ASHRAE OR-16-C062-2016 Energy-Saving Measures in a Classroom Using Low Pressure Drop Ceiling Supply Device - A Field Study.pdf
《ASHRAE OR-16-C062-2016 Energy-Saving Measures in a Classroom Using Low Pressure Drop Ceiling Supply Device - A Field Study.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-16-C062-2016 Energy-Saving Measures in a Classroom Using Low Pressure Drop Ceiling Supply Device - A Field Study.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、 Harald Andersson is a PhD student in the Department of Building, Energy and Environmental Technologies, University of Gvle, Sweden. Mathias Cehlin is Assistant Professor in the Department of Building, Energy and Environmental Technologies, University of Gvle, Sweden. Bahram Moshfegh is Professor in
2、 the Department of Building, Energy and Environmental Technologies, University of Gvle, Sweden. Energy-Saving Measures in a Classroom Using Low Pressure Drop Ceiling Supply Device A Field Study Harald Andersson Mathias Cehlin, PhD Bahram Moshfegh, PhD ABSTRACT Between 1990 and 2006 the energy use by
3、 ventilation systems in Swedish schools doubled. This is explained by high airflows in schools because of the high occupant density. Studies show that 87% of Swedish schools use constant air volume (CAV), and it is estimated that a change to variable air volume (VAV) could save 0.12-0.33 TWh (4.1*10
4、12 - 1.1*1013 Btu) per year. Therefore the aim of this study is to investigate whether it is possible to replace displacement ventilation (DV) with mixing ventilation (MV) to create a comfortable indoor climate in a typical classroom and at the same time decrease the energy use by using VAV and Low
5、Pressure Drop Ceiling Supply Device (LPDCSD). The study used two LPDCSDs which consist of circular channels with 190/228 round jets placed in an interlocking pattern, with a horizontal one/two-way-direction. The field study was carried out in a school which is intended to be extensively renovated. T
6、he school currently has DV and CAV. The study was carried out by installing MV with LPDCSD in one of the typical classrooms. Several different air-flow rates were investigated using tracer-gas technology to measure the local mean age of the air in the occupied zone. Simultaneously, thermal comfort a
7、nd vertical temperature gradients were measured in the room. The results show nearly uniform distribution of the local mean age of air in the occupied zone, even in the cases of relatively low air-flow rates. Since the mixing of air is more or less the same in the entire occupied zone VAV can be use
8、d to reduce air-flow rate based on the desired CO2-level. Because of the number of students in each classroom and the fact that changes in air-flow rates have no significant effect on the degree of mixing, it is possible to reduce the air-flow rates for extended periods of time. Finally, since the L
9、PDCSD has a lower pressure-drop than the currently used supply devices and it is possible to use VAV to lower the airflows in cases with reduced heat loads, it is possible to significantly reduce the energy usage in the school while maintaining the IAQ, increasing the thermal comfort and the availab
10、le floor area of the occupied zone. INTRODUCTION The results from a government survey regarding energy use in Swedish public buildings show that energy use by ventilation systems in Swedish schools doubled from 1990 - 2006. The electrical power used by ventilation fans in Swedish schools has gone fr
11、om 11 kWh/m2 (3500 Btu/ft2) to 23 kWh/m2 (7300 Btu/ft2). This is on average 27% of the total electrical power usage in Swedish schools.This is explained by high airflows in schools because of the high occupant density. Most Swedish schools have mechanical ventilation (90%) and 75% of these systems h
12、ave heat recovery. The survey show that 87% of Swedish schools use constant air volume (CAV) and it is estimated that a change to variable air volume (VAV) could save 0.12-0.33 TWh (4.1*1012-1.1*1013 Btu) per year. (Energimyndigheten, 2010) The school in this case study is owned by the municipal hou
13、sing company and is about to be extensively renovated and retrofitted. The municipal housing company has the ambition to lower energy use and environmental impact of all their buildings. The school currently has wall-mounted displacement ventilation (DV) connected to a CAV system with heat recovery.
