ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 5-2012 IN-ROOM TERMINAL SYSTEMS.pdf
《ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 5-2012 IN-ROOM TERMINAL SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC SYSTEMS AND EQUIPMENT SI CH 5-2012 IN-ROOM TERMINAL SYSTEMS.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、5.1CHAPTER 5IN-ROOM TERMINAL SYSTEMSSystem Characteristics. 5.1System Components and Configurations . 5.4Secondary-Water Distribution . 5.5Piping Arrangements . 5.5Fan-Coil Unit and Unit Ventilator Systems . 5.6Variable-Refrigerant-Flow (VRF) units. 5.7Chilled-Beam Systems 5.7Radiant-Panel Heating S
2、ystems. 5.9Radiant-Floor Heating Systems. 5.9Induction Unit Systems 5.10Supplemental Heating Units 5.10Primary-Air Systems 5.10Performance Under Varying Load . 5.11Changeover Temperature . 5.12Two-Pipe Systems with Central Ventilation . 5.12Four-Pipe Systems 5.15Automatic Controls and Building Manag
3、ement Systems . 5.15Maintenance Management Systems and Building System Commissioning. 5.16ERY early in the design process, the HVAC design engineerVmust analyze and ultimately select appropriate systems, as dis-cussed in Chapter 1. Next, production of heating and cooling isselected as decentralized
4、(see Chapter 2) or centralized (see Chapter3). Finally, distribution of heating and cooling to the end-use spacecan be done by an all-air system (see Chapter 4), or a variety of all-water or air-water systems and local terminals, as discussed in thischapter.One option is use of in-room terminal syst
5、ems to provide heatingand/or cooling to individual zones. Terminal units include consoles,fan-coils, blower coils, unit ventilators, chilled beams, and radiantpanels. Terminal systems add heat energy or absorb the heat in theconditioned space served. The medium that transfers the heat eitherfrom the
6、 space to the outdoors or from a heat source to the condi-tioned spaces may be the same as used with nonterminal systems.Typical uses of in-room terminal unit systems include hotels/motels, apartments and multifamily dwellings, classrooms, andhealth care facilities. In older office buildings, in-roo
7、m terminalunits were commonly used for perimeter rooms, combined withcentral air handlers that served the interior spaces. Systems of thistype are making a comeback with the introduction of variable-refrigerant-flow (VRF) equipment, combined with dedicated out-door air systems (DOAS). Historical pre
8、servation projects often usein-room terminal units to minimize the space problems due to run-ning ductwork in historical structures.SYSTEM CHARACTERISTICSTerminal-unit systems can be designed to provide completesensible and latent cooling and heating to an end-use space; how-ever, most terminal syst
9、ems are best used with a central ventilationsystem providing pretreated air to the space. Heat can be providedby hot water, steam, or an electric heating coil. Cooling can beprovided by chilled-water or direct-expansion (DX) coils. Heatpumps (discussed in Chapter 2) can be used, either with a pipedw
10、ater loop (water-source) or air cooled. In-room terminals usuallycondition a single space, but some (e.g., a large fan-coil unit) mayserve several spaces. In-room terminal systems can allow individ-ual space control of heating or cooling during intermediate sea-sons; satisfying the heating and cooli
11、ng needs of various rooms ona single system. A thermostat for each terminal unit provides indi-vidual zone temperature control.A terminal unit used with central ventilation provides the cool-ing or heating necessary to handle only the sensible heat gain or losscaused by the building envelope and occ
12、upancy. Ventilation, orprimary, air is delivered by a separate ducted system, either to theterminal unit or ducted directly to the space, and should be pre-treated to handle the total latent load of the ventilation air, occu-pancy, and the space, as well as the sensible load of the ventilationair.Te
13、rminal units without central ventilation require additionalcoil capacity to heat or cool and dehumidify the ventilation airrequired for the end space. Terminal units are commonly small, withminimal coil rows; therefore, providing this additional capacity isoften difficult. Care must be taken to mini
14、mize the risk of frozencoils in the winter, and to have enough cooling capacity to not onlycool, but also dehumidify ventilation air in the summer. Terminalunits have very small fans, so ventilation air must be provided to theunit from a central fan-powered source or supplied from a nearbyopening in
15、 the building skin, thereby limiting the location of termi-nal units to the exterior wall of the building.Although a single in-room terminal unit can be applied to a sin-gle room of a large building, this chapter covers applying multiplein-room terminal units to form a complete air-conditioning syst
16、emfor a building.AdvantagesAdvantages of all in-room terminal unit systems include the fol-lowing: The delivery system for the space heating and cooling needs (pip-ing versus duct systems) requires less building space (a smallercentral fan room, or none, and little duct space)System has all the bene
17、fits of a central water chilling and heatingplant, but allows local terminals to be shut off in unused areasIndividual room temperature control allows each thermostat to beadjusted for a different temperatureMinimal cross contamination of recirculated airBecause this system can heat with low-tempera
18、ture water, it isparticularly suitable for use with solar or low-temperature/high-efficiency boilers or with heat recovery equipmentFailure of a single in-room unit affects only the one room, allow-ing other spaces to continue to operateFacilities personnel can remove and replace an in-room terminal
19、unit in hours, allowing them to install a spare and have the roomback in service quickly; units are comparatively inexpensive,small, and light, so the owner has the option of stocking spareunits on the premisesMaintenance procedures generally can be done by nonlicensedHVAC personnel, allowing in-hou
20、se crews to complete the tasksControls for each unit are very simpleCentral control systems can be incorporated to control unit oper-ation and space temperatures during unoccupied hoursThe preparation of this chapter is assigned to TC 9.1, Large Building Air-Conditioning Systems.5.2 2012 ASHRAE Hand
21、bookHVAC Systems and Equipment (SI)In-room terminal unit systems with central ventilation air havethese additional advantages:The central air-handling apparatus used for central ventilation airis smaller than that of an all-air system because less air must beconditioned at that location.Space can be
22、 heated without operating the primary air system,using just the in-room terminal units. Nighttime primary fan oper-ation is avoided in an unoccupied building. Emergency power forheating, if required, is much lower than for most all-air systems.Dehumidification, filtration, and humidification of vent
23、ilation airare performed in a central location remote from conditionedspaces.They allow using central heat recovery devices such as heatwheels.Ventilation air is positively supplied and can accommodate con-stant recommended outdoor air quantities, regardless of the tem-perature control of the room.U
24、se of central ventilation air with terminal units in some climatescan prevent the negative pressurization problems that occur whenoccupants turn off in-room units.DisadvantagesFor many buildings, in-room terminals are limited to perimeterspace; separate systems are required for other areas.In-room t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACSYSTEMSANDEQUIPMENTSICH52012INROOMTERMINALSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-455129.html