ASHRAE 4693-2004 Development and Implementation of HVAC-KBCD A Knowledge-Based Expert System for Conceptual Design of HVAC&R System - Part 2 Application to Office Buildings《制定和实施HV.pdf
《ASHRAE 4693-2004 Development and Implementation of HVAC-KBCD A Knowledge-Based Expert System for Conceptual Design of HVAC&R System - Part 2 Application to Office Buildings《制定和实施HV.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4693-2004 Development and Implementation of HVAC-KBCD A Knowledge-Based Expert System for Conceptual Design of HVAC&R System - Part 2 Application to Office Buildings《制定和实施HV.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、4693 Analysis of the Impact of C02-Based Deman d-Con t ro I led Vent i lati on Strateg es on Energy Consumption Moncef Krarti, Ph.D., P.E. Member ASHRAE ABSTRACT This paper presents an integrated IAQiHVAC simulation environment that can model the impact of contaminant-based demand-controlled ventila
2、tion (DCV) strategies on both indoor air quality and HVAC system energy use for multizone buildings. The predictions of the integrated IAQ/HVAC simu- lation environment are first validated against experimental data obtained from laboratory testing. Then the simulation environment is used to investig
3、ate the performance of three ventilation control strategies, namely: one conventional control using fixed-position for outside air damper and two DCV strategies, including on/of control and proportional- integral-derivative (PID) control. In particulal; a series of parametric analyses is conducted t
4、o determine the impact of selected design and operational features ofDCVstrategies on both indoor air quality and HVAC system energy use. The sensitivity analysis revealed that leakage from outside air dampers, use of a temperature economizers, selection of CO, sensors, tuning of PID controllers, an
5、d selection of CO, setpoints can have a signijicant impact on both indoor air qual- ity and energy consumption of HVAC systems. INTRODUCTION The performance of CO,-based demand-controlled venti- lation (DCV) strategies has been extensively investigated over the last decade. Most of the existing stud
6、ies on DCV are based on simulation analysis and have primarily focused on the potential energy savings of the C02-based demand-controlled ventilation systems (Knoespel et al. 1991; Vaculik and Plett 1993; Emmerich et al. 1994; Sorensen 1996). Only few DCV control strategies have been implemented and
7、 evaluated in real Mohsin Al-Alawi, Ph.D. buildings or under laboratory conditions. Studies have been reported for the following DCV strategies: Odoff controls (Davidge 199 1) Proportional controls (Fleury 1992; Donnini et al. 1991; Haghighat and Donnoni 1992) Step-flow controls (Fehlmann et al. 199
8、3; Zamboni et al. 1991) PID controls (Alawi and Krarti 2002) For most of the reported studies, energy savings of DCV strategies have been estimated relative to a fixed ventilation rate control strategy. The fixed ventilation rate is determined based on ASHRAE Standard 62-2001 (ASHRAE 2001), which sp
9、ecifies minimum ventilation flow rates for various building types and occupancy levels. While the existing field and simulation studies have provided useful insights on the potential benefits of demand- controlled ventilation, the impact of design andor operating parameters of DCV controls have not
10、been extensively explored. Various factors affect the performance of DCV controllers, such as CO, sensor selection, sampling rate of CO, concentration, outdoor air damper leakage, and use of temperature or enthalpy economizer controls. This paper presents a comprehensive simulation environ- ment cap
11、able of modeling the transient effects on both indoor air quality and HVAC system energy use of various design and operational parameters associated with DCV control strate- gies. First, the models and algorithms that constitute the simu- lation environment are briefly described. Then, the predictio
12、ns of the simulation environment are validated against laboratory testing data. Finally, the results of several parametric analyses are summarized. In particular, the effects on both indoor air Moncef Krarti is an associate professor at the University of Colorado, Boulder, Colo. Mohsin Al-Alawi is a
13、n assistant professor at the Univer- sity of Bahrain, Al-Manama, Bahrain. 274 02004 ASHRAE. quality and HVAC system energy use are determined for selected design and operational features, including leakage from outside air dampers, use of temperature economizers, selection of CO, sensors, tuning of
14、the PID controllers, and selection of CO, setpoints. DESCRIPTION OF THE IAQIHVAC SIMULATION ENVIRONMENT Figure 1 illustrates the basic models used to develop an TAQHVAC simulation environment suitable to investigate the performance of CO2-based demand-controlled ventilation strategies under various
15、design and operating conditions. A brief description of each model is given below. The DOE-2 program is used to determine hourly sensible and latent loads. Input parameters for the DOE-2 program include building characteristics and location, occupancy schedule, zone setpoint temperatures, and weathe
16、r. From the hourly results, the sensible and latent loads are deter- mined for any time step using linear interpolation. The VAV model reads the sensible and latent loads calcu- lated from the DOE-2 program and determines zone total supply air. At the same time, the CO, control program determines th
17、e fraction of outside air to be supplied during each time step based on the contaminant concentration in the zone and the CO2-based demand-controlled strategy used. The output variables of the VAV model include pre- heat, reheat, and cooling coil heat transfer rates and supply fan electrical power c
18、onsumption. I I VAV UODFL CON moi. MODEL Wrathsr data EQUIPMENTMODEL a Weatbar dala Chiller dal. Boiler dali coalrn1 %,ralc*y Powrr rooriomption Il CO, TRANSPORT Fgure I Basic models integrated within the IAQ/HVAC simulation module. The CO, transport model used in conjunction with the control progra
19、m provides the variation of indoor CO, concentration as zone outside air intake changes with time. The variation in the CO, concentration is then fed back to a control module that adjusts the outdoor airflow rates to be supplied to the zones depending on the C02-based demand- control ventilation str
20、ategy. The HVAC equipment models estimate the energy consumption for chillers, fans, and boilers based on the heating and cooling transfer rate data received from the VAV model. Input parameters of the HVAC equipment models include weather data and equipment performance data. A more detailed descrip
21、tion of the last three models is provided in the following sections. Air-Handling Unit (AHU) System Model A variable air volume (VAV) system is a single-path system that controls the indoor temperature within a zone by varying the amount of air supply. The damper of the VAV terminal unit adjusts the
22、 airflow rate supplied to the zone depending on heating or cooling loads. The discharge air temperature is kept constant and equal to the supply air temperature from the air-handling unit plus any temperature increase due to heat gains (for instance, from the supply fan motor). As indicated in Figur
23、e 2, a VAV system consists of a central air-handling unit and VAV terminal units with reheat coils located in the zones. The AH unit itself includes a supply fan, a cooling coil, a preheat coil, and an outside air economizer. The AHU delivers air at a controlled fixed temperature, while in the VAV u
24、nit terminals, the damperposi- tion is adjusted to supply the airflow rate needed to meet the thermal load for each zone. In particular, when the zone cool- Fgure 2 Diagram of the variable air volume (VAV) model. ASH RAE Transactions: Research 275 VAV MODFJ. i-i ,-I “ _+ Toother Con c, I I .Y . , “.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE46932004DEVELOPMENTANDIMPLEMENTATIONOFHVACKBCDAKNOWLEDGEBASEDEXPERTSYSTEMFORCONCEPTUALDESIGNOFHVACRSYSTEMPART2APPLICATIONTOOFFICEBUILDINGS

链接地址:http://www.mydoc123.com/p-454276.html