COE CE-R-04 2-1985 REINFORCED MASONRY《配筋砌体》.pdf
《COE CE-R-04 2-1985 REINFORCED MASONRY《配筋砌体》.pdf》由会员分享,可在线阅读,更多相关《COE CE-R-04 2-1985 REINFORCED MASONRY《配筋砌体》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、DEPARTMENT OF THE ARMY 3515789 0013732 157 = Y OFFICE OF THE CHIEF OF ENGINEERS O - SECTION 4 REINFORCED MASONRY INDEX 1. MATERIALS 2. HANDLING AND STORAGE 3. SAMPLES 4. ERECTION 5. PROTECTION 6. POINTING AND CLEANING CE-R-04.2 July 1985 Superseding CE-R-04.2 September 1979 4 -i - Provided by IHSNot
2、 for ResaleNo reproduction or networking permitted without license from IHS-,-,-m 3515789 0033733 093 m CE-R-04 . 2 N1 December 1985 SECTION 4 - REINFORCED MASONRY 1. MATERIALS: (l)(n) 1.1 Brick: Brick modular jumbo sized, ASTM C 216-84, Grade SW (1) Hollow brick, n. by - in., ASTM C 652-84, Grade S
3、W for face brick (1) and ASTM C 62-84a for backup and filler. Face brick texture matte rug velour stone face, color range red through brown white through medium gray pastel yellow through pink through 1, in a blend of four to six colors. Concrete brick, ASTM C 55-75 (R 1980), Type I, Grade N-l. 1 Fu
4、rnish special shapes and sizes as required. (n) 1.2 Concrete masonry units: ASTM C 90-75 (R 1981), Type I, Grade N-1, compressive strength psi. Furnish special shapes and sizes as required. Use bullnose3 unit in vertical external corners, for exposed interior construction except at window and door j
5、ambs. 1.3 Mortar: ASTM C 270-84, Type S. 1.4 Grout: ASTM C 476-83. Minimum 28-day compressive strength of 2,000 1 for coarse aggregates. Use fine aggregate for voids having least dimension up to 2 in.; fine or coarse aggregste for voids or cores having least dimension of 2- to 3-in.; and coarse aggr
6、egate for voids or cores having least dimension greater than 3 in. 3 psi tested per ASTM C 91-83a for fine aggregates and ASTM C 39-83b 1.5 Control joint key: Solid natural or synthetic rubber, plastic or Minimum hardness 70 durometer per ASTM D 2240-85. rubber-like material. Minimum shear section t
7、hickness 5/8-in. with 3/8-in. flange. 1.6 Joint reinforcement: Wire, ASTM A 82-79, not lighter than 9 gage 8 gage, 3/16-in. zinc-coated per ASTM A 116-81, Class 1. Lap reinforcement shall be 6 inches for deformed or 12 inches for smooth wires. The outermost longitudinal wres shall be spaced 2 inches
8、 plus or minus 1/8-inch less than the noninal thickness of the wall in which it is placed. 1.6.1 Single wythe walls: Joint? reinforcement in single wythe walls shall be ladder or truss design having two or more smooth or deformed longitudinal wires. The distance between contacts of crosswires with e
9、ach longitudinal wire shall not exceed 6 inches for smooth longitudinal wires and 16 inches for deformed 1Oitudil wire8 0 1.6.2 Composite or cavity walls: For ladder or truss types, the distance between contacts of crosswires Joint reinforcement in composite walls shall be ladder, trues or rbrace de
10、sign having three or more deformed longitudinal wires. with each longitudinal wire shall not exceed 16 inches. x-bracing shall not exceed 24 inches on centers. and one vire in each face shell of the back up unit. Contractor, joint reinforcement may consist of two longitudinal wires with box tits upa
11、ced not over 16 inches on centers. Intersections of Center one wire in facing unit At the option of the Box ties shall be 4 inch nominal 4 -1 - PROBLEM HARD COPL Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-CE-R-O4 2 N1 December 1985 (1) width and
12、 of length to approximately center upon exterior facing. 1.7 Precast concrete items: Precast concrete lintels, copings, window sills, and splash blocks shall be factory made units reinforced as required. 1.8 Reinforcing steel bars and rods: ASTM A 615-84a, Grade 40 ao. 1.9 Anchors, ties, and centeri
13、ng devices: Ferrous metal, zinc-coated per ASTM A 153-82, Class 8-2. 1.10 Insulation for exterior masonry walls: Specified in SECTION: BUILDING INSULATION. 4 -la - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-m 3535789 0033735 9bb m CE-R-04.2 July
14、 1985 O (n 1.11 Material samples: Material samples shall include anchors, - ties, bricks, concrete units, joint reinforcements and aggregates. 2. HANDLING AND STORAGE: Prevent damaging exposure to weather, or contact with soil. 3. SAMPLES: Furnish brick sample panels to illustrate the material speci
15、fied and to show full range of color and texture. 4. ERECTION: 4.1 General: Do not erect when the ambient temperature is below 40 degrees F. Keep masonry units free from ice and snow and a minimum temperature of 40 degrees F. when laid. Maintain temperature of mortar or grout between 70 degrees F an
16、d 90 degrees F., and mixing water not over 160 degrees F. Maintain air around masonry at 40 degrees F for 72 hours after construction. Do not build on frozen work. Lay plumb, true to line, in level courses accurately spaced with a story pole. Unless otherwise shown, fill spaces around metal doorfram
17、es, and other built-in items, solidly with mortar. Cut and fit masonry units with a masonry saw. Maintain alinement within 1/8-in. allowance between exposed faces of adjacent units. Lay horizontal joint reinforcement in bed joints spaced 16 in. apart except where otherwise shown. Erect exposed units
18、 to show no detracting imperfections when viewed from eye level at a distance of 5 ft. in normal daylight. Set steel angle lintels to bear equally on supports, to line and level, and flash as indicated. In cavity wall and composite wall construction lay up the inner and outer wythes together. Concre
19、te-masonry-unit and concrete-brick surfaces shall be dry-brushed at the end of each days work and after any required pointing. O 4.2 Joints: 4.2.1 Exposed joints: All joints shall be tooled slightly concave after the mortar has taken its initial set. Joints shall be 318-in. nominal except that head
20、joints may have slight variations to maintain bond. 4.2.2 Calked joints: Control joints, joints between metal frames and masonry and other joints indicated shall have mortar raked out 3/4-in. deep and left ready for calking. 4.3 Unfinished work: Step back for joining with new work. Remove loose mort
21、ar and clean joint before laying new work. Protect masonry surfaces not being worked upon. 4.4 Mortar and grout: Discard material that has stiffened due to chemical reaction or is not used within 2 1/2 hours after mixing when air temperature is 80 degrees F. or above; and otherwise when not used wit
22、hin 3 112 hours. Mortar that has stiffened because of evaporation may be retempered as needed. 4.5 Brick facing: Lay in running bond with the better race of the brick exposed. Bed fully in mortar with full shoved head joints. Set head joints . in a plumb line in alternate courses. O 4 -2 Provided by
23、 IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3535789 O033736 8T2 CE-R-04.2 July 1985 4.6 Concrete masonry units: Do not wet before laying. Apply a full bed of mortar under face shells of units but not across webs, except that full mortar beds are required un
24、der units at starting courses on footing-, solid founda- tion walls, beams and lintels and in load-bearing piers, columns and pilasters and where voids are filled. Bond each course at corners. Fill voids with mortar in units at door and window jambs and in units at supports for plumb- ing, heating,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- COECER0421985REINFORCEDMASONRY 配筋砌体 PDF