ASHRAE LO-09-080-2009 VFD Application for Constant Volume Air-Handling Units《VFD应用于空气处理单元恒定体积》.pdf
《ASHRAE LO-09-080-2009 VFD Application for Constant Volume Air-Handling Units《VFD应用于空气处理单元恒定体积》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-080-2009 VFD Application for Constant Volume Air-Handling Units《VFD应用于空气处理单元恒定体积》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、824 2009 ASHRAEABSTRACTTraditional constant air volume systems consume signif-icantly more energy than variable air volume (VAV) systems because a constant amount of air is supplied to each zone regardless of the zone load. Due to seasonal and daily load variations, variable frequency drives (VFDs)
2、can be installed on these constant air volume systems to reduce system energy consumption without needing to retrofit the terminal box. This paper presents the procedures for supply fan speed control and the results of its application in an office building. The results show electricity savings of 23
3、% and gas savings of 19% over a six-month period. INTRODUCTIONMany constant air volume (CAV) systems were installed in the 1950s and 1960s. Unfortunately, many of these systems are still in use due to the high cost of converting them to VAV systems. Constant air volume systems, like VAV systems, are
4、 often oversized and incur a significant energy penalty due to their incapability of modulating airflow. Zone loads are often much lower than the design load due to partial occupancy and maintain cooler air temperatures than design weather condi-tions. Since a constant supply air temperature is requ
5、ired for humidity control, more energy may be used during moderate weather conditions. CAV systems consume more fan power, more heating energy, and more cooling energy. The conven-tional method of reducing energy consumption is to install variable frequency drives (VFDs) on the supply and return air
6、 fans and convert the terminal box. Retrofitting the existing terminal box requires significant investment and interrupts the buildings normal occupancy pattern.Liu and Claridge (1999) presented a method to convert dual-duct constant volume systems without having to retrofit the terminal boxes to a
7、VAV system. A damper is installed in the main hot duct. During summer, the hot air is shut off. This method reduces both fan and thermal energy. For single-duct constant volume systems, Liu et al. (2002) suggested install-ing VFDs on both supply and return air fans to reduce airflow at night and on
8、weekends. This practice can be extended to normal operating hours with use of a proper control sequence for the CAV system.The objective of this study is to develop a method for VFD control through a case implementation. This paper presents facility information, procedures for supply fan speed contr
9、ol, and the results of the case study application.FACILITY INFORMATIONThe test facility is a 12-story office building with 489,000 ft2in Omaha, Nebraska. It was built in the late 1960s. The typical office hours are 8:00 a.m. to 5:00 p.m. during the weekdays. Two typical air-handling units (AHUs) loc
10、ated in the east interior zone and exterior zone were chosen for the case study. Each AHU is a typical single-duct CAV system with terminal boxes. The interior zone unitshave one 60 hp supply fan, and the exterior zone units have one 25 hp supply fan. To apply the method for VFD control, VFDs were i
11、nstalled in the supply fan of each unit. The AHU schematic diagram is shown in Figure 1. Figure 2 shows a schematic diagram of the section plan.VFD CONTROL METHODThe building load varies significantly with outside air conditions and internal occupancy conditions. In constant air VFD Application for
12、Constant Volume Air-Handling UnitsYoung-Hum Cho Mingsheng Liu, PhD, PE Gang Wang, PhDStudent Member ASHRAE Member ASHRAE Member ASHRAEJinrong Wang, PE Timothy Rauscher, PEMember ASHRAE Associate Member ASHRAEYoung-Hum Cho is a student and Mingsheng Liu is a professor in the Architectural Engineering
13、 Department at the University of Nebraska-Lincoln, Omaha, NE. Gang Wang is an assistant professor of Civil and Architectural Engineering at the University of Texas A&M-Kingsville, TX. Jinrong Wang and Timothy Rauscher are senior technical analysis engineers for Omaha Public Power District, Omaha, NE
14、.LO-09-080 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted w
15、ithout ASHRAEs prior written permission.ASHRAE Transactions 825Figure 1 Schematic diagram of AHU.Figure 2 Section plan of the building.826 ASHRAE Transactionsvolume systems, a significant amount of energy is consumed unnecessarily. Most of this energy waste can be reduced by simply installing a VFD
16、on the supply fan without a major retrofit effort if there are no retrofit funds available. The following is the procedure for identifying the VFD speed control. Step 1: Trend the Zone TemperaturesTo identify the building load profile for an AHU, room air temperature (Tr), supply air temperature, (T
17、SA) and zone discharge air temperature (TDA) should be measured daily. Figure 3 shows trended data of zone temperatures with highest TDA(zone A) and lowest TDA(zone B). The graphic shows that the supply air temperature and room air temperature have similar trends. The difference between zone dischar
18、ge air temperatures is about 10F. Hence, each zone has a different load profile and wastes reheating energy. Step 2: Calculate Zone Load ProfileThe interior zone load profile in an office building depends on occupancy only. The building load ratio can be calculated by the following equation based on
19、 the previous measurement data:(1)Figure 4 shows the zone load profile calculated by Equa-tion 1. The graph shows that zones A and B have different load profiles. Although zone B has the maximum load, it still wastes reheat energy because of the high airflow. The supply air temperature (TSA) from th
20、e central units was maintained at design value (55F) for the humidity control, but the discharge air temperature increased to maintain the room temperature setpoint. To reduce the reheat energy, the supply air Figure 3 Measured data of zone temperatures.Figure 4 Calculated zone load profile.TrTDATrT
21、SA-=ASHRAE Transactions 827temperature (TSA) can be increased, or the airflow can be decreased using a VFD control. Step 3: Pick-Up Maximum Load ProfileIn this case study building, there were load profiles for 12 zones between maximum and minimum, according to the previous calculated zone load profi
22、le. To control the supply fan speed of the CAV system, the maximum load profile zone, zone B, was chosen as shown in Figure 4.Step 4 : Set-Up VFD Speed as the Profile Interior Zone Unit. Develop the supply fan speed setpoint based on the previous picked up maximum load profile and modulate the VFD s
23、peed to maintain its setpoint. The VFD speed of the interior zone unit is a function of the time of day, which is determined by Equation 2. The exam-ple in Figure 5 shows the VFD speed setpoint of the interior zone unit as 55% from 8:00 a.m. to 9:00 a.m. and 65% from 9:00 a.m. to 11:00 a.m. (2)Exter
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090802009VFDAPPLICATIONFORCONSTANTVOLUMEAIRHANDLINGUNITSVFD 应用于 空气 处理 单元 恒定 体积 PDF

链接地址:http://www.mydoc123.com/p-455360.html