14、 Because of complaints from teachers and students about the thermal comfort in the occupied zone close to the supply devices, the housing company wants to change from wall-mounted DV to ceiling-mounted mixing ventilation (MV), even though DV normally has higher ventilation efficiency (Cao .et al 201
15、3). Therefore the aim of this study is to investigate experimentally whether it is possible to replace DV with MV to create a comfortable indoor climate in a typical classroom and at the same time decrease the energy use by using VAV and Low Pressure Drop Ceiling Supply Device (LPDCSD). EXPERIMENTAL
16、 SET-UP AND PROCEDURE This field measurement was performed in a classroom at a local school in the city of Gvle in Sweden. The school currently has DV and CAV in all of its classrooms. The classrooms dimensions are 8.0 7.5 3.0 m (26.2 24.6 9.8 ft) and are equipped with two wall-mounted DV supply dev
17、ices. The study was carried out by installing MV with LPDCSD in one of the typical classrooms and five test cases were conducted with different set-ups, see Table 1. Figure 1 LPDCSD and DV supply devices The different set-ups vary in supply devices, heat loads and airflow rates. Case 1 aims to simul
18、ate the current situation at school which consists of two wall-mounted DV supply devices with a total airflow of 300 l/s (636 cfm). Cases 2-5 use two LPDCSDs which consist of circular channels with 190/228 round jets placed in an interlocking pattern, with a horizontal one/two-way direction. Case 2
19、has similar airflow rate as Case 1 in order to make a comparison between the two systems, while Cases 3-5 use airflows based on 5 l/s (10.6 cfm) per person plus 0.6 l/s (1.3 cfm) per m2 floor area (ASHRAE, 2007). The set-ups also included person-simulators (manikins) with a thermal power of 95 W (32
20、0 Btu/h) each to simulate a person with a Met value of 1.0. Cases 1-3 used 28 manikins to simulate a full classroom, while Case 4 used 22 manikins and Case 5 used 16 manikins to simulate smaller classes. The classroom was illuminated by seven pairs of fluorescent lights, consuming a total of 14 36 W
21、 (14 120 Btu/h) electrical power and the test equipment inside the classroom is estimated to consume 150 W (510 Btu/h) of electrical power. During each case IAQ, vertical temperature gradient and thermal comfort were measured. Table 1. Case Set-up Case Supply device Manikins Airflow l/s (cfm) Heatlo
22、ad W (Btu/h) Ts C (F) Case 1 DV 28 299 (634) 3300 (11260) 20.8 (69.4) Case 2 LPDCSD 28 312 (660) 3300 (11260) 20.8 (69.4) Case 3 LPDCSD 28 181 (383) 3300 (11260) 20.6 (69.1) Case 4 LPDCSD 22 156 (330) 2700 (9212) 20.7 (69.3) Case 5 LPDCSD 16 133 (281) 2200 (7500) 20.4 (68.7) Tracer gas decay method
23、with SF6 was used to measure the total airflow as well as the variation of the local mean age of air (p) throughout the breathing zone (BZ) (Sandberg 1983). Figure 2 show the experimental set-up of the classroom where the red points indicate the measuring points for tracer gas. Tracer gas measuring
24、points (TGMP) 1-5 are all located at a height of 1.2 m and are in the BZ. TGMP6 is located at the outlet at a height of 2.6 m in order to measure the nominal time constant (n). Figure 2 Experimental set-up: eith TMPs A-K in blue, TGMPs 1-6 in red and manikins in black. The local mean age of air (p)
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR16C0622016ENERGYSAVINGMEASURESINACLASSROOMUSINGLOWPRESSUREDROPCEILINGSUPPLYDEVICEAFIELDSTUDYPDF

链接地址:http://www.mydoc123.com/p-455785.html