1、Designation:D272903 Designation: D2729 11An American National StandardStandard Specification forPoly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings1This standard is issued under the fixed designation D2729; the number immediately following the designation indicates the year oforiginal adoption or, in
2、 the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope*1.1 T
3、his specification covers requirements and test methods for materials, dimensions, workmanship, chemical resistance, andjoint tightness of poly(vinyl chloride) (PVC) sewer and drain pipe and fittings. Four-inch perforated Perforated pipe is alsocovered; the joint tightness test is not applicable for
4、this product.perforated pipe. A form of marking to indicate compliance withthis specification is also included.1.2 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. These notesand footnotes (excluding those in tables and figures) shall not
5、 be considered as requirements of the specification.1.3 The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for informationonly.1.4 The following precautionary caveat pertains only to the test methods portion, Section 6, of this specification
6、: This standarddoes not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of thisstandard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.2. Referenced Docum
7、ents2.1 ASTM Standards:2D618 Practice for Conditioning Plastics for TestingD1600 Terminology for Abbreviated Terms Relating to PlasticsD1784 Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and Chlorinated Poly(Vinyl Chloride) (CPVC)CompoundsD2122 Test Method for Determining Dimensions o
8、f Thermoplastic Pipe and FittingsD2152 Test Method for Adequacy of Fusion of Extruded Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by AcetoneImmersionD2321 Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow ApplicationsD2412 Test Method for Determina
9、tion of External Loading Characteristics of Plastic Pipe by Parallel-Plate LoadingD2444 Test Method for Determination of the Impact Resistance of Thermoplastic Pipe and Fittings by Means of a Tup (FallingWeight)D2564 Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Sys
10、temsF412 Terminology Relating to Plastic Piping Systems2.2 Federal Standard:Fed. Std. No. 123 Marking for Shipment (Civil Agencies)32.3 Military Standard:MIL-STD-129 Marking for Shipment and Storage33. Terminology3.1 DefinitionsDefinitions used are in accordance with Terminology F412, and abbreviati
11、ons are in accordance withTerminology D1600, unless otherwise specified. The abbreviation for poly(vinyl chloride) is PVC.3.1.1 Pipe having perforations is called perforated pipe; without perforations it is called standard pipe.1This specification is under the jurisdiction of ASTM Committee F17 on P
12、lastic Piping Systems and is the direct responsibility of Subcommittee F17.62 on Sewer.Current edition approved Aug. 10, 2003. Published September 2003. Originally approved in 1968. Last previous edition approved in 1996 as D272996a. DOI:10.1520/D2729-03.Current edition approved Feb. 1, 2011. Publis
13、hed February 2011. Originally approved in 1968. Last previous edition approved in 2003 as D2729 03. DOI:10.1520/D2729-11.2For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer
14、to the standards Document Summary page on the ASTM website.3Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700 Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.1This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indica
15、tion of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be con
16、sidered the official document.*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4. Materials4.1 GeneralThe pipe shall be made from virgin cell 12164 with a minimum tensil
17、e strength of 4000 psi (28 MPa), 12454 or12454 poly(vinyl chloride) compounds, as defined and described in Specification D1784. The fittings shall be made from virginpoly(vinyl chloride) compounds of cell classification PVC 12454, PVC 12454, or PVC 13343. Compounds that have different cellclassifica
18、tion because one or more properties are superior to those of the specified compounds are also acceptable.4.2 Rework MaterialThe manufacturer shall use only his own clean pipe or fitting rework material; the pipe and fittingsproduced shall meet all the requirements of this specification.5. Requiremen
19、ts5.1 Qualification and Referee Testing:5.1.1 Joint TestingJoints made with pipe and fittings or belled end pipe shall show no signs of leakage when tested inaccordance with 6.5. This test is not required for perforated pipe.5.2 Quality Control Testing:5.2.1 WorkmanshipThe pipe and fittings shall be
20、 homogeneous throughout and free from visible cracks, holes, foreigninclusions, or other injurious defects. The pipe shall be as uniform as commercially practical in color, opacity, density, and otherphysical properties.5.2.2 FlatteningThere shall be no evidence of splitting, cracking, or breaking w
21、hen the pipe is tested in accordance with 6.4.5.2.3 Extrusion QualityThe pipe or fittings shall not flake or disintegrate when tested in accordance with Test Method D2152.In the case of fittings, slight flaking in the gate area is acceptable.NOTE 1This test is intended only for use as a quality cont
22、rol test, not for use as a simulated service test.5.2.4 Impact ResistanceThe impact resistance of pipe shall be determined in accordance with Test Method D2444, using a20-lb (10-kg) Tup A and Holder B (flat plate), and shall comply with the requirements given in Table 1 (Note 1). For perforatedpipe,
23、 samples are to be cut and tested at random without regard to hole location, except that the point of impact shall not coincidewith a perforation.5.2.5 Dimensions:5.2.5.1 Pipe and fittings dimensions (for both standard and perforated pipe) shall comply with Table 2, Table 3, or Table 4, asapplicable
24、, when measured in accordance with Test Method D2122.5.2.5.2 Pipe shall be supplied in 10 ft 614-in. laying lengths unless otherwise specified.5.2.5.3 For belled pipe and fittings fabricated from pipe sections, the thickness of the belled section shall be consideredsatisfactory if the bell was forme
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD27292011STANDARDSPECIFICATIONFORPOLYVINYLCHLORIDEPVCSEWERPIPEANDFITTINGS 聚氯乙烯 PVC 污水 配件 标准 规格 PDF

链接地址:http://www.mydoc123.com/p-513430.html