1、July 2009 Translation by DIN-Sprachendienst.English price group 10No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 9
2、1.140.30!$mzp“1748777www.din.deDDIN 1946-7Ventilation and air conditioning Part 7: Ventilation systems in laboratoriesEnglish translation of DIN 1946-7:2009-07Raumlufttechnik Teil 7: Raumlufttechnische Anlagen in LaboratorienEnglische bersetzung von DIN 1946-7:2009-07Ventilation Partie 7: Systmes de
3、 ventilation pour laboratoiresTraduction anglaise de DIN 1946-7:2009-07SupersedesDIN 1946-7:1992-06www.beuth.deDocument comprises pagesIn case of doubt, the German-language original shall be considered authoritative.1606.11 DIN 1946-7:2009-07 Contents Page Foreword. 3 Introduction 4 1 Scope . 5 2 No
4、rmative references . 5 3 Terms and definitions 5 4 Tasks of the HVAC system 8 5 Planning and design of HVAC systems . 9 5.1 General. 9 5.2 Planning criteria 9 5.3 Air volume flow rates . 10 5.3.1 General. 10 5.3.2 Supply air volume flow rates for all rooms as in 5.3.3 to 5.3.8 10 5.3.3 Extract air v
5、olume flow for laboratory rooms10 5.3.4 Extract air volume flow rates for solvent storage rooms . 11 5.3.5 Extract air volume flow for chemicals storage rooms 11 5.3.6 Extract air volume flow for rooms for pressurized gas cylinder storage . 11 5.3.7 Extract air volume flow for temperature-controlled
6、 rooms 11 5.3.8 Extract air volume flow for storage of cryogenic gases. 12 5.4 Fume cupboards. 12 5.5 Other extract air equipment. 12 5.6 Air flows within the room. 13 5.7 Quality of room air 13 6 Supply air and extract air systems . 13 6.1 General. 13 6.2 Supply air system . 13 6.3 Extract air syst
7、em. 14 6.3.1 Air routing 14 6.3.2 Retainment and filter systems. 14 6.3.3 Maintenance and repair 14 6.3.4 Explosion protection 14 7 Sound pressure level . 15 8 Special requirements for HVAC systems in microbiology laboratories . 15 9 Labelling 15 Bibliography . 16 2 A comma is used as the decimal ma
8、rker. DIN 1946-7:2009-07 Foreword This standard has been prepared by Working Committee NA 055-02-01 AA Abzge und Laborlufttechnik of the Normenausschuss Laborgerte und Laboreinrichtungen (FNLa) (Laboratory Devices and Installations Standards Committee) together with the Working Committee NA 041-02-5
9、3 AA Sonderrume of the Normenausschuss Heiz- und Raumlufttechnik (Heating and Ventilation Technology Standards Committee). Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. DIN and/or DKE shall not be held responsible for identifyin
10、g any or all such patent rights. DIN 1946 Ventilation and air conditioning comprises: Part 3: Air conditioning of passenger cars and commercial vehicles Part 4: VAC systems in buildings and rooms used in the health care sector Part 6: Ventilation for residential buildings General requirements, requi
11、rements for measuring, performance and labelling, delivery/acceptance (certification) and maintenance Part 7: Ventilation systems in laboratories Amendments The standard differs from DIN 1946-7:1992-06 as follows: a) requirements have been supplemented with functional aspects; b) air volume flows ha
12、ve been adapted to laboratory functions in a more flexible manner; c) air volume flows for adjacent rooms and special rooms are now to be taken into consideration in design and planning; d) safety requirements have been aligned with the 2005 edition of the Gefahrstoffverordnung GefStoffV (German Haz
13、ardous Substances Ordinance); e) requirements for heating, ventilation and air conditioning (HVAC) systems in microbiological laboratories are now included; f) new European Standards on the ventilation of buildings and for saving energy have been taken into consideration and referred to. Previous ed
14、itions DIN 1946-7: 1992-06 3 DIN 1946-7:2009-07 Introduction The operation of heating, ventilation and air conditioning (HVAC) systems in laboratory buildings or in individual laboratory rooms requires particular care and attention due to their relevance to safety. This applies for users of ventilat
15、ion and air conditioning systems as well as for operators of laboratory buildings. This standard supports the planning, execution and maintenance of such HVAC systems. Special expertise with regard to workflows in laboratories and the modes of operation of technical laboratory equipment is required
16、particularly because of the many possible interfaces to safety-relevant extract air equipment. 4 DIN 1946-7:2009-07 1 Scope This standard applies to the planning and execution of heating, ventilation and air conditioning systems (hereinafter referred to as HVAC systems) for industrial laboratories a
17、nd laboratories in universities and institutes. It also applies to HVAC systems in science classrooms in schools if these are equipped with such a system. This standard does not stipulate, however, when laboratories or science classrooms in schools are to be equipped with a HVAC system; for this pur
18、pose superordinate rules and regulations apply that shall be taken into account. This standard only specifies the tasks of and requirements for HVAC systems. This standard not only applies to laboratories in a narrower sense, but also to laboratory-related rooms in which work with hazardous substanc
19、es is performed. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. DIN EN 12
20、128:1998-05, Biotechnology Laboratories for research, development and analysis Containment levels of microbiological laboratories, areas of risk, localities and physical safety requirements DIN EN 12792:2004-01, Ventilation for buildings Symbols, terminology and graphical symbols DIN EN 13779:2007-0
21、9, Ventilation for non-residential buildings Performance requirements for ventilation and room conditioning systems DIN EN 14175-1:2003-08, Fume cupboards Part 1: Vocabulary DIN EN 15251, Indoor environmental input parameters for design and assessment of energy performance of buildings addressing ai
22、r quality, thermal environment, lighting, and acoustics VDI 2081 Part 1, Noise generation and noise reduction in air-conditioning systems 3 Terms and definitions For the purposes of this document the terms and definitions according to DIN EN 12792 and the following apply. For the different types of
23、air in a laboratory or in a laboratory building (such as extract air, recirculation air, exhaust air) DIN EN 13779:2007-09, Table 2 applies. 3.1 laboratory spatially defined area with specific technical requirements for ventilation NOTE In a laboratory, tasks are usually carried out during which pos
24、sible hazards, e.g. those generated by substances or procedures, can be kept under control. A HVAC system is usually essential for such tasks. 3.2 useable laboratory floor space floor space of a laboratory room or a laboratory area; not included as useable laboratory floor space are constructionally
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DIN194672009VENTILATIONANDAIRCONDITIONINGPART7VENTILATIONSYSTEMSINLABORATORIES 通风 空气调节 部分 实验室 系统 PDF

链接地址:http://www.mydoc123.com/p-654357.html