1、7.1CHAPTER 7CONTROL OF MOISTURE AND OTHER CONTAMINANTS IN REFRIGERANT SYSTEMSMoisture 7.1Other Contaminants 7.6System Cleanup Procedure After Hermetic Motor Burnout . 7.8Contaminant Control During Retrofit. 7.9Chiller Decontamination. 7.10MOISTUREOISTURE (water) is an important and universal contami
2、nantM in refrigeration systems. The amount of moisture in a refrig-erant system must be kept below an allowable maximum for satis-factory operation, efficiency, and longevity. Moisture must beremoved from components during manufacture, assembly, and ser-vice to minimize the amount of moisture in the
3、 completed system.Any moisture that enters during installation or servicing should beremoved promptly.Sources of MoistureMoisture in a refrigerant system results from Inadequate equipment drying in factories and service operationsIntroduction during installation or service operations in the fieldLea
4、ks, resulting in entrance of moisture-laden airLeakage of water-cooled heat exchangersOxidation of some hydrocarbon lubricants that produce moistureWet lubricant, refrigerant, or desiccantMoisture entering a nonhermetic refrigerant system throughhoses and sealsDrying equipment in the factory is disc
5、ussed in Chapter 5. Properinstallation and service procedures as given in ASHRAE Standard147 minimize the second, third, and fourth sources. Lubricants arediscussed in Chapter 12. If purchased refrigerants and lubricantsmeet specifications and are properly handled, the moisture contentgenerally rema
6、ins satisfactory. See the section on Electrical Insula-tion under Compatibility of Materials in Chapter 6 and the sectionon Motor Burnouts in this chapter.Effects of MoistureExcess moisture in a refrigerating system can cause one or all ofthe following undesirable effects:Ice formation in expansion
7、valves, capillary tubes, or evaporatorsCorrosion of metalsCopper platingChemical damage to motor insulation in hermetic compressors orother system materialsHydrolysis of lubricants and other materialsSludge formationIce or solid hydrate separates from refrigerants if the water con-centration is high
8、 enough and the temperature low enough. Solidhydrate, a complex molecule of refrigerant and water, can form attemperatures higher than those required to separate ice. Liquid waterforms at temperatures above those required to separate ice or solidhydrate. Ice forms during refrigerant evaporation when
9、 the relativesaturation of vapor reaches 100% at temperatures of 32F or below.The separation of water as ice or liquid also is related to the sol-ubility of water in a refrigerant. This solubility varies for differentrefrigerants and with temperature (Table 1). Various investigatorshave obtained dif
10、ferent results on water solubility in R-134a andR-123. The data presented here are the best available. The greaterthe solubility of water in a refrigerant, the less the possibility that iceor liquid water will separate in a refrigerating system. The solubilityof water in ammonia, carbon dioxide, and
11、 sulfur dioxide is so highthat ice or liquid water separation does not occur.The concentration of water by mass at equilibrium is greater inthe gas phase than in the liquid phase of R-12 (Elsey and FlowersThe preparation of this chapter is assigned to TC 3.3, Refrigerant Contami-nant Control.Table 1
12、 Solubility of Water in Liquid Phase ofCertain Refrigerants, ppm (by weight)Temp., F R-11 R-12 R-13 R-22R-113R-114R-123R-134aR-410AR-502160 460 700 4100 460 450 2600 4200 1780150 400 560 3600 400 380 2300 3600 1580140 340 440 3150 344 320 2000 3200 7200 1400130 290 350 2750 290 270 1800 2800 5800 12
13、20120 240 270 2400 240 220 1600 2400 4600 1080110 200 210 2100 200 180 1400 2000 3600 930100 168 165 1800 168 148 1200 1800 2800 81090 140 128 1580 140 120 1000 1500 2200 69080 113 98 1350 113 95 900 1300 1700 58070 90 76 1140 90 74 770 1100 1300 49060 70 58 44 970 70 57 660 880 950 40050 55 44 830
14、55 44 560 730 700 33540 44 32 26 690 44 33 470 600 510 27830 34 23.3 573 34 25 400 490 370 22520 26 16.6 14 472 26 18 330 390 270 18010 20 11.8 384 20 13 270 320 190 1460 15 8.3 7 308 15 10 220 250 130 11510 11 5.7 244 11 7 180 200 88 9020 8 3.8 3 195 8 5 140 150 59 6930 6 2.5 152 6 3 110 120 39 534
15、0 4 1.7 1 120 2 90 89 25 4050 3 1.1 91 1.5 70 66 3060 2 0.7 68 1 53 49 2270 1 0.4 50 0.6 40 35 1680 0.8 0.3 37 0.4 30 25 1190 0.5 0.1 27 0.2 22 18 8100 0.3 0.1 19 0.1 16 12 5Data on R-134a adapted from Thrasher et al. (1993) and Allied-Signal Corporation.Data on R-123 adapted from Thrasher et al. (1
16、993) and E.I. DuPont de Nemours it also varies with tem-perature. Table 2 shows the distribution ratios of water in the vaporphase to water in the liquid phase for common refrigerants. It canbe used to calculate the equilibrium water concentration of the liq-uid-phase refrigerant if the gas phase co
17、ncentration is known, andvice versa.Freezing at expansion valves or capillary tubes can occur whenexcessive moisture is present in a refrigerating system. Formationof ice or hydrate in evaporators can partially insulate the evaporatorand reduce efficiency or cause system failure. Excess moisture can
18、cause corrosion and enhance copper plating (Walker et al. 1962).Other factors affecting copper plating are discussed in Chapter 6.The moisture required for freeze-up is a function of the amountof refrigerant vapor formed during expansion and the distribution ofwater between the liquid and gas phases
19、 downstream of the expan-sion device. For example, in an R-12 system with a 110F liquidtemperature and a 20F evaporator temperature, refrigerant afterexpansion is 41.3% vapor and 58.7% liquid (by mass). The percent-age of vapor formed is determined by(1)wherehL(liquid)= saturated liquid enthalpy for
20、 refrigerant at liquid temperaturehL(evap)= saturated liquid enthalpy for refrigerant at evaporatingtemperaturehfg(evap)= latent heat of vaporization of refrigerant at evaporatingtemperatureTable 1 lists the saturated water content of the R-12 liquid phaseat 20F as 3.8 ppm. Table 2 is used to determ
21、ine the saturated vaporphase water content as3.8 ppm 15.3 = 58 ppmWhen the vapor contains more than the saturation quantity(100% rh), free water will be present as a third phase. If the temper-ature is below 32F, ice will form. Using the saturated moisture val-ues and the liquid-vapor ratios, the cr
22、itical water content of thecirculating refrigerant can be calculated asMaintaining moisture levels below critical value keeps free waterfrom the low side of the system.The previous analysis can be applied to all refrigerants and appli-cations. An R-22 system with 110F liquid and 20F evaporatingtempe
23、ratures reaches saturation when the moisture circulating is139 ppm. Note that this value is less than the liquid solubility,195 ppm at 20F.Excess moisture causes paper or polyester motor insulation tobecome brittle, which can cause premature motor failure. However,not all motor insulations are affec
24、ted adversely by moisture. Theamount of water in a refrigerant system must be small enough to avoidice separation, corrosion, and insulation breakdown.Polyol ester lubricants (POEs), which are used largely with hy-drofluorocarbons (HFCs), absorb substantially more moisture thando mineral oils, and d
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEREFRIGERATIONIPCH72010CONTROLOFMOISTUREANDOTHERCONTAMINANTSINREFRIGERANTSYSTEMS 制冷系统 水分 控制 其它 污染物

链接地址:http://www.mydoc123.com/p-455924.html