ASHRAE AB-10-002-2010 Measured and Predicted Pressure Loss in Corrugated Spiral Duct.pdf
《ASHRAE AB-10-002-2010 Measured and Predicted Pressure Loss in Corrugated Spiral Duct.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AB-10-002-2010 Measured and Predicted Pressure Loss in Corrugated Spiral Duct.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、380 ASHRAE TransactionsABSTRACTAn experimental program was initiated to determine the absolute roughness of three corrugated circular spiral ducts. The average absolute roughness value for these ducts was 0.85 mm (0.0028 ft). Pressure loss tests were likewise performed on a round standard spiral sea
2、m duct using Pitot-static tubes mounted at the duct centerline, and also using wall static pres-sure taps mounted on the duct surface at identical axial loca-tions. The absolute roughness values obtained by these two approaches were indistinguishable. The resulting average abso-lute roughness for th
3、e standard spiral duct was 0.12 mm (0.0004 ft). Pressure loss predictions for corrugated and standard spiral ducts are compared. INTRODUCTIONCorrugated spiral ducts are increasingly being used in aboveground HVAC systems. The presence of corrugations increases the rigidity and structural strength of
4、 the duct, so that lighter gauges can be employed in many applications. Under those circumstances corrugated ducts may be less expensive and easier to install than conventional spiral seam ducts. Furthermore their enhanced resistance to permanent deforma-tion allows them to be stacked higher for tra
5、nsportation and storage.In the present research the roughness characteristics of corrugated galvanized spiral ducts having a somewhat different corrugation profile from that examined by Kulkarni et al. (2009). The objective of this research was to verify whether minor corrugation profile and seam pi
6、tch variations have a significant impact on the resulting abso-lute roughness and roughness category. The test procedure was validated by measuring pressure loss characteristics of a standard conventional spiral seam duct per ASHRAE Standard 120. Those results were then compared to data presented pr
7、eviously in the literature. Pressure loss characteristics of conventional galvanized steel ducts with continuously rolled spiral seams have been described in Griggs et al. (1987). Similarly, roughness factors for galvanized steel spiral seam ducts with varying numbers of ribs have been reported in G
8、riggs et al. (1987). In these instances the data were not obtained by tests conducted in accordance with ASHRAE Standard 120. Until recently there has been a lack of corrugated galvanized spiral round duct information available to the designers of duct systems. However Kulkarni et al. (2009) used AS
9、HRAE Standard 120 to obtain pressure loss data for one particular corrugation configuration. EXPERIMENTAL PROGRAMThree round, spiral, 24 gauge, galvanized steel ducts with four corrugations between helical seams were tested in this project. The geometric details of the corrugations and seams are sho
10、wn in Figure 1; in the present study the depth and configuration of the corrugations differed from those tested in Kulkarni et al. (2009). The duct diameters were 203 mm (8 in.), 356 mm (14 in.), and 508 mm (20 in.). In each case the duct sections were 3.05 m (10 ft) in length, and were connected by
11、 beaded slip couplings possessing integral sealing gaskets. Each joint was further wrapped by commercial duct tape. The 356 mm (14 in.) diameter non-corrugated galvanized steel ducts tested in this project possessed a standard spiral seam (RL-1 seam per SMACNA (2005) having a pitch of 121 mm (4.75 i
12、n.). The 3.05 m (10 ft) duct sections were connected by beaded slip couplings and sealed using duct tape.Measured and Predicted Pressure Loss in Corrugated Spiral DuctD.C. Gibbs S. Idem, PhDAssociate Member ASHRAE Member ASHRAED.C. Gibbs is a mechanical engineer with BWSC, Inc., in Nashville, TN. S.
13、 Idem is a professor in the Department of Mechanical Engineering at Tennessee Tech University, Cookeville, TN.AB-10-0022010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). For personal use o
14、nly. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.2010 ASHRAE 381The test apparatus shown in Figure 2 (excerpted from ASHRAE Standard 120) was used to measure the pressure loss characteristics of the
15、corrugated and standard spiral duct. In every instance the duct test apparatus consisted of an entrance duct section to achieve fully developed flow (upstream length), the test section, and a tail portion (down-stream length). All tests were conducted with a plenum cham-ber and bellmouth combination
16、 situated between the upstream nozzle chamber and the downstream test section, per ASHRAE Standard 120. The plenum chamber had one settling screen with a 46.8% open area. The dimensions for each test setup are listed in Table 1. The duct diameters were measured in three planes and averaged. The appa
17、ratus, dimen-sions, and test procedures were in compliance with ASHRAE Standard 120.For tests conducted on corrugated ducts and conventional spiral ducts the pressure loss was measured using the static pressure ports of Pitot-static tubes mounted at the duct center-line at axial locations as prescri
18、bed by ASHRAE Standard 120. The standard spiral duct tests were also repeated using static wall pressure taps soldered onto the duct surface (at precisely the same locations as the Pitot-static tubes) in order to measure the pressure loss; the Pitot-static tubes were with-drawn from the test section
19、 for these tests. The pressure taps Figure 1 Geometric details of round corrugated duct.Figure 2 Straight duct test setup (ASHRAE 2008).2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). F
20、or personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.382 ASHRAE Transactionswere fashioned into a piezometric ring using flexible plastic tubing. The piezometer rings were connected to a
21、 single micromanometer by means of flexible tubing so as to measure the pressure drop across the test section. For all pressure loss tests static gage pressure was measured at each location by inserting tees into the pressure tubing. This procedure allowed for the determination of whether the use of
22、 Pitot-static tubes to measure pressure loss would yield similar results to measure-ments performed using wall static pressure taps.The system was blow-through. Airflow was generated by a 30-hp centrifugal fan. A cylindrical nozzle chamber was used for flow measurement, and a variable frequency driv
23、e was used to control air flow through the system. Screens mounted upstream and downstream of the nozzle board inside the chamber were used to settle the flow. The nozzle board contained four long-radius spun aluminum flow nozzles having throat diameters of 51-mm (2-in.), 102-mm (4-in.), 152-mm (6-i
24、n.) and 203-mm (8-in.). The nozzles were mounted on a 25-mm (1-in.) thick plywood board. Various combinations of flow nozzles were employed, depending on the desired flow rate. Nozzles that were not used were blocked using smooth vinyl balls. The pressure drop was measured by two piezometer rings lo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAB100022010MEASUREDANDPREDICTEDPRESSURELOSSINCORRUGATEDSPIRALDUCTPDF

链接地址:http://www.mydoc123.com/p-454497.html