1、 MIL-PRF-32389 14 Aug 2013 PERFORMANCE SPECIFICATION LOAD BANK, ELECTRICAL This specification is approved for use by the Communication-Electronic Research and Development Center (CERDEC) and is available for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This d
2、ocument specifies the requirements for the design modification, fabrication, integration, test, and verification of a Load Bank, Electrical, hereinafter referred to as Load Bank. The Load Bank is intended to replace the TS-4216/G Load Bank (6625-01-220-2619), which is defined by military specificati
3、on MIL-L-52366. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While
4、every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this specification, whether or not they are listed. 2.2 Government Documents 2.2.1 Specifications, standards, a
5、nd handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. AMSC N/A FSC 6150 INCH-POUND Comments, suggestions, or question
6、s on this document should be addressed to Communication Electronic Research and Development Center (CERDEC), ATTN: RDER-PRO, Aberdeen Proving Ground, MD 21005 or emailed to us at army.apg.cerdec.mbx.standardization-crxmail.mil. Since contact information can change, you may want to verify the currenc
7、y of this address information using the ASSIST Online database at https:/assist.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32389 2 DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-PRF-28800 Performance Specification, Test Equipment For
8、Use With Electrical and Electronic Equipment, General Specification (Copies of this document are available online at http:/quicksearch.dla.mil/ or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) DEPARTMENT OF DEFENSE STANDARDS MIL-STD-1472
9、 Human Engineering MIL-STD-13231 Marking for Electronic Items (Copies of this document are available online at http:/quicksearch.dla.mil/ or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 Order of precedence. In the event of a conflic
10、t between the text of this document and the references cited herein, the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 Equipment sample requirements. When specif
11、ied (see 6.2), sample equipment shall be provided for inspections as specified in 3.1.1 and 3.1.2. 3.1.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection (see 4.2). 3.1.2 Conformance inspection. When specified (see 6.2), a sample shall be subjected to
12、conformance inspection (see 4.3). 3.2 Mode of Operation Requirements. The overall functional capability of the Load Bank shall be rated for continuous and operational performance providing reliable and safe conditions for testing and maintaining electrical generating equipment. 3.2.1 Load Power Capa
13、city. The Load Bank shall be specified for resistive standard load capacity consisting of single-phase and three-phase voltage ratings. The minimum load capacity ratings are provided in Table 1. Table I. Load Power Capacity MIN LOAD CAPACITY VOLTAGE RATING PHASE/FREQUENCY MIN LOAD STEP VALUES 60 kW
14、208 VAC 3-Phase/60 Hz 5 kW, 10 kW, 15 kW, 30 kW, 60 kW 3 kW 120 VAC 1-Phase/60 Hz 1 kW, 2 kW, 3 kW 3.2.2 Load Capacity. The Load Bank shall support single phase and three-phase load capacities. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-
15、32389 3 3.2.2.1 Three-Phase Load Capacity. The Load Bank shall provide at least 60 kW three-phase load capacity. 3.2.2.2 Single-Phase Load Capacity. The Load Bank shall provide at least 3 kW single-phase load capacity. 3.2.3 Voltage Rating. The Load Bank shall provide voltage rating for single phase
16、 and three phase configurations. 3.2.3.1 Three Phase Voltage Rating. The Load Bank shall provide 208 VAC voltage rating for three-phase load capacity. 3.2.3.2 Single Phase Voltage Rating. The Load Bank shall provide 120 VAC voltage rating for single-phase load capacity. 3.2.4 Phase/Frequency. The Lo
17、ad Bank shall provide operational functions for 60 Hz and 400 Hz generators. 3.2.4.1 60 Hz Generator. The Load Bank shall operate at 60 Hz for single phase and three-phase configurations generators. 3.2.4.2 400 Hz Generator. The Load Bank shall provide functional capability to support 400 Hz generat
18、ors. 3.2.5 Load Increments. The Load Bank shall provide the capability to adjust loads in step increments. 3.2.5.1 Three Phase Load Increments. The Load Bank while in three phase operation shall, at a minimum, provide adjustable loads in 5 kW steps. 3.2.5.2 Single Phase Load Increments. The Load Ban
19、k while in single phase operation shall, at a minimum, provide adjustable loads in 1 kW steps. 3.2.6 Control Power. The Load Bank shall operate from a generator under test with the exception that it may operate with an external 60 Hz source when testing a 400 Hz generator. 3.2.7 Operators Controls.
20、The Load Bank shall have a control panel with switches and devices capable of selection by the operator. 3.2.7.1 Control Panel. The Load Bank control panel shall provide a Master load on/off switch, a load step on/off switch consisting of a minimum of four load increments, power indicators, and test
21、 points to measure the voltage across the load. 3.2.7.2 Panel Orientation. The Load Bank panel shall be capable of being positioned in a face up orientation, as well as face front. The Load Bank shall be stable in both positions in accordance with MIL-PRF-28800. 3.2.8 Measurements. The Load Bank sha
22、ll be capable of measuring voltage, current, and frequency per phase to at least 3% accuracy. Accuracy verification shall be performed every twelve months. If calibration is a feature of the instrumentation, it shall be done at that time. Provided by IHSNot for ResaleNo reproduction or networking pe
23、rmitted without license from IHS-,-,-MIL-PRF-32389 4 3.3 External Interface Requirements. The Load Bank shall provide external AC power connections. 3.3.1 Connectors. The modified Load Bank shall support 175 Amp Powerpole type connectors. 3.3.2 Cables. The Load Bank shall include single and 3-phase
24、cable assemblies 8 to 10 feet in length with the generator end terminating in bare metal in a manner to provide size compatibility with all serviced generator lugs from 2 kW to 60 kW. 3.3.3 Cable Conductors. The Load Bank shall provide flexible conductors of an appropriate size (AWG) with insulation
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF323892013LOADBANKELECTRICALPDF