-A-59559 23 June 2000 COMMERCIAL ITEM DESCRIPTION POST, BINDING, ELECTRICAL, WATERPROOF (INSULATED), DUAL O-RING SEAL The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SCOPE. This commer
3、cial item description (CID) covers an insulated electrical binding post used as a wiring termination on terminal boards and test set panels. 2. CLASSIFICATION. The electrical binding post shall be classified and identified by the types in accordance with the characteristics specified in table I. The
4、 selected types of products to be supplied shall be specified in the acquisition order (see 7.3(b). TABLE I. Electrical binding post dimensions. Dimensions Type Cap color A1 B1 (0.015)C1 (+0.016/-0.049) I Black 2.000 (max.) 1.950 (min.) 1.000 0.719 II Red 2.000 (max.) 1.950 (min.) 1.000 0.719 1See f
5、igure 1. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59559A 2 3. SALIENT CHARACTERISTICS 3.1 Components. The electrical binding post shall be similar to the one shown in figure 1. The product shall consist of the binding post, insulated sprin
6、g-loaded cap and mounting washers, o-rings, and all mounting hardware. 0.0620.125SOLDER DIP0.125HEX NUTNO. 10-32UNF-2B0.0000.003DEPRESS CAP TOINSERT WIRE(SEE NOTE 2)0.062 MAX WIREACCOMMODATION“O“ RINGS 0.302 (PANEL THICKNESS 0.062 TO 0.125 INCHES)SEE NOTE 2SPLITLOCK WASHERNO. 10-32UNF-2APOST 0.5830.
7、010SEE NOTE 2NO. 10 MED, BRASS WASHERACBNOTES: 1. The figure depicts only general characteristics and is not intended to limit specific manufacturing processes. 2. This is the insulated portion. 3. Dimensions (listed in table I) are in inches. Tolerance is 0.015 inch unless otherwise shown. FIGURE 1
8、. Binding post configuration. 3.2 Materials. 3.2.1 Metal. Unless specified otherwise in the acquisition order (see 7.3(c), the current-carrying portions of the binding post shall be brass conforming to the requirements of the ASTM B16/B 16M, “Standard Specification for Free-Cutting Brass Rod, Bar an
9、d Shapes for Use in Screw Machines“. 3.2.2 Finish. Unless otherwise specified in the acquisition order (see 7.3(d), metal portions of the binding post shall be nickel plated in accordance with the SAE AMS-QQ-N-290, “Nickel Plating (Electrodeposited)“. 3.2.2.1 Solder coating. Unless otherwise specifi
10、ed in the acquisition order (see 7.3(e), the solder terminal end shall be hot solder dipped/coated. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59559A 3 3.2.3 Insulation. The material used for the insulated portions of the binding post shall
11、be specified in the acquisition order (see 7.3(f). The insulated washers of the binding post shall be natural/milky white unless otherwise specified in the acquisition order (see 7.3(g). The insulated cap shall be the color listed in table I. 3.2.4 Cap and cap spring. The cap shall be insulated and
12、non-removable. The strength of the cap spring shall permit the cap to be depressed using a force of 5 to 10 pounds. 3.3 Dielectric withstanding voltage. When specified in the acquisition order (see 7.3(h), the insulated binding post shall be tested in accordance with method 301 of MIL-STD-202, “Test
13、 Method Standard for Electronic and Electrical Component Parts“. The following details and exceptions shall apply: a. The binding post shall be mounted on a 0.125 inch thick bare metal test mount. The binding post shall be mounted with insulators and o-rings by applying a torque of 10 2 inch-pounds.
14、 b. The magnitude of the test voltage shall be 1,200 VAC RMS. The harmonic content of the voltage shall not exceed 0.50 percent of the fundamental waveform. c. The duration of application of test voltage shall be 1 minute 5 seconds. d. The test voltage shall be applied between the conductor accommod
15、ation and the metal test mount. e. The binding post shall show no evidence of damage, arcing, or breakdown after application of the test voltage. 3.4 Contact resistance. When specified in the acquisition order (see 7.3(i), the binding post contact resistance shall be tested as follows: a. A solid AW
16、G size 16 copper conductor shall be inserted in the contact cavity. b. A test current of 1 ampere shall be passed through the contact. c. Contact resistance shall be determined by measuring the potential drop between the extreme terminal end of the binding post and the copper conductor. d. The poten
17、tial drop shall not be greater than 0.002 V. 3.5 Solderability of solder terminal end. When specified in the acquisition order (see 7.3(j), the solderability of the binding post solder terminal end shall be tested in accordance with method 208 of MIL-STD-202. 3.6 Insulation resistance. When specifie
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAAA59559A2007POSTBINDINGELECTRICALWATERPROOFINSULATEDDUALORINGSEAL 密封 绝缘 防水 电气 接线柱 PDF

链接地址:http://www.mydoc123.com/p-687529.html