《ASTM C727-2012 Standard Practice for Installation and Use of Reflective Insulation in Building Constructions 《建筑结构中反射隔热的装置及应用标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM C727-2012 Standard Practice for Installation and Use of Reflective Insulation in Building Constructions 《建筑结构中反射隔热的装置及应用标准实施规程》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C727 12Standard Practice forInstallation and Use of Reflective Insulation in BuildingConstructions1This standard is issued under the fixed designation C727; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of l
2、ast revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice has been prepared for use by the designer,specifier, and installer of reflective insulation for use inbui
3、lding construction. The scope is limited to recommenda-tions relative to the use and installation of thermal insulationconsisting of one or more surfaces, having an emittance of 0.1or less such as metallic foil or metallic deposits unmounted ormounted on substrates and facing enclosed air spaces. Th
4、ereflective insulation covered by this practice must meet therequirements of Specification C1224.1.2 This practice covers the installation process from pre-installation inspection through post-installation procedure. Itdoes not cover the production of the insulation materials.1.3 This practice is no
5、t intended to replace the manufactur-ers installation instructions, but shall be used in conjunctionwith such instructions. This practice is not intended to super-cede local, state, or federal codes.1.4 This practice assumes that the installer possesses a goodworking knowledge of the applicable code
6、s and regulations,safety practices, tools, equipment, and methods necessary forthe installation of thermal insulation materials. It also assumesthat the installer understands the fundamentals of constructionthat affect the installation of insulation.1.5 The values stated in inch-pound units are to b
7、e regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of th
8、e user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC1224 Specification for Reflective Insulation for BuildingAp
9、plicationsE96/E96M Test Methods for Water Vapor Transmission ofMaterials2.2 NFPA Standards:NFPA 31 Standard for the Installation of Oil BurningEquipment3NFPA 54 National Fuel Gas Code3NFPA 211 Standard for Chimneys, Fireplaces, and Vents32.3 Code of Federal Regulations:16 CFR 460 Federal Trade Commi
10、ssion Trade RegulationRule: Labeling and Advertising of Home Insulation43. Terminology3.1 DefinitionsFor definitions of terms used in this prac-tice refer to Terminology C1683.2 Descriptions of Terms Specific to This Standard:3.2.1 applicatorthe person or persons who apply thermalinsulation material
11、s in buildings whether or not such person orpersons have contracted with the owner to perform the work.3.2.2 conditioned spaceany space in a building that isserved by a heating or cooling system.3.2.3 ownerthe person, partnership, corporation, agency,or other entity owning the building to be insulat
12、ed whethersuch ownership is by virtue of deed, contract, or any otherinstrument for acquiring legal title under the laws of the statein which the building is located.1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C
13、16.21 on ReflectiveInsulation.Current edition approved May 1, 2012. Published June 2012. Originallyapproved in 1972. Last previous edition approved 2007 as C727 01(2007)1. DOI:10.1520/C0727-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at se
14、rviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.4Federal Register, Vol 70, No. 103. Available
15、 from Department of Housing andUrban Development, 451 7th St. N.W., Washington, D.C. 20410.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.4 reflective insulation systemthermal insulation con-sisting of one or more low emittance
16、surfaces, bounding one ormore enclosed air spaces.3.2.5 vapor retarderany material (membrane or paint)that has a water vapor permeance (perm) rating of 57 ng/(Pasm2) (1 perm) or less, in accordance with Test MethodsE96/E96M, using the desiccant method.4. Significance and Use4.1 This practice recogni
17、zes that effectiveness, safety, anddurability of reflective insulation depends not only on thequality of the insulating materials, but also on proper installa-tion.4.2 There is potential for reduced thermal effectiveness, firerisks and structural deterioration when the insulation is improp-erly inst
18、alled. Specific potential hazards from improper instal-lation include fires caused by (1) heat build-up in recessedlighting fixtures, and (2) deterioration in wood structures andpaint failure due to moisture accumulation.4.3 This practice provides procedures for the installation ofreflective insulat
19、ion in a safe and effective manner. Actualconditions in existing buildings vary greatly and in some casesadditional care must be taken to ensure safe and effectiveinstallation.4.4 This practice presents requirements that are general innature and practical. They are not intended as specific instal-la
20、tion instructions. The user shall consult the manufacturer forspecific applications/installations.5. Safety Precautions5.1 The applicator shall wear proper protective clothing,gloves, and eye protection when installing the insulation.6. Pre-Installation Inspection and Preparation6.1 In areas where i
21、nsulation is to be installed, componentsof the electrical system shall be in good condition. When theelectrical system is found to be faulty, proper inspection andrepair shall be accomplished. (See Note 1.)6.2 Inspect the roof, walls, ceilings, and floors to identifyareas where a previous or existin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC7272012STANDARDPRACTICEFORINSTALLATIONANDUSEOFREFLECTIVEINSULATIONINBUILDINGCONSTRUCTIONS 建筑结构 反射

链接地址:http://www.mydoc123.com/p-508139.html