ASTM D6157-1997(2011) 7500 Standard Practice for Determining the Performance of Oil Water Separators Subjected to a Sudden Release《测定突然释压时油 水分离器性能的标准操作规程》.pdf
《ASTM D6157-1997(2011) 7500 Standard Practice for Determining the Performance of Oil Water Separators Subjected to a Sudden Release《测定突然释压时油 水分离器性能的标准操作规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6157-1997(2011) 7500 Standard Practice for Determining the Performance of Oil Water Separators Subjected to a Sudden Release《测定突然释压时油 水分离器性能的标准操作规程》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D6157 97 (Reapproved 2011)Standard Practice forDetermining the Performance of Oil/Water SeparatorsSubjected to a Sudden Release1This standard is issued under the fixed designation D6157; the number immediately following the designation indicates the year oforiginal adoption or, in the c
2、ase of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice describes the testing procedure, any nec-essary related apparatus, and the
3、sampling technique to be usedin determining the performance characteristics of an oil/waterseparator subjected to the sudden release of a relatively largequantity of hydrocarbons that may appear in its influent in pureform or at high concentration.1.2 This practice does not address the determination
4、 of theperformance characteristics of an oil/water separator subjectedto surface run-off resulting from rain water draining fromimproved or unimproved land. In this case, refer to PracticeD6104.1.3 This practice does not address the determination of theperformance characteristics of an oil/water sep
5、arator subjectedto a mechanically emulsified influent such as provided by apump.1.4 This practice does not investigate the ability of theseparator to handle debris or suspended solids, that is, grit ortree leaves.1.5 While the effluent may meet code requirements for totaloil and grease content, this
6、 practice does not address thepresence of soluble organics, that is, benzene, toluene, ethyl-benzene and xylene (BTEXs) that may be detected in theeffluent. It also does not make any provisions for the effects ofdetergents, surfactants, soaps or any water soluble matter (thatis, salts) or any portio
7、n of an essentially insoluble matter thatmay be found in solution on separation. (Effects of certainwater soluble chemicals or solids may be investigated byadding them to the water at predetermined constant concentra-tions.)1.6 In order to estimate the effect of water temperature onthe performance o
8、f the separator, the tests described in thispractice must be performed at two water temperatures. Theselected temperatures must be at least 10 C (18 F) apart, withthe temperature ranging from a minimum of 0 C (32 F) to amaximum of 50 C (122 F).1.7 This practice does not make any provisions for theva
9、riation of pH or temperature during a test run. Refer toAppendix X1 for further detail.1.8 This practice can be used with a variety of hydrocar-bons. It adopts No. 2 fuel oil with a density2of 845 kg/m3(52.73 lbm/ft3) and a viscosity2of 1.9 to 4.1 centistokes at40 C (104 F) and SAE 90 lubricating oi
10、l with a density (SeeSAE J313) of 930 kg/m3(58 lbm/ft3) at 15.5 C (60 F) and aviscosity (See SAE J306) of 13.5 to 24 centistokes at 100 C(212 F) as the comparative testing media. It is understood thatthe results obtained from this practice are only directlyapplicable to No. 2 fuel oil and SAE 90 lub
11、ricating oil for thetested concentrations and only careful interpolation or extrapo-lation, or both, is allowed to other hydrocarbons. Low viscosityor high density hydrocarbons or hydrocarbons that contain alarger fraction of highly soluble compounds may need to betested separately.NOTE 1No extrapol
12、ation outside the range of the tested influent oreffluent oil concentrations is allowed as performance may not be linear.Hence, to establish performance at a higher or lower concentration, theseparator shall be tested for that specific condition. In addition, linearitymust be established prior to us
13、ing linear interpolation.1.9 Since regulations are based on effluent total hydrocar-bon content, this practice does not set forth any lower limits onoil particle size for the evaluation of separator efficiency.However, a standardized means for mixing oil and water shallbe specified to ensure repeata
14、bility. It must be noted howeverthat smaller particles, having a greater surface area to volumeratio, rise at a slower rate than their larger counterparts. (GuideF933 requires that 20 % of all oil particles be smaller than orequal to 50 m and IMO MEPC 60 (30) does not mention anyparticle size requir
15、ements but asks the user to avoid emulsioncausing chemicals.)1.10 Although the tests described in this practice intend tosimulate the performance of a separator subjected to a suddenrelease, they do not cover all possible applications. It is the end1This practice is under the jurisdiction of ASTM Co
16、mmittee D19 on Water andis the direct responsibility of Subcommittee D19.06 on Methods for Analysis forOrganic Substances in Water.Current edition approved May 1, 2011. Published June 2011. Originallyapproved in 1997. Last previous edition approved in 2003 as D6157 97 (2003).DOI: 10.1520/D6157-97R11
17、.2Ray E. Bolz and George L. Tuve, CRC Handbook of tables for AppliedEngineering Science, 2ndEdition, CRC Press, 1991.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.users responsibility to determine whether his separation re-quiremen
18、ts are within the scope of this practice.1.11 A product different from the general description hereinmay be tested and found to be in compliance with theperformance criteria set forth.1.12 The values stated in SI units are to be regarded as thestandard. The inch-pound units given in parentheses are
19、forinformation only.1.13 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior t
20、o use.2. Referenced Documents2.1 ASTM Standards:3D1129 Terminology Relating to WaterD3370 Practices for Sampling Water from Closed ConduitsD4281 Test Method for Oil and Grease (FluorocarbonExtractable Substances) by Gravimetric DeterminationF933 Guide for Evaluation of Oil Water Separation Systemsfo
21、r Spilled Oil Recovery Applications (Discontinued2001)4D6104 Practice for Determining the Performance of Oil/Water Separators Subjected to Surface Run-Off2.2 EPA Standards:EPA-413.1, “Methods for Chemical Analysis of Water andWastes,” EPA 600/4-79-0205EPA-413.2, “Methods for Chemical Analysis of Wat
22、er andWastes,” EPA 600/4-79-0205EPA-1664, H-Hexane Extractable Material (HEM) andSilica Gel Treated N-Hexane Extractable Material (SGT-HEM) by Extraction and Gravimetry (Oil and Grease andTotal Petroleum Hydrocarbons) EPA-821-B-94-004B540 CFR Ch. 1 (7-1-95 Edition)52.3 SAE Standards:SAE J306 Axle an
23、d Manual Transmission Lubricant Vis-cosity Classification6SAE J313 Surface Vehicle Recommended Practice (R)Diesel Fuels63. Terminology3.1 Definitions: For definitions of terms used in this prac-tice, refer to Terminology D1129.3.2 Definitions of Terms Specific to This Standard:3.2.1 calibrationthe c
24、ertified evaluation of the accuracyof a measuring instrument as performed by its manufacturer oran independent licensed or accredited third party.3.2.2 contaminated run-offrain water which has collectedoily contaminants from the surfaces it came in contact with andwhich may appear in the influent to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD6157199720117500STANDARDPRACTICEFORDETERMININGTHEPERFORMANCEOFOILWATERSEPARATORSSUBJECTEDTOASUDDENRELEASE

链接地址:http://www.mydoc123.com/p-521720.html