ASHRAE AB-10-003-2010 Flat Oval Duct Leakage Class Measurement.pdf
《ASHRAE AB-10-003-2010 Flat Oval Duct Leakage Class Measurement.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AB-10-003-2010 Flat Oval Duct Leakage Class Measurement.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、2010 ASHRAE 387ABSTRACTThis paper presents results of an experimental program to determine the leakage class for three cross section flat oval ducts for positive and negative internal pressures. Sealed and unsealed duct leakage tests were performed. The leakage data were found to be a power law func
2、tion of static pressure differ-ence between the interior and the exterior of the duct. The power law exponent ranged from 0.675 to 1.065 for sealed conditions, and 0.437 to 0.729 for unsealed conditions. Gener-ally the exponent found for an individual duct tested in the negative pressure mode was le
3、ss than that for the correspond-ing positive pressure mode. Leakage class values ranged from 0.034 to 1.048 mL/s per m2(0.23 to 2.2 cfm per 100 ft2) for sealed duct tests, and between 297.4 to 1342.2 mL/s per m2 (197.2 to 366.5 cfm per 100 ft2) for unsealed tests where sheet metal screws were not us
4、ed to assemble the duct sections. The flat oval sealed leakage results were lower than those for spiral and longitudinal seam circular ducts reported in the ASHRAE Handbook. INTRODUCTIONUnsealed duct leakage depends on the machinery used for its fabrication, material thickness, assembly methods empl
5、oyed, and workmanship during installation. Duct leakage tests by ASHRAE/SMACNA/TIMA (1985) and Swim and Griggs (1995) have verified that a power law relation can represent the duct leakage from longitudinal seams and trans-verse joints of assembled duct sections. It was also confirmed that for the s
6、ame duct construction the behavior of duct leak-age was almost the same under negative and positive pressure. These tests have suggested that for unsealed or unwelded ducts the joint leakage dominates, as the longitudinal seam leakage is about 10% to 15% of the total duct leakage.There is a wide ran
7、ge of products and sealing methods available for ducts. A forecast of leakage class attainable by commonly used duct construction and sealing methods, based on the data obtained by Swim and Griggs (1995) and ASHRAE/SMACNA/TIMA (1985), is available in the Duct Design chap-ter of the ASHRAE Handbook (
8、2009). These data do not account for the presence of fittings, a realistic spacing of rect-angular and round duct transverse joints and duct-mounted components, such as access doors and balancing dampers. The leakage classes were calculated under the assumption of 0.82 joints per meter, or 25 joints
9、 per 100-ft of duct length. The stud-ies cited above suggest that duct system leakage rates are primarily a function of the geometry of the joint and seams, the sealing used (if any), and the pressure difference between the inside and outside of the duct. Future leakage classes should be adjusted fo
10、r typical rectangular and round transverse joint spac-ing, 1.2 m (4 ft) and 3.1 m (10 ft), respectively. Ducts possessing a lower proportion of joints would have less leakage in both the sealed and unsealed categories.Many researchers have previously attempted to perform in-situ measurements of the
11、effects of duct leakage on air distribution system performance and building envelope infil-tration; representative studies are by Modera (1989), Yuill and Musser (1997), Proctor (1998), and Walker (1999). Most of these studies have tended to compare different sealing tech-niques. Performance studies
12、 by Xu et al. (2000, 2004) of air distribution systems in light and large commercial buildings have reported air leakage ratios from one-quarter to one-third of the fan-supplied airflow in constant-air-volume systems. The air leakage from the ducts including supply and return, Flat Oval Duct Leakage
13、 Class MeasurementD.C. Gibbs S. Idem, PhDAssociate Member ASHRAE Member ASHRAED.C. Gibbs is a mechanical engineer with BWSC, Inc., in Nashville, TN. S. Idem is a professor in the Department of Mechanical Engineering at Tennessee Tech University, Cookeville, TN.AB-10-0032010, American Society of Heat
14、ing, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission
15、.388 ASHRAE Transactionswere reported in terms of the ASHRAE-defined leakage class with the reported values within a range much higher than the leakage classes predicted by the ASHRAE Handbook (2009) for unsealed ducts.Leakage measurement studies by Aydin and Ozerdem (2006) on round and rectangular
16、ducts for positive internal pressures were conducted along with a branched duct system having different duct diameters; the results were fitted to the power law model developed by J. Stratton from ETL data (ASHRAE/ SMACNA/TIMA 1985) and confirmed by Swim and Griggs (1995). Apparently leakage data ar
17、e unavailable in the literature for flat oval ducts. As a result the present project was initiated to study the leakage characteristics of spiral seam galvanized steel flat oval ducts.EXPERIMENTAL PROGRAMExperiments were performed to estimate the leakage class of three cross sections of flat oval du
18、cts. The tests conformed to requirements of SMACNAs HVAC Air Duct Leakage Test Manual (1985). The duct cross sections are listed in Table 1. In every instance the ducts were constructed from 24-ga galva-nized sheet metal with spiral seams. The test section consisted of a total of six duct sections.
19、Each duct section was 1.2 m (4-ft) in length, and individual sections were connected by means of standard beaded slip couplings. Then 19 mm (-in.) thick plywood caps secured with duct tape were used to seal the ends of the ducts (refer to Figure 1). Thereafter, the system was pres-surized with a wet
20、/dry shop vacuum connected to the ductwork by a combination of PVC and dryer hose tubing. The shop vacuum was capable of producing in excess of 2.5 kPa, equiv-alent to approximately 10-in water pressure or vacuum in the ductwork. A ball valve was used to regulate the pressure from the shop vacuum. T
21、he makeup air flow rate entering the enclosed system (which equaled the leakage rate) was deter-mined by measuring the pressure drop across a calibrated Meriam Instruments laminar flow element (LFE), model 50MC2-2. Care was taken to ensure that sufficient straight runs of tubes were mounted at the e
22、ntrance and exit of the LFE.Figure 1 Duct leakage test setup.Table 1. Flat Oval Duct Cross Section and SealingCross Sectionmm mm(in. in.)Seam Type Joint Type Joint SealingSurface Aream2(ft2)356 152 (14 6)Spiral(RL-1)Beaded Slip Sealed/Unsealed 6.48 (69.7)381 102(15 4)Spiral(RL-1)Beaded Slip Sealed/U
23、nsealed 6.42 (69.1)559 152(22 6)Spiral(RL-1)Beaded Slip Sealed/Unsealed 9.45 (101.7)2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). For personal use only. Additional reproduction, distr
24、ibution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.2010 ASHRAE 389Ambient pressure was measured with a Fortin-type barometer with an accuracy of 0.25-mm (0.01-in.) of mercury. Pressure taps constructed from 6.4 mm (1/4 in.) diameter cop
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAB100032010FLATOVALDUCTLEAKAGECLASSMEASUREMENTPDF

链接地址:http://www.mydoc123.com/p-454498.html