1、*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 00.00 10 (November 2008)-Preparing Activity: USACE SupersedingUFGS-28 31 00.00 10 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2008*SECTION TABLE OF CONTENTSDIVISION 28 - ELECTRONIC SAFETY AND SECURI
2、TYSECTION 28 31 00.00 10FIRE DETECTION AND ALARM SYSTEM, DIRECT CURRENT LOOP11/08PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.2.1 Operation1.2.2 Operational Features1.2.3 Alarm Functions1.2.4 Primary Power1.2.5 Battery Backup Power1.2.6 Interface With Existing Fire Alarm Equipment1.2.7 Interf
3、ace With Other Equipment1.3 SUBMITTALS1.4 QUALITY ASSURANCE1.4.1 Qualifications1.4.2 Engineer and Technician1.4.3 Installer1.4.4 Fire Protection Engineer1.4.5 Detail Drawings1.5 TECHNICAL DATA AND COMPUTER SOFTWARE1.6 DELIVERY, STORAGE, AND HANDLING1.7 SPECIAL TOOLS AND SPARE PARTSPART 2 PRODUCTS2.1
4、 STANDARD PRODUCTS2.2 NAMEPLATES2.3 CONTROL PANEL2.3.1 Remote System Trouble Audible/Visual Appliance2.3.2 Circuit Connections2.3.3 System Expansion and Modification Capabilities2.4 STORAGE BATTERIES2.5 BATTERY CHARGER2.6 MANUAL FIRE ALARM STATIONS2.7 FIRE DETECTING DEVICES2.7.1 Heat Detectors2.7.1.
5、1 Combination Fixed-Temperature and Rate-of-Rise DetectorsSECTION 28 31 00.00 10 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.7.1.2 Rate Compensating Detectors2.7.1.3 Fixed Temperature Detectors2.7.2 Smoke Detectors2.7.2.1 Ionization Detec
6、tors2.7.2.2 Photoelectric Detectors2.7.2.3 Projected Beam Smoke Detectors2.7.2.4 Duct Detectors2.7.3 Combination Smoke and Heat Detectors2.7.4 Flame Detectors2.7.4.1 Infrared (IR) Single Frequency Flame Detector2.7.4.2 Infrared (IR) Dual Frequency Flame Detector2.7.4.3 Ultraviolet (UV) Flame Detecto
7、rs2.7.4.4 Combination UV/IR Flame Detector2.8 NOTIFICATION APPLIANCES2.8.1 Alarm Bells2.8.2 Alarm Horns2.8.3 Chimes2.8.4 Visual Notification Appliances2.8.5 Combination Audible/Visual Notification Appliances2.9 REMOTE ANNUNCIATION EQUIPMENT2.9.1 Remote Annunciator2.9.2 Remote Graphic Annunciator2.10
8、 FIRE DETECTION AND ALARM SYSTEM PERIPHERAL EQUIPMENT2.10.1 Electromagnetic Door Hold-Open Devices2.10.2 Conduit2.10.3 Wiring2.11 TRANSMITTERS2.11.1 Radio Alarm Transmitters2.11.1.1 Transmitter Power Supply2.11.1.2 Radio Alarm Transmitter Housing2.11.1.3 Antenna2.11.2 Master Fire Alarm Boxes2.11.3 T
9、elephonic Reporting SystemPART 3 EXECUTION3.1 EXAMINATION3.2 INSTALLATION3.2.1 Power Supply for the System3.2.2 Wiring3.2.3 Control Panel3.2.4 Detectors3.2.5 Notification Appliances3.2.6 Annunciator Equipment3.2.7 Supervisory and Alarm Contacts3.3 OVERVOLTAGE AND SURGE PROTECTION3.3.1 Power Line Sur
10、ge Protection3.3.2 Low Voltage DC Circuits Surge Protection3.4 GROUNDING3.5 SUPERVISING STATION PROVISIONS3.5.1 Revisions to Existing Facilities3.5.2 Additions to Existing Facilities3.6 TRAINING3.7 TESTING3.7.1 Preliminary Tests3.7.2 Acceptance Test- End of Section Table of Contents -SECTION 28 31 0
11、0.00 10 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 00.00 10 (November 2008)-Preparing Activity: USACE SupersedingUFGS-28 31 00.00 10 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences a
12、re in agreement with UMRL dated October 2008*SECTION 28 31 00.00 10FIRE DETECTION AND ALARM SYSTEM, DIRECT CURRENT LOOP11/08*NOTE: This guide specification covers the requirements for fire detection and alarm systems, direct current loop.Edit this guide specification for project specific requirement
13、s by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and
14、should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: A smoke
15、detector should be shown on the drawings per NFPA 72, paragraph 1-5.6. The following information should be on the project drawings:1. On electrical floor plans, show location of control panel, batteries and charger, transmitter, annunciator, primary power supply, remote trouble device, remote annunc
16、iator, detectors, notification appliances, and each alarm initiating device including fire extinguishing system switches.2. Show single-line fire alarm riser diagram, device and zone schedules. Each device on the riser SECTION 28 31 00.00 10 Page 3Provided by IHSNot for ResaleNo reproduction or netw
17、orking permitted without license from IHS-,-,-should be identified by type and location, with device number. Indicate connection of equipment by circuit runs, or conduit runs.*1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publi
18、cations are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Referenc
19、e Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below
20、 form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ACOUSTICAL SOCIETY OF AMERICA (ASA)ASA S3.41 (1990; R 2001) Audible Emergency Evacuation Signal (ASA 96)FM GLOBAL (FM)FM P7825a (2005) Approval Guide Fire Prote
21、ctionINSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)IEEE C62.41.1 (2002) IEEE Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power CircuitsIEEE C62.41.2 (2002) IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power CircuitsNATI
22、ONAL FIRE PROTECTION ASSOCIATION (NFPA)NFPA 1221 (2006; Errata 2006) Installation, Maintenance and Use of Emergency Services Communications SystemsNFPA 70 (2007; AMD 1 2008) National Electrical Code - 2008 EditionSECTION 28 31 00.00 10 Page 4Provided by IHSNot for ResaleNo reproduction or networking
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYUFGS28310000102008FIREDETECTIONANDALARMSYSTEMDIRECTCURRENTLOOP 直流 线圈 火灾 检测 报警 系统 PDF

链接地址:http://www.mydoc123.com/p-449675.html