ASHRAE AN-04-8-1-2004 A Bin Method Energy Analysis for Ground-Coupled Heat Pumps《为地面耦合热泵RP-1217用的仓式能量分析》.pdf
《ASHRAE AN-04-8-1-2004 A Bin Method Energy Analysis for Ground-Coupled Heat Pumps《为地面耦合热泵RP-1217用的仓式能量分析》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AN-04-8-1-2004 A Bin Method Energy Analysis for Ground-Coupled Heat Pumps《为地面耦合热泵RP-1217用的仓式能量分析》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、AN-04-8-1 (RP-1217) A Bin Method Energy Analysis for Ground-Coupled Heat Pumps Stephen P. Kavanaugh, Ph.D. Member ASHRAE ABSTRACT The objective ofASHRAE research project 121 7-TRP was to develop accurate performance models of ground-coupled heat pump (GCHP) pump and piping system designs and to prov
2、ide easy-to-use evaluation tools. One product of this project is a GCHP bin method program that integrates the measured results for pump energy and demand for several design options with annual heatpump energy use. The basics ofthe program are described in this papel: Analyses for an example ofice b
3、uilding are presented for systems that follow ASHRAE energy-eficient recommendations and systems that are oversized. Multiple subcentralpiping systems with unitary circulators and central systems with variable-speed pump motors consume the least amount of enem, while constant- volume pumping andprim
4、ay-secondary systems consume the greatest amount of enera. INTRODUCTION The goal of every designer is to find an optimum balance between capital costs and operating costs. Two primary areas of concern with ground-coupled (closed-loop) heat pumps are the ground heat exchanger and the pumping/piping s
5、ubsystem. Engineers have traditionally focused a great deal of effort on the ground heat exchanger design since it is typi- cally a novel undertaking. However, in an ASHRAE-spon- sored survey (Caneta 1995), it was found that installed pumping power represented anywhere from 0.04 to 0.21 HP/ ton (0.0
6、085 to 0.045 kWelect/kWthem) of heat pump power. A continuation of the survey presented information that indi- cated pump energy exceeds heat pump (compressor and fan) energy in some installations (ASHRAE 1998). Continuously operating central pumps have been shown to consume Steven E. Lambert, P.E.
7、between 32% and 130% of heat pump energy (Kavanaugh and Rafferty 1997). Thus, circulating pumps may represent a significant portion of the total energy consumption of GCHP systems. A simplified (bin method) energy analysis program pack- age for ground-coupled heat pumps has been developed. In additi
8、on to the energy consumption of the heat pump units, the program breaks out the pump demand and energy consump- tion and permits multiple pump options to be compared simul- taneously. The level of effort required of the user is only slightly more than that required to conduct the building heat- ing
9、and cooling load calculation. However, the validity of the output is improved because the pump demand and energy use are based on the correlations that were generated from infor- mation gathered and measured during ASHRE 12 17-RP, “Development of Guidelines for the Selection and Design of the Pumpin
10、gPiping Subsystem for GCHP Systems” (Kavanaugh et al. 2003). USE OF THE BIN METHOD FOR GCHPS Weather data can be arranged in temperature bins of 5F (3C) increments (Degelman 1986; InterEnergy 1999). The number of hours per year that the outdoor temperature is within the range of the bin is referred
11、to as the bin hours. For example, there are typically seven hours per year in Birming- ham where the temperature is between 95F and 99F (97F average). Thus, there are seven bin hours in the 97F (36C) temperature bin. Each bin and time increment also has a mean coincident wet-bulb temperature (WBT),
12、which is an indicator of the humidity level. The bin data used in this program are subdivided into four-hour increments. Of the seven bin hours in the 97F Steve Kavanaugh is a professor and Steven Lambert is a graduate student in the Department of Mechanical Engineering at the University of Alabama,
13、 Tuscaloosa. 02004 ASHRAE. 535 (36OC) bin, six occur between noon and 4 p.m., and one occurs between 4 and 8 p.m. This allows more detailed bin calcula- tions since loads change with time of day and occupancy, The structure of the program allows loads for both the occupied and unoccupied conditions
14、at any of the six four-hour time increments. The number of days per week the building is occu- pied can also be adjusted. The program currently computes the energy based on annual bin hours at 20 locations. Since GCHPs are widely used in schools, nine-month bin data are also available for selected l
15、ocations. The traditional bin method (ASHRAE 2001) correlates the outdoor air temperature to conventional air-based equip- ment capacity and demand using linear or higher-order poly- nomial correlations. Unfortunately, GCHP capacity and demand are not direct functions of outside air temperature. Add
16、itional steps are necessary to relate outdoor temperature to building load, building load to estimated part-load factor, and estimated partial-load factor (PLF,) to the ground-loop temperature, which is also a function of maximum system loop temperature and the temperature and conductivity of the fo
17、rmation surrounding the ground loop. The required input also includes occupied and unoccupied building loads, occu- pancy patterns, heat pump output, and demand data as a func- tion of water flow and temperature, maximum and minimum loop temperatures, and ground temperature. The most frequently used
18、 determinant of water-to-air heat pump perfor- mance is liquid temperature entering the unit. It is used to replace the outdoor air temperature for the variable required to calculate equipment capacity and demand. These correlations are available from heat pump manufacturers. When the outdoor temper
19、ature is maximum, the loop temperature is at the design point, and the PLF is near unity. When the load is near zero but the equipment is operating in cooling, the loop temperature will be offset slightly above the normal local ground temperature. The offset is dependent on flow rate and earth tempe
20、rature recovery. A conservative esti- mate is to offset the loop temperature at zero PLF to a value equal to the temperature rise in the heat pump condenser, which is near 10F (6C) at 3 gpdton (3.2 LpmkW) and 12.5“F (7C) at 2.5 gpdton (2.7 Lpm/kW). However, in multizone applications where simultaneo
21、us heating and cool- ing are likely to occur, the offset is near zero. A linear corre- lation between this temperature (PLF = O) and the design loop temperature (PLF = 1 .O) can be developed. The computation can then proceed as described for the air-based equipment bin method calculation. For each b
22、in, the cooling capacity (qccup) of the unit normally exceeds the load. The building load to unit capacity fraction is referred to as the theoretical partial-load factor (PLF,). Since equipment normally takes a short period to begin cooling or heating effectively after it has been started, a cycling
23、 capacity adjustment factor (CCAF) should be applied when the unit has to stop and start. = 1 - C,( 1 - PLF,) = 1 - 0.25( 1 - 0.75) = 0.94 , (1) where 0.25 is a typical default value for the degradation coef- ficient (C,). To find the energy use for each temperature bin and four- hour time increment
24、, P x PLF, x T (2) CCAF E= where E = energy, kWh, P = power to heat pump (compressor and fan), kW, PLF, = theoretical partial-load factor, and z = time in number of bin hours. The seasonal cooling energy use is the sum of the energy use in all temperature bins for all time periods. Heat pumps have s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAN04812004ABINMETHODENERGYANALYSISFORGROUNDCOUPLEDHEATPUMPS 地面 耦合 RP1217 能量 分析 PDF

链接地址:http://www.mydoc123.com/p-454561.html