ASHRAE 90 1-2013 SI ERTA-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf
《ASHRAE 90 1-2013 SI ERTA-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 90 1-2013 SI ERTA-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Page 1 of 10 2016 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2013 (SI Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings June 13, 2016 The corrections listed in this errata sheet apply to ANSI/ASHRAE/IES Standard 90.1-2013, SI Edition. The f
2、irst printing is identified on the outside back cover of the standard as “Product code: 86275 10/13” and the second printing as “Product code: 86275 1/15 Errata noted in the list dated 10/22/14 have been corrected.” The shaded items have been added since the previously published errata sheet dated M
3、arch 10, 2016 was distributed. Items identified with an asterisk “*” apply only to the first printing, they have already been incorporated into the second printing. NOTICE: ASHRAE now has a list server for Standing Standards Project Committee 90.1 (SSPC 90.1). Interested parties can now subscribe an
4、d unsubscribe to the list server and be automatically notified via e-mail when activities and information related to the Standard and the Users Manual is available. To sign up for the list server please visit Project Committee List Servers for Standard on the Technology / Standards section of the AS
5、HRAE website at http:/www.ashrae.org/resources-publications/periodicals/listserves. Page(s) Erratum 1* CONTENTS. In the table of contents change Informative Appendix G to Normative Appendix G. 3* 3.2 Definitions. Add the following definition to Section 3.2: (Note: Additions are shown in underline.)
6、boiler system: one or more boilers and their piping and controls that work together to supply steam or hot water to heat output devices remote from the boiler. 20* 3.3 Abbreviations and Acronyms. In Section 3.3 delete “ENVSTD Envelope System Performance Compliance Program”. 25 5.4.3.1.3 Acceptable M
7、aterial and Assemblies. In Section 5.4.3.1.3a and 5.4.3.1.3b delete the redundant text as shown below. (Note: Deletions are shown in strikethrough.) 5.4.3.1.3 Acceptable Materials and Assemblies. a. Materials that have an air permeance not exceeding 0.02 L/sm2under a pressure differential of 0.02 L/
8、sm2at 75 Pa when tested in accordance with ASTM E2178. The following materials meet these requirements: b. Assemblies of materials and components (sealants, tapes, etc.) that have an average air leakage not to exceed 0.2 L/sm2under a pressure differential of 0.2 L/sm2at 75 Pa when tested in accordan
9、ce with ASTM E2357, ASTM E1677, ASTM E1680, or ASTM E283. The following assemblies meet these requirements: Errata Sheet for ANSI/ASHRAE/IES Standard 90.1-2013 (SI edition) Page 2 of 10 2016 ASHRAE. All rights reserved. 26* 5.4.3.4 Vestibules. Add the following exceptions shown below. (Note: Additio
10、ns are shown in underline.) 8. Semiheated spaces. 9. Enclosed elevator lobbies for building entrances directly from parking garages. 35* 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Revise Section 5.5.3.1.1 as shown below. (Note: Additions are shown in underline and deletions are shown in
11、 strikethrough.) 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Roofs in Climate Zones 1 through 3 shall have one of the following: a. A minimum three-year-aged solar reflectance of 0.55 and a minimum three-year-aged thermal emittance of 0.75 when tested in accordance with CRRC-1 Standard b
12、. A minimum Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 using a convection coefficient of 12 W/m2K, based on three-year-aged solar reflectance and three-year-aged thermal emittance tested in accordance with CRRC-1 Standard c. Incr
13、eased roof insulation levels found in Table 5.5.3.1.1 Exceptions: 1. Ballasted roofs with a minimum stone ballast of 74 kg/m2or 117 kg/m2pavers 2. Vegetated roof systems that contain a minimum thickness of 63.5 mm of growing medium and covering a minimum of 75% of the roof area with durable planting
14、s 3. Roofs where a minimum of 75% of the roof area a. is shaded during the peak sun angle on June 21 by permanent components or features of the building; b. is covered by offset photovoltaic arrays, building-integrated photovoltaic arrays, or solar air or water collectors; or c. is permitted to be i
15、nterpolated using a combination of 1 and 2 above 4.d. Steep-sloped roofs 5.e. Low-sloped metal building roofs in Climate Zones 2 and 3 6.f. Roofs over ventilated attics, roofs over semiheated spaces, or roofs over conditioned spaces that are not cooled spaces 7.g. Asphaltic membranes in Climate Zone
16、s 2 and 3 The values for three-year-aged solar reflectance and three-year-aged thermal emittance shall be determined by a laboratory accredited by a nationally recognized accreditation organization and shall be labeled and certified by the manufacturer. 37* 5.5.4.4.2 SGHC of Skylights. Change except
17、ion 2 to Section 5.5.4.4.2 as shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.) 2. For dynamic glazing, the minimum SHGC shall be used to demonstrate compliance with this section. Dynamic glazing shall be considered separately from other skylights vertic
18、al fenestration, and area-weighted averaging with other skylights vertical fenestration that is not dynamic glazing shall not be permitted. 41* 6.1.1.3 Alterations to Heating, Ventilating, Air Conditioning, and Refrigeration in Existing Buildings. Change the exceptions immediately following Section
19、6.1.1.3.5 to read “Exceptions to Errata Sheet for ANSI/ASHRAE/IES Standard 90.1-2013 (SI edition) Page 3 of 10 2016 ASHRAE. All rights reserved. 6.1.1.3:” The exceptions apply to Section 6.1.1.3 rather than Section 6.1.1.3.5 alone. 41* 6.2.1 Compliance. Revise Section 6.2.1 as shown below. (Note: Ad
20、ditions are shown in underline.) 6.2.1 Compliance. Compliance with Section 6 shall be achieved by meeting all requirements for Sections 6.1, “General”; Section 6.7, “Submittals”; Section 6.8, “Minimum Equipment Efficiency Tables”; and one of the following: a. Section 6.3, “Simplified Approach Option
21、 for HVAC Systems” b. Sections 6.4, “Mandatory Provisions” and 6.5, “Prescriptive Path” c. Sections 6.4, “Mandatory Provisions” and 6.6, “Alternative Compliance Path” 43* 6.4.1.2.1 Water-Cooled Centrifugal Chilling Packages. Change the first sentence in Section 6.4.1.2.1 as shown below. The remainde
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE9012013SIERTA2016ENERGYSTANDARDFORBUILDINGSEXCEPTLOWRISERESIDENTIALBUILDINGSPDF

链接地址:http://www.mydoc123.com/p-454422.html