ASHRAE OR-10-014-2010 Consumption Analysis of Telco and Data Center Cooling and Humidification Options《电话和数据中心冷却和湿度选择的消耗分析》.pdf
《ASHRAE OR-10-014-2010 Consumption Analysis of Telco and Data Center Cooling and Humidification Options《电话和数据中心冷却和湿度选择的消耗分析》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-10-014-2010 Consumption Analysis of Telco and Data Center Cooling and Humidification Options《电话和数据中心冷却和湿度选择的消耗分析》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、118 2010 ASHRAEABSTRACTThis is an analysis of electrical and water consumption forcooling systems involving refrigeration with dry coolers, watereconomizers and air economizers combined with steam, ultra-sonic and evaporative humidifiers on telco/data centerslocated at various cities throughout the
2、United States.Air economizers with evaporative humidifiers are the mostenergy efficient model, although the savings are quite small fortropical locations. Air economizers are often able to satisfycooling requirements without any refrigeration and are alsoable to reduce refrigeration load for additio
3、nal time. Theseperiods when refrigeration is not required have improved reli-ability uptime and provide low risk opportunities for chillerplant servicing. The Air economizer system also consumes lesswater than water economizer or refrigeration only systems.Water economizers are less effective than a
4、ir economizersat improving energy efficiency and reducing refrigerationdependency. The modeled dry cooler did not provide any sav-ings versus refrigeration only.Evaporative humidifiers are more efficient than ultrasonichumidifiers and much more efficient than steam humidifiers.Air economizers with s
5、team humidifiers are an energywasteful design. More power is consumed by the steam humid-ifiers than is saved by the air economizers.INTRODUCTIONThis article analyzes electrical and water consumption forfour different cooling systems combined with three differenthumidification systems on hypothetica
6、l telco/data centerslocated at 262 cities throughout the United States.The four analyzed cooling systems include refrigerationonly, refrigeration with dry coolers, refrigeration with watereconomizers, and refrigeration with air economizers. Thesecooling systems do not represent every conceivable mod
7、el, butthey do represent the most common configurations.The three analyzed humidifiers include steam, ultrasonicand evaporative.Equipment, installation, and maintenance costs are notdirectly addressed.DATABASENOAA Hourly United States Weather Observations 1990-1995 Database has been used to determin
8、e weather conditionson an hourly basis for these consumption calculations. Theresults are based upon calculations repeated for every hour forthe six year period from the beginning of 1990 until the end of1995. Weather data records include station, date, hour of day,dry bulb temperature, relative hum
9、idity, barometric pressure,humidity ratio, wet bulb temperature, and enthalpy. Theweather data also included solar radiation data, but this datawas too inconsistent to be relied upon.Appendix A contains Transact SQL source code forcreation of all tables, stored procedures and functions andis availab
10、le on-line at http:bruceAppendixA.pdf.Water and moist air property functions were derived fromequations and tables within “Psychrometrics” (ASHRAE2005a).Refrigerant property functions were derived from“Refrigerant 134a (1,1,1,2-Tetrafluoroethane) Properties ofSaturated Liquid and Saturated Vapor” Ta
11、ble (ASHRAE2005b).The motor efficiency function is based upon NEMA MG14-pole squirrel cage TEFC Premium efficiency motors. TheConsumption Analysis of Telco and Data Center Cooling and Humidification OptionsBruce A. HellmerMember ASHRAEBruce A. Hellmer is a professional engineer with Tier IV Consulti
12、ng Group, Lees Summit, MO.OR-10-014 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digita
13、l form is not permitted without ASHRAEs prior written permission. ASHRAE Transactions 119VFD efficiency function assumes load independent losses of1.8% of full load and load dependent losses of 0.6% of actualload.BUILDING LOADSEquipment continuously releases one MW of heat withinthese hypothetical t
14、elco/data centers. This one MW heat loadwas selected to make scaling the results easy.Internal heat loads:Telco, data and conditioned electrical power distributionequipment: 1 MWLighting: 20 kWMiscellaneous: 10 kWPeople: 25 at 450 Btu/h (0.132 kW) each, latent loadwas disregardedBuilding characteris
15、tics:Height 18 ft (5.5 m)Length: 140 ft (42.7 m)Width: 140 ft (42.7 m)Equipment space: 10,000 ft2(929 m2) at 100 W/ft2(1076 W/m2)Support space: 9600 ft2(892 m2)Roof R-factor: 30 Btu/h ft2F (170 W/m2C)Exterior wall R-factor: 20 Btu/hft2F (114 W/m2C)The solar heat gain for each location has been calcu
16、latedfor the roof and the north, south, east and west walls for eachhour of the day and for each month of the year using the trig-onometric equations in “Fenestration” (ASHRAE 2005d).Heat transfer through the buildings exterior envelope hasbeen calculated using sol-air temperatures derived from sola
17、rheat gain for a light colored surface using the methoddescribed in “Nonresidential Cooling and Heating LoadCalculations” (ASHRAE 2005c). Return air grilles are locatedat ceiling so the bottom of roof is exposed to air at return airconditions. The inside of exterior walls is exposed to air atroom ai
18、r conditions.STANDARD OPERATING CONDITIONSThe most sensitive equipment should operate in a Class 1environment with the following recommended conditions(ASHRAE 2004):Dry-bulb temperature: between 68 and 77F (20 and25C)Relative humidity: between 40 and 55%Dew-point temperature: below 62.6F (17C)ASHRAE
19、 Technical Committee 9.9 has revised theserecommended conditions in its recent Second Edition(ASHRAE 2009):Dry-bulb temperature: between 64.4F and 80.6F (18and 27C)Relative humidity: below 60%Dew point temperature: between 41.9F and 59F (5.5and 15C)This energy analysis is not intended to address ene
20、rgysaving associated with operating at elevated space tempera-tures; thus these assumed operating conditions target themiddle of the recommended temperature range:Cold aisle, zone and room temperature setpoints: 72F(22.2C)Return air temperature: 80F (26.7C)Cold aisle, zone and room relative humidity
21、 setpoints(low limit): 40%Maximum supply humidity ratio corresponding to aroom temperature of 72F (22.2C) and a relativehumidity of 55%.AIR HANDLERSLarge central station air handlers were modeled. These airhandlers were utilized because they are easily equipped withair economizers and evaporative hu
22、midifiers. ComputerRoom Air Handlers (CRAHs) can be equipped with air econ-omizers, but this would generally require that they be locatedadjacent to exterior walls or below roof penetrations. CRAHsare also not generally available with ultrasonic or evaporativehumidifiers.Large central station air ha
23、ndlers may be good modelswith respect to electrical and water consumption for moresmaller air handlers, such as CRAHs, so long as the supply fankWh values are adjusted to reflect the different bhp/cfm ratios.Air handler characteristics:Quantity: six, four essential and two redundantTags: AH1, AH2, A
24、H3, AH4, AH5 and AH6Mass flow rate: 182,343 lb/h (50.65 kg/s)Volume flow rate: about 40,000 cfm (18.88 m3/s) fornear sea level installationsExternal static pressure: 2.0 inWC (498 Pa)Coil face velocity: 488 fpm (2.48 m/s)Coil size: 82 ft2(7.62 m2) for near sea level installationsPre-filters: 2 in. (
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR100142010CONSUMPTIONANALYSISOFTELCOANDDATACENTERCOOLINGANDHUMIDIFICATIONOPTIONS 电话 数据中心 冷却 湿度

链接地址:http://www.mydoc123.com/p-455676.html