ASTM E119-2014 red 5984 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf
《ASTM E119-2014 red 5984 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E119-2014 red 5984 Standard Test Methods for Fire Tests of Building Construction and Materials《建筑结构和材料防火试验的标准试验方法》.pdf(47页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E119 12aE119 14 An American National StandardStandard Test Methods forFire Tests of Building Construction and Materials1This standard is issued under the fixed designation E119; the number immediately following the designation indicates the year oforiginal adoption or, in the case of re
2、vision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThe performa
3、nce of walls, columns, floors, and other building members under fire-exposureconditions is an item of major importance in securing constructions that are safe, and that are not amenace to neighboring structures or to the public. Recognition of this is registered in the codes ofmany authorities, muni
4、cipal and other. It is important to secure balance of the many units in a singlebuilding, and of buildings of like character and use in a community; and also to promote uniformityin requirements of various authorities throughout the country. To do this it is necessary that thefire-resistive properti
5、es of materials and assemblies be measured and specified according to a commonstandard expressed in terms that are applicable alike to a wide variety of materials, situations, andconditions of exposure.Such a standard is found in the test methods that follow. They prescribe a standard exposing fire
6、ofcontrolled extent and severity. Performance is defined as the period of resistance to standard exposureelapsing before the first critical point in behavior is observed. Results are reported in units in whichfield exposures can be judged and expressed.The test methods may be cited as the “Standard
7、Fire Tests,” and the performance or exposure shallbe expressed as “2-h,” “6-h,” “12-h,” etc.When a factor of safety exceeding that inherent in the test conditions is desired, a proportionalincrease should be made in the specified time-classification period.1. Scope Scope*1.1 The test methods describ
8、ed in this fire-test-response standard are applicable to assemblies of masonry units and to compositeassemblies of structural materials for buildings, including loadbearing and other walls and partitions, columns, girders, beams,slabs, and composite slab and beam assemblies for floors and roofs. The
9、y are also applicable to other assemblies and structuralunits that constitute permanent integral parts of a finished building.1.2 It is the intent that classifications shall register comparative performance to specific fire-test conditions during the periodof exposure and shall not be construed as h
10、aving determined suitability under other conditions or for use after fire exposure.1.3 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire hazar
11、d or fire risk assessment of the materials,products or assemblies under actual fire conditions.1.3 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required fo
12、r fire hazard or fire risk assessment of the materials,products or assemblies under actual fire conditions.1.4 These test methods prescribe a standard fire exposure for comparing the test results of building construction assemblies. Theresults of these tests are one factor in assessing predicted fir
13、e performance of building construction and assemblies. Applicationof these test results to predict the performance of actual building construction requires the evaluation of test conditions.1 These test methods are under the jurisdiction of ASTM Committee E05 on Fire Standards and are the direct res
14、ponsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved July 15, 2012Oct. 1, 2014. Published September 2012November 2014. Originally approved in 1917. Last previous edition approved in 2012 asE119 12.E119 12a. DOI: 10.1520/E0119-12A.10.1520/E0119-14.These test methods, of whic
15、h the present standard represents a revision, were prepared by Sectional Committee on Fire Tests of Materials and Construction, under thejoint sponsorship of the National Bureau of Standards, the ANSI Fire Protection Group, and ASTM, functioning under the procedure of the American National Standards
16、Institute.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult
17、 prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA
18、 19428-2959. United States11.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.6 This standard does not purport to address all of the
19、 safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.1.7 The text of this standard references notes and footnotes which provid
20、e explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2C569 Test Method for Indentation Hardness of Preformed Thermal Insulations (Withdrawn 1988)3D6513 Practice for C
21、alculating the Superimposed Load on Wood-frame Walls for Standard Fire-Resistance TestsE176 Terminology of Fire StandardsE177 Practice for Use of the Terms Precision and Bias in ASTM Test MethodsE691 Practice for Conducting an Interlaboratory Study to Determine the Precision of a Test MethodE814 Tes
22、t Method for Fire Tests of Penetration Firestop SystemsE2226 Practice for Application of Hose Stream3. Terminology3.1 DefinitionsFor definitions of terms found in this test method, refer to Terminology E176.4. Significance and Use4.1 These test methods are intended to evaluate the duration for which
23、 the types of building elements noted in 1.1 contain a fire,retain their structural integrity, or exhibit both properties during a predetermined test exposure.4.2 The test exposes a test specimen to a standard fire controlled to achieve specified temperatures throughout a specified timeperiod. When
24、required, the fire exposure is followed by the application of a specified standard fire hose stream applied inaccordance with Practice E2226. The test provides a relative measure of the fire-test-response of comparable building elementsunder these fire exposure conditions. The exposure is not repres
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME1192014RED5984STANDARDTESTMETHODSFORFIRETESTSOFBUILDINGCONSTRUCTIONANDMATERIALS 建筑结构 材料 防火 试验 标准

链接地址:http://www.mydoc123.com/p-526890.html