ASHRAE 4688-2004 Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units《户外和回流气流 在典型的空气处理设备RP-1045中的热混合》.pdf
《ASHRAE 4688-2004 Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units《户外和回流气流 在典型的空气处理设备RP-1045中的热混合》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4688-2004 Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units《户外和回流气流 在典型的空气处理设备RP-1045中的热混合》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、4688 (RP-1045) Thermal Mixing of Outdoor and Return Airflows in Typical Air-Handling Units Miiind Mainkar Fathi Finaish Associate Member ASHRAE Harry J. Sauer, Jr., Ph.D., P.E. FellowlLife Member ASHRAE Member ASHRAE Robert Van Beceiaere ABSTRACT Thispaper examines thermal mixingofoutdoor andreturn
2、airstreams in typical air-handling units equipped with parallel blade dampers. The mixing ofthe two airstreams in rectangu- lar and square mixing chambers is studiedfor eight diferent dampers and blade orientations. Testing is conducted at a total supply air of I6000 CFM with outdoor flow percentage
3、s of 15% and 30%. The temperature diferential between the outdoor and return airflows is kept at 40F Damper blades with chords of4 and 6 inches are tested. To examine the mixing ofthe two airstreams, temperature distributions in the mixed region are measured by an array ofthermocouples and utilized
4、to compute the thermal mixing eflectiveness of the mixedjlow. It appears that the relative flow momentum ofthe two streams plays an important role in the mixing. Values ofrange mixing efectiveness increase signijcantly with increase in the return air velocity. However, this conclusion is not applica
5、ble to conjigurations with minimum outside air in which cold spots can occur downstream in the mixing box. Retesting of conjig- urations producing the least stratijcation at 50% total supply airflow shows that thermal mixing is degraded, particularlyfor the cases ofl5% outside air: INTRODUCTION Mixi
6、ng of two airstreams has attracted considerable attention in the HVAC industry. Increased awareness about indoor air quality (IAQ) among the end-users and stringent standards governing IAQ in buildings dictate an increase in the amount of outdoor air introduced in the building. Moreover, mixing of a
7、 cold OA stream with a hot RA stream in winter poses serious problems of stratification (Haines I 980; Buchko 1999), which further leads to coil freeze-ups (Alyea 1958), sensor errors, and nuisance trips. The most well known effects of stratification are repeated shutdowns due to low-limit ther- mos
8、tat (freeze-stat) trips and fi-ozen cooling coils (Delaney et al. 1984). Another effect is increased sensor error (Ka0 1985). With the newly revised ASHRAE Standard 62-200 1, the seri- ousness of solving the problems associated with stratification has increased due to increased interest in adding ve
9、ntilation air to combat IAQ problems. The gravity of this issue is further increased due to lack of sufficient information about stratifi- cation in the HVAC environment in textbooks or journals. Under such circumstances, researchers and professionals in the field often tend to analyze this problem
10、using empirical observations. One common method suggested to improve mixing has been to introduce outdoor air at the top of the mixing box. The reasoning behind this suggestion is that the cold outside air will drop due to density difference and mix with the warmer return air that will be introduced
11、 from the side. In reality, the momentum of the return airstream is typically greater than the force due to density difference and the cold air introduced from the top is simply carried downstream before it has time to drop (Robinson 1999). Lower air velocities through the dampers and duct configura
12、tion were also suspected to be the cause of lower mixing effectiveness (Robinson 1998). With regard to the air-handling unit/mixing box design, Haines (1980) has presented a discussion of practices that may be used to improve mixing; however, no information concerning the performance of the suggeste
13、d methods was included in the discussion. Experimental work done by Robinson (1999) on air-handling unit combination mixing/filter boxes revealed that the placement of filters within the mixing box decreases the mixing effectiveness of an AHU mixing box. Even with the Milind Mainkar is a mechanical
14、engineer at Bums and McDonnell, Kansas City, Mo. Fathi Finaish and Hank Sauer are professors in the Department of Mechanical, Aerospace Engineering and Engineering Mechanics, University of Missouri-Rolla, Rolla, Mo. Robert Van Becelaere is the vice president of engineering at Ruskin Dampers and Louv
15、ers, Kansas City, Mo. 194 02004 ASHRAE filters removed from the mixing box, the increase in the mixing effectiveness obtained is not sufficient to reduce the stratification to acceptable levels. Mixing needs to be increased to avoid frozen coils and freeze-stat trips in the future. Hence, it was pro
16、posed to either increase the length of the mixing box to provide additional mixing length or to install static air mixers. Static mixers enhance the mixing effective- ness-but at the cost of additional pressure loss. Also, space is a major constraint in design of AHU. In this paper, we present resul
17、ts from a series of tests to measure the thermal mixing for eight configurations with different outdoor and return damper orientations, blade size, and aspect ratios for 15% and 30% outdoor air. Special atten- tion was paid to the parametric combination that results in the most and the least mixing.
18、 Temperature distributions in the mixed region were measured and utilized to compute thermal mixing effectiveness. TEST CONFIGURATIONS AND FACILITY As seen in Figure 1, eight flow configurations are tested. All the tests are conducted using parallel blade dampers with blade sizes of 4 and 6 inches.
19、Two damper aspect ratios-3: 1 and 1:l-are tested. The damper blades are oriented to direct the two airstreams into each other for configurations 4, 5, 7, and 8. The blades are oriented in the same directions for configurations 1, 2, 3, and 6. The testing was conducted at the RUSKIN Research and Deve
20、lopment Laboratory located in Kansas City, Mo. A 7.5 ft test chamber, constructed in accordance with AMCA standard _ /t 2 XED IR O 500-89, is used as the air supply for the tests. The flow is main- tained by a blower at the end of the 7.5 ft chamber, which draws air through the chamber. This blower
21、is controlled by a frequency-control drive and is capable of producing 16000 CFM flow. Tests are conducted at 15% and 30% outside air by volume, which corresponds to 2,400 CFM and 4,800 CFM, respectively. The outside air dampers are sized for velocities of 500 and 1500 fpm. Similarly, the return air
22、 dampers are sized at 85% of total supply air and velocities of 1 O00 and 2000 fpm. The temperature differential between the return and outside airstreams is maintained constant at 4OoF, irrespective of the outside air temperature, by heating the return airstream. The 7.5 ft chamber has nine accurat
23、ely calibrated flow- measuring orifices, which are used to maintain flow control. Suitable instrumentation (manometers, differential pressure gauges, etc.) is used to monitor nozzle pressure drop, static pressure, and airflow monitoring station pressure drop. The return air damper is mounted in a sl
24、eeve containing an airflow monitoring station. The fresh air dampers are attached to a ducted system, which is connected to an outside air source. Figure 2 shows a three-dimensional view of the test facility with a broad classification of its major components. The outside airstream and the return ai
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE46882004THERMALMIXINGOFOUTDOORANDRETURNAIRFLOWSINTYPICALAIRHANDLINGUNITS 户外 回流 气流 典型 空气 处理 设备 RP1045

链接地址:http://www.mydoc123.com/p-454271.html