1、A-A-52b00 = 9999974 0370770 Tb4 G METRIC A-A-52600 blmhLw% SUPERSEDING MIL-T-462E 16 September 1985 Beneficial comments, recommendations, additions, deletions clarifications, etc. and any other data which may improve this document should be sent by letter to: U.S. Army Tank-automotive and Armaments
2、Command, ATTN: AMSTA-TR-E/BLUE, Warren, MI 48397-5000. - COMMEXCIAL ITEM DESCRIPTION TANK, LIQUID STORAGE, METAL: EUEL-OIL, HORIZONTAL The General Services Administration has authorized the use of this Commercial Item Description (CID) for all federal agencies. 1. SCOPE. This CID covers a 1041 liter
3、 (L) (275 gallon (gal) nominal capacity, horizontal, non-pressure type, above ground fuel oil storage tank. The tank is intended for unenclosed installation inside of buildings, primarily for the storage and supply of fuel oil for oil burners. Outdoor installation is not precluded. 2. SALIENT CHARAC
4、TERISTICS 2.1 Materials. Unless otherwise specified herein, materials shall be in accordance with the applicable requirements of Underwriters Laboratories, Inc., UL 80. The use of recovered material made in compliance with regulatory requirements is acceptable providing that ail requirements of this
5、 CID are met (see 3.1). 2.1.1 -ade steel . The tank shall be constructed of commercial grade steel having a less than 1.70 millimeter (mm) (0.067 inches (in) and for galvanized steel, 1.78 mm (0.070 in). - carbon content of 0.25 percent or less. The minimum thickness of uncoated steel shall be not r
6、 Licensed by Information Handling ServicesA-A-52b00 m 9999974 OL7077L 9TO m A-A-52600 2.2 -and constructiqn. 2.2.1 m. The tank shall be fabricated in accordance with the requirements of Underwriters Laboratories Inc., UL 80. The tank shall have the form as shown in Figure 1. 12 in (300 mm) ft9 in 40
7、 rnm) L II I 275 GALLONS ( 1041 L ) 0.50 in b (13 mm 0) (75 mm) -5 ft O in(1520 mm)- NOTES: 12 in (300 rnm) 1. All openings internaiiy threaded NPT. 2. Tolerance on dimensions locating openings is f13 mm (0.50 in). 9 FIGUREl. Tank. 2 Licensed by Information Handling ServicesA-A-52600 9999974 0370772
8、 837 A-A-52600 2.2.2 Shell seams. Welding shall be of the continuous or lap type. AU lap welds shall have a continuous full et the length of the seam. 2.2.3 Mounting brackets. Two 100 by 100 by 6.4 mm (4 by 4 by 0.25 in) steel angle brackets 100 mm (4 in) long shall be welded, with a continuous fidl
9、 fiilet weld, on each side of the tank. The brackets shall be located 15 mm (6 in) from the ends of the tank. Each bracket shall be drilled and tapped for a 32 mm (1.25 in) pipe leg. 2.2.4 Fill. vent and gauge openinas. Not less than three threaded openings shall be provided in the top of the tank f
10、or connection of fiil and venting piping, and for installation of a liquid level gauge. Au openings on the top of the tank shaii be equal in size and not less than a nominal 50 mm (2 in) pipe size. 2.2.5 Top piPe connections. Stamped or forged steel pipe connections shall be furnished by welding thr
11、eaded flanges to the tank openings. The connections shall be in accordance with the requirements of Underwriters Laboratories Inc., (VL) 80. 2.2.6 Burner supplv connection. A threaded opening not less than 13 mm (0.50 in) pipe size shall be provided in the bottom of the tank shell for connection of
12、piping supplying fuel to the oil burner. The center of this opening shall be located not more than 75 mm (3 in) from the end of the shell, and the opening shad be without internai projections to permit complete drainage. A burner supply connection shaU not be located in a head. 2.2.7 Treatment and p
13、ainting;. The parts of the tank normally painted shall be cleaned, treated and painted in accordance with the contractors commercial practice. Unless otherwise specified in the contract, the fnish coat shall be camouflage green. 2.2.8 Identification marking number. Each tank shall be marked with the
14、 manufacturers or private labelers name or identwg symbol. This marking shall be embossed, etched or stamped on a metal nameplate that is permanently attached by welding or brazing. Ea mandacturer produces tanks at more than one factory, each tank shall have a distinctive marking to identify it as t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYAA526001996TANKLIQUIDSTORAGEMETALFUELOILHORIZONTAL 横向 燃油 金属 贮存 PDF

链接地址:http://www.mydoc123.com/p-440182.html