ASHRAE LO-09-088-2009 A Calibrated Multi-Zone Airflow Model for Extension of Ventilation System Tracer Gas Testing《通风系统示踪气体测试的扩展用校正多区气流模型》.pdf
《ASHRAE LO-09-088-2009 A Calibrated Multi-Zone Airflow Model for Extension of Ventilation System Tracer Gas Testing《通风系统示踪气体测试的扩展用校正多区气流模型》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-088-2009 A Calibrated Multi-Zone Airflow Model for Extension of Ventilation System Tracer Gas Testing《通风系统示踪气体测试的扩展用校正多区气流模型》.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、924 2009 ASHRAEABSTRACT The software CONTAM was used to create a calibrated multi-zone model to replicate in-field tracer gas decay measurements of a new 2-story, 2600 ft2(240 m2), single-family house in Sacramento, CA under different whole-house dilution ventilation scenarios. The model incorporate
2、d measured values of ventilation system airflow rate, building enclosure leakage, fan-forced mixing between floor levels, indoor and outdoor temperature, and wind speed and direc-tion. The enclosure leakage distribution was adjusted to tune the model to the measured tracer gas concentration data. Th
3、e calibrated model was then used to compare different ventila-tion systems under identical outdoor conditions over a one-day period. Zones that received more ventilation air had faster concentration decay rates compared to zones that received less ventilation air. Results showed that ventilation sys
4、tems that delivered air to all zones, either by a dedicated duct system or by incorporation of the central forced-air space conditioning system, had more uniform ventilation air distribution.INTRODUCTIONThis paper describes the creation of a calibrated computer model for residential ventilation syst
5、ems and the use of the calibrated model to extend the results obtained in previous field testing. The model calibration process used test data from tracer gas testing of residential ventilation systems in a new single-family house near Sacramento, California. Hendron (2007) detailed the tracer gas t
6、esting and conclusions. The work described in this paper was performed in order to eval-uate ventilation systems that were not present in the houses tested by Hendron and to provide the capability to extend the results of field testing in one location under one set of envi-ronmental conditions to ma
7、ny locations under many sets of environmental conditions.DESCRIPTION OF HOUSEThis work concentrates on one of the two houses tested by Hendron (2007). The house is two-story, approximately 2600 ft2(240 m2), with four bedrooms and three bathrooms. The first floor consists of one bedroom, one bathroom
8、, a laun-dry room, the living room area, and a kitchen and dining room. The second floor consists of the master bedroom and bath-room, two additional bedrooms, an additional bathroom, and a small common area at the top of the stairway which over-looks the living room below. Figure 1 contains a drawi
9、ng of the floor plan of the house.Figure 1 House floor plan.A Calibrated Multi-Zone Airflow Model for Extension of Ventilation System Tracer Gas TestingAaron Townsend, PE Armin Rudd Joseph Lstiburek, PhD, PEngAssociate Member ASHRAE Member ASHRAE Fellow ASHRAEAaron Townsend is an associate and Armin
10、 Rudd and Joseph Lstiburek are principals with Building Science Corporation, Somerville, MA.LO-09-088 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional rep
11、roduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.ASHRAE Transactions 925DESCRIPTION OF PREVIOUS TRACER GAS TESTINGHendron (2007) describes the tracer gas testing in detail. In total, seventeen ventilation tests were pe
12、rformed on the house using tracer gas decay methods. Table 1 lists the tracer gas tests performed. For each test, the house was first brought to a well-mixed state with uniform tracer gas concentration in all zones by running the central air handler (AHU) and auxil-iary mixing fans. The test was ini
13、tiated by deactivating the mixing systems and activating the ventilation system as appro-priate for the test, and leaving the house in that state for a period of 2 to 14 hours. Three ventilation systems were tested. The first ventilation system tested was the central-fan-inte-grated supply (CFIS) ve
14、ntilation system, which consists of an outside-air duct to the return side of the AHU and a controller that operates the AHU on a minimum duty cycle. The outside-air duct contains a damper that remains closed except when the CFIS system is activated. The duty cycle of the AHU and CFIS system varied
15、from test to test. This ventilation system was operated at different ventilation rates using a variable-speed fan installed inline with the outside air duct, as described in Table 1. The second and third ventilation systems were upgraded exhaust fans located in the laundry room and master bedroom, r
16、espectively. The exhaust fans were tested only at 100% of the ASHRAE Standard 62.2-2003 (ASHRAE 2003) (referred to elsewhere in this paper simply as 62.2) ventilation rate, and were tested with and without simultaneous operation of the AHU for mixing. In addition to the ventilation tests, natural in
17、filtration and air handler bump (natural infiltration with the AHU running) tests were also conducted. During the tracer gas tests, the bedroom doors were either open or closed. The house was built with transfer grills, which are passive openings above the doorways that allow a return air path when
18、the bedroom doors are closed. The transfer grills were also either open or closed (taped over) during the tracer gas tests. The doors to the bathrooms and laundry room were always open. All exterior doors and windows were always closed.DESCRIPTION OF MODELING SOFTWARECONTAM is a multi-zone air flow
19、network modeling software developed by the National Institute of Standards and Technology (Walton 2005; Emmerich 2003; Emmerich 2001). It is commonly used in ventilation research to model build-ings, ventilation systems, and contaminants in indoor and outdoor air (Emmerich 1995; Persily 1998). In CO
20、NTAM, the user specifies attributes of the buildings zones, air flow path-ways between zones (such as leaks or fans and ducts), contam-inant sources and sinks, and other relevant inputs. The software performs the simulation and the results are available for visualization or export.TESTING OF SUBSTIT
21、UTE HOUSEAt the time of the work described in Hendron (2007), an enclosure air leakage test was performed with a blower door (ASTM 2003), but no further diagnostics were performed on the house enclosure or interior demising walls as further work was not planned at the time. Later, when the decision
22、was made to create a calibrated computer model, much more detailed information about the enclosure and interior airflow paths was needed in order to provide a reasonable starting point for the calibration process. The original house was no longer available for testing, so another house of the same f
23、loor plan was tested instead. While two houses of the same floor plan can certainly have different leakage characteristics, these Table 1. Tracer Gas TestsTest Number DescriptionCFIS Tests With Mixing (All have AHU 20 min off/10 min on)1Doors Closed, Transfer Grills Open, 95% of the 62.2 Ventilation
24、 Rate*2Doors Closed, Transfer Grills Open, 60% of the 62.2 Ventilation Rate3Doors Closed, Transfer Grills Open, 33% of the 62.2 Ventilation Rate4Doors Closed, Transfer Grills Closed, 60% of the 62.2 Ventilation RateLaundry Exhaust Tests With Mixing (All at 100% of the 62.2 ventilation rate)5Doors Cl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090882009ACALIBRATEDMULTIZONEAIRFLOWMODELFOREXTENSIONOFVENTILATIONSYSTEMTRACERGASTESTING 通风 系统

链接地址:http://www.mydoc123.com/p-455367.html