ASTM C1086-2009 Standard Specification for Glass Fiber Mechanically Bonded Felt Thermal Insulation《玻璃纤维机械粘合油毛毡的热绝缘的标准规范》.pdf
《ASTM C1086-2009 Standard Specification for Glass Fiber Mechanically Bonded Felt Thermal Insulation《玻璃纤维机械粘合油毛毡的热绝缘的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1086-2009 Standard Specification for Glass Fiber Mechanically Bonded Felt Thermal Insulation《玻璃纤维机械粘合油毛毡的热绝缘的标准规范》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1086 09Standard Specification forGlass Fiber Mechanically Bonded Felt Thermal Insulation1This standard is issued under the fixed designation C 1086; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last re
2、vision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers glass fiber unsupportedneedled felt (mechanically bonded) binder-free insulation forthermal insulat
3、ion. This material is used as the thermalinsulation component in the fabrication of insulation systemsfor use on machinery and equipment, such as steam turbines,boilers, boiler feed pumps, and piping at temperatures fromambient up to 1200F (650C).1.2 This standard does not purport to address all of
4、thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.3 The values stated in inch-pound units are to be regardedas stand
5、ard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 See Supplementary Requirements for modifications toparagraphs in this standard when using Specification C 1086 inlieu of the United States Department
6、 of Defense, Departmentof Navy, Naval Sea Systems Command, in Washington, DC.Military Specifications No.(s) MIL-I-16411F.2. Referenced Documents2.1 ASTM Standards:2C 167 Test Methods for Thickness and Density of Blanketor Batt Thermal InsulationsC 168 Terminology Relating to Thermal InsulationC 177
7、Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC 335 Test Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC 390 Practice for Sampling and Acceptance of ThermalInsulation LotsC411 Test Method for H
8、ot-Surface Performance of High-Temperature Thermal InsulationC 518 Test Method for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC 1045 Practice for Calculating Thermal TransmissionProperties Under Steady-State ConditionsC 1058 Practice for Selecting Temperatur
9、es for Evaluatingand Reporting Thermal Properties of Thermal InsulationD 123 Terminology Relating to TextilesD 578 Specification for Glass Fiber Strands2.2 U.S. Federal Standard:FED-STD-191 Textile Test Methods32.3 U.S. Military Standards:MIL-I-16411F Insulation Felt, Thermal, Glass Fiber3MIL-STD-16
10、23 Fire Performance Requirements and Ap-proved Specifications for Interior Finish Materials andFurnishings (Naval Shipboard Use)33. Terminology3.1 Definitions:3.1.1 Terminology C 168 and D 123 shall be considered asapplying to the terms used in this specification.3.1.2 Definitions in Specification D
11、 578 shall be consideredas applying to the terms used in defining glass fiber composi-tion code, process, and fiber diameter.4. Classification4.1 Thermal insulation shall be glass fiber, unsupportedneedled felt insulation, for use on surfaces with temperaturesup to 1200F (650C).5. Ordering Informati
12、on5.1 The purchase order or contract shall specify the follow-ing:5.1.1 Quantity of each thickness (10.1).5.1.2 Any special requirements for nonstandard sizes ordimensions (10.2 and 10.3).5.1.3 Any requirements for certification (19.1).5.1.4 Any special requirements for supplementary testingrequirem
13、ents (9.1). and1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.23 onBlanket and Loose Fill Insulation.Current edition approved May 1, 2009. Published June 2009. Originallyapproved in 1987. Last previous edi
14、tion approved in 2008 as C 1086 08.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Standardiz
15、ation Documents Order Desk, DODSSP, Bldg. 4,Section D, 700 Robbins Ave., Philadelphia, PA 19111-5098, http:/www.dodssp.daps.mil.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5.1.5 Any special packaging information.6. Materials and
16、Manufacture6.1 The material shall consist of 100 % glass fiber needledinto insulation felts without the use of binders. No organicfibers and no glass or mineral shot shall be included in theproduct. It is acceptable for the insulation felt to be composedof laminates formed without the use of binders
17、. The glass fibersshall meet the designation C, Continuous Filament Yarns, inaccordance with Specification D 578 (see Note 1).6.2 The fiber diameter of the glass fiber used in the finalproduct, when determined in accordance with the FilamentDiameter section of Specification D 578 shall conform to th
18、erequirements of Table 1. The certification of the diameter of thefiber is to be provided in one of two ways: either by the feltmanufacturer or by certification of the glass fiber supplier anddocumentation by the manufacturer as to sources of supply.6.3 All materials used shall be asbestos and ceram
19、ic (refrac-tory) fiber-free.NOTE 1The fibers from glass composition designated as “E” glass(electrical glass) in the range from D through G meet the requirements ofTables 1 and 2.7. Physical Properties7.1 When tested in accordance with Section 16, the insula-tion shall conform to the physical requir
20、ements listed in Table2.8. Performance Characteristics8.1 Any of the following conditions can result in damage tothe needled glass fiber insulation:8.1.1 Direct exposure to hydrofluoric acid.8.1.2 Prolonged direct exposure to strong caustics.8.1.3 Prolonged exposure to boiling water.8.2 Conditions o
21、utlined in 8.1 are mentioned only to makethe user aware of such applications that require specialconsideration. Contact the insulation manufacturer for recom-mendations when the above conditions are anticipated.9. Other Requirements9.1 Supplementary requirements include qualification testsand accept
22、ance tests to special standards. These supplementaryrequirements are made by agreement to the supplier and thepurchaser only when specified in the purchase order orcontract.10. Standard Sizes and Dimensions10.1 ThicknessThe insulation shall be furnished in thethicknesses shown in Table 3.10.2 Insula
23、tion LengthUnless otherwise specified, theinsulation shall be furnished in rolls of the lengths given inTable 3.10.3 Insulation WidthUnless otherwise specified (5.1.2),the width of the insulation shall be 60 in. (1.52 m).10.4 Nominal Mass per AreaThe insulation shall befurnished in the mass per area
24、 shown in Table 4.11. Dimensional Tolerances11.1 Thickness ToleranceThe average thickness as deter-mined in accordance with 16.1.1 shall be within 60.125 in.(3.2 mm) of the specified thickness.11.2 Mass per Area ToleranceThe average mass per areashall be within 610 % of that specified in Table 4.11.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC10862009STANDARDSPECIFICATIONFORGLASSFIBERMECHANICALLYBONDEDFELTTHERMALINSULATION 玻璃纤维 机械 粘合 油毛毡

链接地址:http://www.mydoc123.com/p-463301.html