ASTM C636 C636M-2008 Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels《吸音砖和衬板用金属吊顶系统安装的标准实施规程》.pdf
《ASTM C636 C636M-2008 Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels《吸音砖和衬板用金属吊顶系统安装的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM C636 C636M-2008 Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels《吸音砖和衬板用金属吊顶系统安装的标准实施规程》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 636/C 636M 08Standard Practice forInstallation of Metal Ceiling Suspension Systems forAcoustical Tile and Lay-In Panels1This standard is issued under the fixed designation C 636/C 636M; the number immediately following the designation indicates the yearof original adoption or, in the
2、case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This p
3、ractice covers the installation of suspension sys-tems for acoustical tile and lay-in panels. It is applicable tocontractors whose services are utilized for installing acousticalceilings and to other trades if their activities are responsible forinterference with ceiling components or performance as
4、 de-fined in this recommended practice.1.2 While the practices described in this document haveequal application to rated fire-resistive suspension systems,additional requirements may have been imposed to obtain thefire endurance classification of particular floor-ceiling or roof-ceiling assemblies.
5、These details should be obtained from themanufacturers.1.3 Similarly, additional detailing may be necessary to meetsound attenuation requirements when ceiling plenums extendover contiguous rooms. These, too, should be obtained fromthe manufacturer of the acoustical material employed.1.4 The values s
6、tated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two systems may result in non-conformancewith the standard.1.5
7、 While many of the practices described in this practicehave application to the installation of metal suspension systemsin exterior environments, the specific design of exterior ceilinginstallations requires the review and approval of the architector engineer, or both, who are responsible for the con
8、structionof the building or modifications to an existing building. Whilerecommendations from the manufacturer should be solicited, itremains the final responsibility of the architect/engineer toensure proper application of the materials in question.1.6 This standard does not purport to address of th
9、e safetyconcerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety andhealth practices and determine the applicability of regulatorylimitations prior to use.2. Installation of Components2.1 Hangers:2.1.1 Where acoustical ceilings a
10、re suspended from a struc-ture of wood construction, attach hangers with suitable me-chanical devices either to the bottom edge of the wood joists orto the vertical face of the wood joists near the bottom edge.Holding power tests certified by the manufacturer must beavailable on request for bottom e
11、dge attachment devices.2.1.2 Where acoustical ceilings are suspended from a struc-ture of concrete construction, mount hangers using cast-in-place hanger wires, hanger inserts, or other hanger attachmentdevices whose suitability has been demonstrated by standardconstruction practice or by certified
12、test data.2.1.3 Space hangers for carrying channels or main runners 4ft 0 in. 1200 mm on centers. If local situations allow greatercenter distances between hangers, reduce the load-carryingcapacity of the ceiling suspension system commensurate withthe actual center-to-center hanger distances used. I
13、f localsituations allow lesser center distances between hangers, in-crease the load-carrying capacity of the ceiling suspensionsystem commensurate with the actual center-to-center hangerdistances used.2.1.4 Each suspension wire shall not hang more than one insix out of plumb unless a countersloping
14、wire or horizontalbracing is provided. See Fig. 1 for allowable counterslopingmethods. Suspension wires should not press against ducts orpipes.2.1.5 Hangers formed from galvanized sheet metal stockshall be suitable for suspending carrying channels or mainrunners from an existing structure provided t
15、hat the hangers donot yield, twist, or undergo other objectionable movement.2.1.6 Wire hangers for suspending carrying channels ormain runners from an existing structure shall be prepared froma minimum of No. 12-gage 2.70 mm galvanized, soft-annealed, mild steel wire.1This practice is under the juri
16、sdiction of ASTM Committee E33 on Buildingand Environmental Acoustics and is the direct responsibility of SubcommitteeE33.04 on Application of Acoustical Materials and Systems.Current edition approved April 1, 2008. Published April 2008. Originallyapproved in 1969. Last previous edition approved in
17、2006 as C 636 06.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.2.1.7 In some installations hanger wires are secured tospecial attachment devices that support the carrying channelsor main runners. Such attachment devices shall have
18、certifiedload test data from an independent test laboratory and shall becapable of carrying five times the design load.2.2 Carrying Channels:2.2.1 Install the carrying channels so that they are all levelto within18 in. in 12 ft 3.2 mm in 3600 mm.2.2.2 Perform leveling with the supporting hangers tau
19、t toprevent any subsequent downward movement of the carryingchannels when the ceiling loads are imposed.2.2.3 Local kinks or bends shall not be made in hanger wiresas a means of leveling carrying channels.2.2.4 In installations where hanger wires are wrappedaround carrying channels, the wire loops s
20、hall be tightlyformed to prevent any vertical movement or rotation of themember within the loop.2.3 Main Runners:2.3.1 Install main runners so that they are all level to within14 in. in 10 ft 6 mm in 3000 mm. Determine evaluation oflevelness from measurements taken below hanger points. MakeFIG. 1 Al
21、lowable Countersloping MethodsC 636/C 636M 082the measurements after completion of the ceiling installationsbut prior to building occupancy.2.3.2 Where main runners are supported directly by hang-ers, perform leveling with the supporting hanger taut to preventany subsequent downward movement of the
22、main runnerswhen the ceiling loads are imposed.2.3.3 Local kinks or bends shall not be made in hanger wiresas a means of leveling main runners.2.3.4 In installations where hanger wires are wrappedthrough or around main runners, the wire loops shall be tightlywrapped and sharply bent to prevent any v
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC636C636M2008STANDARDPRACTICEFORINSTALLATIONOFMETALCEILINGSUSPENSIONSYSTEMSFORACOUSTICALTILEANDLAYINPANELS

链接地址:http://www.mydoc123.com/p-507849.html