ASHRAE 90 1-2013 I-P ERTA-2015 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf
《ASHRAE 90 1-2013 I-P ERTA-2015 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 90 1-2013 I-P ERTA-2015 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Page 1 of 10 2014 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2013 (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings March 20, 2015 The corrections listed in this errata sheet apply to ANSI/ASHRAE/IES Standard 90.1-2013, I-P Edition. Th
2、e first printing is identified on the outside back cover of the standard as “Product code: 86273 10/13” and the second printing as “Product code: 86273 12/13 Errata noted in the list dated 12/9/13 have been corrected.” The shaded items have been added since the previously published errata sheet date
3、d October 22, 2014 was distributed. Items identified with an asterisk “*” apply only to the first printing, they have already been incorporated into the second printing. NOTICE: ASHRAE now has a list server for Standing Standards Project Committee 90.1 (SSPC 90.1). Interested parties can now subscri
4、be and unsubscribe to the list server and be automatically notified via e-mail when activities and information related to the Standard and the Users Manual is available. To sign up for the list server please visit Project Committee List Servers for Standard on the Technology / Standards section of t
5、he ASHRAE website at http:/www.ashrae.org/resources-publications/periodicals/listserves. Page(s) Erratum 1* CONTENTS. In the table of contents change Informative Appendix G to Normative Appendix G. 3* 3.2 Definitions. Add the following definition to Section 3.2: (Note: Additions are shown in underli
6、ne.) boiler system: one or more boilers and their piping and controls that work together to supply steam or hot water to heat output devices remote from the boiler. 20 3.3 Abbreviations and Acronyms. In Section 3.3 delete “ENVSTD Envelope System Performance Compliance Program”. 26 5.4.3.4 Vestibules
7、. Add the following exceptions shown below. (Note: Additions are shown in underline.) 8. Semiheated spaces. 9. Enclosed elevator lobbies for building entrances directly from parking garages. 35* 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Revise Section 5.5.3.1.1 as shown below. (Note: A
8、dditions are shown in underline and deletions are shown in strikethrough.) 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Roofs in Climate Zones 1 through 3 shall have one of the following: a. A minimum three-year-aged solar reflectance of 0.55 and a minimum three-year-aged thermal Errata S
9、heet for ANSI/ASHRAE/IES Standard 90.1-2013 (I-P edition) Page 2 of 10 2015 ASHRAE. All rights reserved. emittance of 0.75 when tested in accordance with CRRC-1 Standard b. A minimum Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 usi
10、ng a convection coefficient of 2.1 Btu/hft2F, based on three-year-aged solar reflectance and three-year-aged thermal emittance tested in accordance with CRRC-1 Standard c. Increased roof insulation levels found in Table 5.5.3.1.1 Exceptions: 1. Ballasted roofs with a minimum stone ballast of 17 lb/f
11、t2or 23 lb/ft2pavers 2. Vegetated roof systems that contain a minimum thickness of 2.5 in. of growing medium and covering a minimum of 75% of the roof area with durable plantings 3. Roofs where a minimum of 75% of the roof area a. is shaded during the peak sun angle on June 21 by permanent component
12、s or features of the building; b. is covered by offset photovoltaic arrays, building-integrated photovoltaic arrays, or solar air or water collectors; or c. is permitted to be interpolated using a combination of 1 and 2 above 4.d. Steep-sloped roofs 5.e. Low-sloped metal building roofs in Climate Zo
13、nes 2 and 3 6.f. Roofs over ventilated attics, roofs over semiheated spaces, or roofs over conditioned spaces that are not cooled spaces 7.g. Asphaltic membranes in Climate Zones 2 and 3 The values for three-year-aged solar reflectance and three-year-aged thermal emittance shall be determined by a l
14、aboratory accredited by a nationally recognized accreditation organization and shall be labeled and certified by the manufacturer. 37 5.5.4.4.2 SGHC of Skylights. Change exception 2 to Section 5.5.4.4.2 as shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.
15、) 2. For dynamic glazing, the minimum SHGC shall be used to demonstrate compliance with this section. Dynamic glazing shall be considered separately from other skylights vertical fenestration, and area-weighted averaging with other skylights vertical fenestration that is not dynamic glazing shall no
16、t be permitted. 41 6.1.1.3 Alterations to Heating, Ventilating, Air Conditioning, and Refrigeration in Existing Buildings. Change the exceptions immediately following Section 6.1.1.3.5 to read “Exceptions to 6.1.1.3:” The exceptions apply to Section 6.1.1.3 rather than Section 6.1.1.3.5 alone. 41* 6
17、.2.1 Compliance. Revise Section 6.2.1 as shown below. (Note: Additions are shown in underline.) 6.2.1 Compliance. Compliance with Section 6 shall be achieved by meeting all requirements for Sections 6.1, “General”; Section 6.7, “Submittals”; Section 6.8, “Minimum Equipment Efficiency Tables”; and on
18、e of the following: a. Section 6.3, “Simplified Approach Option for HVAC Systems” b. Sections 6.4, “Mandatory Provisions” and 6.5, “Prescriptive Path” c. Sections 6.4, “Mandatory Provisions” and 6.6, “Alternative Compliance Path” 46 6.4.3.8 Ventilation Controls for High-Occupancy Areas. Delete “grea
19、ter than” from the first sentence as shown below. Errata Sheet for ANSI/ASHRAE/IES Standard 90.1-2013 (I-P edition) Page 3 of 10 2015 ASHRAE. All rights reserved. 6.4.3.8 Ventilation Controls for High-Occupancy Areas. Demand control ventilation (DCV) is required for spaces larger than 500 ft2and wit
20、h a design occupancy for ventilation of greater than 25 people per 1000 ft2of floor area and served by systems with one or more of the following: 49 6.5.1 Economizers. In the first sentence change Section 6.5.1.6 to 6.5.1.5. 50-52 6.5.1.3 Integrated Economizer Control and Table 6.5.1.4 DX Cooling St
21、age Requirements for Modulating Airflow Units. Correct as shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.) 6.5.1.3 Integrated Economizer Control. Economizer systems shall be integrated with the mechanical cooling system and be capable of providing parti
22、al cooling even when a. b. 6.5.1.4 c. Effective 1/1/2014, all other DX units, including those that control space temperature by modulating the airflow to the space, shall comply with the requirements of Table 6.5.1.3 6.5.1.4. 6.5.1.54 Economizer Heating System Impact. 6.5.1.65 Economizer Humidificat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE9012013IPERTA2015ENERGYSTANDARDFORBUILDINGSEXCEPTLOWRISERESIDENTIALBUILDINGSPDF

链接地址:http://www.mydoc123.com/p-454414.html