ASHRAE 90 1-2013 I-P ERTA-2013 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf
《ASHRAE 90 1-2013 I-P ERTA-2013 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 90 1-2013 I-P ERTA-2013 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Page 1 of 3 2013 ASHRAE. All rights reserved. ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD 90.1-2013 (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings December 9, 2013 The corrections listed in this errata sheet apply to ANSI/ASHRAE/IES Standard 90.1-2013, I-P Edition. T
2、he first printing is identified on the outside back cover of the standard as “Product code: 86273 10/13”. The shaded item has been added since the previously published errata sheet dated November 14, 2013 was distributed. NOTICE: ASHRAE now has a list server for Standing Standards Project Committee
3、90.1 (SSPC 90.1). Interested parties can now subscribe and unsubscribe to the list server and be automatically notified via e-mail when activities and information related to the Standard and the Users Manual is available. To sign up for the list server please visit Project Committee List Servers for
4、 Standard on the Technology / Standards section of the ASHRAE website at http:/www.ashrae.org/resources-publications/periodicals/listserves. Page(s) Erratum 1 CONTENTS. In the table of contents change Informative Appendix G to Normative Appendix G. 3 3.2 Definitions. Add the following definition to
5、Section 3.2: (Note: Additions are shown in underline.) boiler system: one or more boilers and their piping and controls that work together to supply steam or hot water to heat output devices remote from the boiler. 35 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Revise Section 5.5.3.1.1 a
6、s shown below. (Note: Additions are shown in underline and deletions are shown in strikethrough.) 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance. Roofs in Climate Zones 1 through 3 shall have one of the following: a. A minimum three-year-aged solar reflectance of 0.55 and a minimum three-yea
7、r-aged thermal emittance of 0.75 when tested in accordance with CRRC-1 Standard b. A minimum Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 using a convection coefficient of 2.1 Btu/hft2F, based on three-year-aged solar reflectance a
8、nd three-year-aged thermal emittance tested in accordance with CRRC-1 Standard c. Increased roof insulation levels found in Table 5.5.3.1.1 Exceptions: 1. Ballasted roofs with a minimum stone ballast of 17 lb/ft2or 23 lb/ft2pavers 2. Vegetated roof systems that contain a minimum thickness of 2.5 in.
9、 of growing medium and covering a minimum of 75% of the roof area with durable plantings 3. Roofs where a minimum of 75% of the roof area a. is shaded during the peak sun angle on June 21 by permanent components or Errata Sheet for ANSI/ASHRAE/IES Standard 90.1-2013 (I-P edition) Page 2 of 3 2013 AS
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE9012013IPERTA2013ENERGYSTANDARDFORBUILDINGSEXCEPTLOWRISERESIDENTIALBUILDINGSPDF

链接地址:http://www.mydoc123.com/p-454412.html