ARMY MIL-F-51539 A-1990 FILTER UNIT GAS-PARTICULATE 400 CFM 208 V 400 HZ M59《毒气颗粒物过滤器机组 400 CFM 208 V 400 HZ M59》.pdf
《ARMY MIL-F-51539 A-1990 FILTER UNIT GAS-PARTICULATE 400 CFM 208 V 400 HZ M59《毒气颗粒物过滤器机组 400 CFM 208 V 400 HZ M59》.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-F-51539 A-1990 FILTER UNIT GAS-PARTICULATE 400 CFM 208 V 400 HZ M59《毒气颗粒物过滤器机组 400 CFM 208 V 400 HZ M59》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-F-5 P539A(EA) 28 SeDtember 1990 SUPERSEDING 29 March 1988 MIL-F-S1539(EA) MILITARY SPECIFICATION FILTER UNIT, GAS-PARTICULATE: 400 CFM, 208 V, 400 Hz, M59 This specification is approved for use by the US. Army Chemical Research, Development and Engineering Center, Department of the Army, and is
2、available for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers one type of gas particulate filter unit capable of delivering filtered air at a rate of 400 cubic feet per minute (cfm). (See 6.1.) 2. APPLICABLE DOCUMENTS 2.1 Government doc
3、uments. 2.1.1 Specifications, standards, and handbooks. The following specifications, stan- dards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the De- partment of Defense Index o
4、f Specifications and Standards (DODISS) and supplement thereto, cited in the solicitation (see 6.2). Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: Commander, U.S. Army Chemical Research, Devel
5、opment and Engineering Center, AITN: SMCCR-PET-S, Aberdeen Proving Ground, MD 2 10 10-5423 by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter, AMSC NIA FSC 4240 DISTRIBUTION STATEMENT A. Approved for public rele
6、ase; distribution is unlimited. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-F-5 15 39A SPECIFICATIONS MILITARY . MIL-F-5 1527 - Filter Set, Gas and Particulate, 200 CFM (Modular Collective Protection Equipment (MCPE)/Simplified Collective Pro
7、tection Equipment (SCPE) Applications) STANDARDS MILITARY- MIL-STD-781 HANDBOOKS MILITARY MIL-HDBK-781 - Reliability Testing for Engineering Development, Qualification, and Production - Reliability Test Methods, Plans, and Environments for Engineering Development, Qual if ica tion, and Production (U
8、nless otherwise indicated, copies of federal and military specifications, standards, and handbooks are available from the Standardization Documents Order Desk, Building 4D, 700 Robbins Avenue, Philadelphia, PA 19111-5094.) 2.1.2 Other Government documents, drawings, and publications. The following o
9、ther Government documents, drawings, and publications form a part of this document to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicita- tion. U.S. ARMY CHEMICAL RESEARCH, DEVELOPMENT AND ENGEERING CENTER DRAWINGS 5-19-6699 - Filter Unit, Gas-Particu
10、late, 400 CFM, 208 V, 400 Hz, b59 SPECIAL PACKAGING INSTRUCTIONS (SPI) P5-19-6699 - Filter Unit, Gas-Particulate: 400 CFM, 208 V, 400 Hz, M59 i (Copies are available from Commander, U.S. Army Information Systems Command, ATTN: ASQNC-AM-CT, Rock Island, IL 61229-7300.) 2 Provided by IHSNot for Resale
11、No reproduction or networking permitted without license from IHS-,-,-MIL-F-5 1 5 39A 2.2 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document takes precedence. Nothing in this document, however, supersedes applic
12、able laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 Materials and components. 3.1.1 Materials. AI1 materials cited on Drawing 5-19-6699 and subsidiary drawings shall conform to the specifications listed thereon and to the specific characteristics set forth on
13、 the drawings. 3.1.2 Components. All components of the filter unit shall conform to the specifications and drawings listed on Drawing 5-19-6699 and subsidiary drawings. 3.2 Manufacture and assembly. The filter unit shall be manufactured and assembled in accordance with Drawing 5-19-6699. 3.3 Perform
14、ance. 3.3.1 Cycling burn-in. The filter unit shall be cycled for a period of 3 hours during which time the airflow valve shall drive alternately to the fully open and then to the fully closed position (see 6.3) at a rate of 3 times per minute in resp.onse to an air pressure differential of 25 inches
15、 water gage (iwg) when tested in accordance with 4.4.6.2. 3.32 Operational characteristics. Prior to and after completion of the cycling burn-in, the filter unit shall meet the following operational characteristics: 3.3.2.1 Airflow valve closing. The airflow valve shall start to drive closed between
16、 1.2 and 1.7 iwg when tested in accordance with 4.4.6.3(b). and 1.7 iwg when tested in accordance with 4.4.6.3(c). 3.3.2.2 Airflow valve opening. The airflow valve shall start to drive open between 1.2 3.3.2.3 Warning horn and MASK indicator. The warning horn shall sound and the MASK indicator shall
17、 flash between 0.85 and 1.10 iwg when tested in accordance with 4.4.6.3(c) and 4.4.6.3(d). shall be a minimum of 11,000 rpm when tested in accordance with 4.4.6.3(e). article inspection in accordance with 4.3. 3.3.2.4 Fan assembly rotational speed. The fan assembly impeller rotational speed 3.4 Firs
18、t article. When specified (see 6.2), a sample shall be subjected to the first 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-F-52537A 42 M 7777706 04bb737 MIL-F-51539A 3.5 Reliability. Concurrent with the start of regular production, a product
19、ion sample of four filter units shall be tested in accordance with Task 302 of MIL-STD-781 and test plan IV-D of MIL-HDBK-781. The lower test mean-time-between-failure (01) shall be 467 hours and the upper test mean-time-between-failure (00) shall be 935 hours. The produc- tion sample shall be teste
20、d continuously in the configuration specified in 4.4.6.1 and 4.4.6.2 without temperature, vibration or input voltage cycling. An accountable failure shall be defined as any deviation from the requirements specified in 3.3.2. 3.6 Workmanship. The filter units shall be free from cracked, bent or dente
21、d metal sections and foreign matter (dirt, oil or viscous materials). 4. QUALITY ASSURANCE PROVISIONS 4.1 Responsibility for inspection. Unless otherwise specified in the contract or pur- chase order, the contractor is responsible for the performance of all inspection require- ments (examinations an
22、d tests) as specified herein. Except as otherwise specified in the contract or purchase order, the contractor may use his own or any other facilities suitable for the performance of the inspection requirements specified herein, unless disapproved by the Government. The Government reserves the right
23、to perform any of the inspections set forth in this specification where such inspections are deemed necessary to ensure supplies and services conform to prescribed requirements. 4.1.1 Responsibility for compliance, All items shall meet all requirements of sections 3 and 5. The inspection set forth i
24、n this specification shall become a part of the contractors overall inspection system or quality program. The absence of any inspection requirements in the specification shall not relieve the contractor of the responsibility of ensuring that all products or supplies submitted to the Government for a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILF51539A1990FILTERUNITGASPARTICULATE400CFM208V400HZM59 毒气 颗粒 过滤器 机组 400 CFM208V400HZM59PDF

链接地址:http://www.mydoc123.com/p-444777.html