ASHRAE OR-05-8-1-2005 Air Distribution in Rooms Generated by Textile Terminal-Comparison with Mixing and Displacement Ventilation《混合和置换通风与纺织终端所产生的相比的室内里的空气分配》.pdf
《ASHRAE OR-05-8-1-2005 Air Distribution in Rooms Generated by Textile Terminal-Comparison with Mixing and Displacement Ventilation《混合和置换通风与纺织终端所产生的相比的室内里的空气分配》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-05-8-1-2005 Air Distribution in Rooms Generated by Textile Terminal-Comparison with Mixing and Displacement Ventilation《混合和置换通风与纺织终端所产生的相比的室内里的空气分配》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、OR-05-8-1 Air Distribution in Rooms Generated by a Textile Terminal-Comparison with Mixing and Displacement Ventilation Peter V. Nielsen, PhD Fellow ASHRAE Mads Sjnnichsen ABSTRACT Experiments with air distribution in rooms generated by a low impulse textile terminal are compared with the air distri
2、- bution obtained by mixing ventilation and displacement venti- lation. The air distribution in the room is mainly controlled by buoyancy forces from the heat sources, although thejlow from the textile terminal can be characterized as a passive displace- mentjlow with a downward direction in areas w
3、ithout thermal load. A variant of the system is supplied with horizontal jets from openings in the textile terminal to generate a mixingflow in the room. Both systems are compared with mixing ventila- tion based on a wall-mounted difuser and with displacement ventilation with a wall-mounted low velo
4、city difuser. All systems are tested in the same room with the same heat load consisting of two manikins, each sitting at a desk, two PCs, and two desk lamps, producing a total heat load of 480 W In addi- tion, cases with a single workplace are also tested. The design of the air distribution system
5、is in all four cases based on flow elements for the difuser, a maximum velocity assumption, and a critical vertical temperature gradient in the room. The characteristics of the air distribution systems are addressed by analyzing the acceptable conditions for the supplyjlow rate and the temperature d
6、iference for the different systems. The paper shows that an air distribution system based on textile terminals is able to generate comfortable velocity and temperature conditions at the same thermal load as can be obtained by both a mixing ventilation system with a wall- mounted difuser and a displa
7、cement ventilation system with a low-velocity wall-mounted difuser. Claus Topp, PhD Associate Member ASHRAE Heine Andersen The comparison is extended by considering both the local discomfort caused by draft rating and the percentage of dissat- isJied due to the temperature gradient when this is rele
8、vant to the systems. The draft rating is very low for the low impulse system (textile terminals), and the temperature gradient is also low because of the high level of room air mixing. INTRODUCTION The aim of an air-conditioning system is to remove excess heat in a room and replace room air with fre
9、sh air to obtain a high air quality. It is not sufficient to remove heat and contam- inated air; it is also necessary to distribute and control the air movement in the room to create thermal comfort in the occu- pied zone. Most air distribution systems are based on mixing venti- lation with ceiling
10、or wall-mounted diffusers or on displace- ment ventilation with wall-mounted low velocity diffusers. New principles for room air distribution are introduced with the textile terminals, which can be arranged as low impulse systems. Figure 1 shows the layout of a low impulse system with a passive and
11、an active downward-directed flow from the textile terminal, respectively. The right illustration in Figure 1 shows a textile terminal with a number of small openings that generate horizontal flow to increase the width of the down- ward flow from the diffuser and to improve mixing in situa- tions whe
12、n heated air is supplied to the room. The heat sources in the room control the flow in a large area, and a displacement effect will only be present in some parts of the room. The effect is especially pronounced if heat sources are located outside the downward-directed flow from the terminals. Peter
13、V. Nielsen is a professor and Mads Sennichsen and Heine Andersen are students in the Department of Building Technology and Struc- tural Engineering, Aalborg University, Copenhagen, Denmark. Claus Topp is with the engineering firm, Lindab A/S Comfort, Farum, Denmark. 02005 ASHRAE. 733 Textile termina
14、ls have been used for many years in the catering and food processing industry because they are easy to clean and because condensation on fabric surfaces is prevented. Textile terminals are now increasingly used as comfort ventilation in large offices as call centers and in other areas with a high co
15、oling load. This paper addresses four air distribution systems in all, namely, two low impulse systems based on textile terminals with and without horizontal jet flow (see Figure 1) and mixing ventilation from a wall-mounted terminal and displacement ventilation from a wall-mounted low velocity diff
16、user (see Table 1). The design strategies are discussed for all four systems. The supply flow rate qo and the temperature differ- ence AT, between return and supply are chosen as design parameters. The local discomfort caused by draft rating and the dissatisfied due to the temperature gradient are a
17、lso addressed. System Supply Return Mixing ventilation End wall-mounted Return opening below sup- Displacement ventilation End wall-mounted End wall-mounted below ply terminal ceiling Low impulse textile tenni- Ceiling-mounted End wall-mounted at floor na1 level TEST ROOM Figure 2 shows the full-sca
18、le rooms and the location ofthe diffuser for mixing ventilation, the diffuser for displacement ventilation, and the textile terminal at the ceiling. The dimen- sions of the room are in accordance with the requirements of the International Energy Agency Annex 20 work with length, width, and height eq
19、ual to 4.2 m, 3.6 m, and 2.5 m. The return openings have different locations, as indicated in Figure 2 and described in Table 1. Load, one person Load, two persons W W 240 480 240 480 240 480 Figure 1 Low impulse systems without and with horizontal control jets. Low impulse textile termi- na1 with h
20、orizontal con- trol jets Figure 3 shows the textile terminal, which is designed as a half cylinder (d = 3 15 mm) located close to the ceiling. The textile terminal with horizontal control jets has the same loca- tion and it has four groups of openings on both sides of the terminal. Every group of op
21、enings consists of 42 openings each with a diameter of 4.5 mm covering a distance of 475 mm of the textile terminal. They are distributed at a distance of 525 mm along the terminal. Figure 4 shows the furnishings and the heat load of the room (office room layout). The heat load consists of two PCs,
22、two desk lamps, and two manikins, producing a total heat load of 480 W. The room dimensions, the furnishings, and the heat load are identical to earlier test cases with mixing and displacement ventilation (see Jacobsen et al. 2002 and Nielsen et al. 2003). Therefore, it is possible to make a direct
23、comparison between four different air distribution systems. Some experiments are also carried out with a single workplace in the room. In this case the workplace is located symmetri- cally in the room. The temperature distribution is measured along three vertical lines and in supply and return with
24、type-K thermocou- ples connected to a data logger. The velocities are measured along a line at the height of 1.8 m (height of the occupied zone). The measurement line is moved down along the whole length of the room. Velocities are also measured at head, chest, and foot height of the two thermal man
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR05812005AIRDISTRIBUTIONINROOMSGENERATEDBYTEXTILETERMINALCOMPARISONWITHMIXINGANDDISPLACEMENTVENTILATION

链接地址:http://www.mydoc123.com/p-455652.html