ANSI ARI 400-2001 Liquid to Liquid Heat Exchangers《液体对液体的热交换器》.pdf
《ANSI ARI 400-2001 Liquid to Liquid Heat Exchangers《液体对液体的热交换器》.pdf》由会员分享,可在线阅读,更多相关《ANSI ARI 400-2001 Liquid to Liquid Heat Exchangers《液体对液体的热交换器》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、 ARI STANDARD 400-2001 WITH ADDENDUM 2, Liquid to Liquid Heat Exchangers April 2005 ARI Standard 400-2001 with Addendum 2, Liquid to Liquid Heat Exchangers, is comprised of only the shaded portions shown. The September 2005 Addendum 2 has been incorporated into the already published 2001 version of
2、ARI Standard 400 to avoid confusion. Particular additions (shown shaded in the standard), deletions (shown with a strikethrough and shaded in the standard), and corrections (shown shaded in the standard) are as follows: 1. In 5.3, the requirement for pressure drop not to exceed more than 110% of the
3、 published pressure drop was removed. 2. In 5.3, a requirement for tested pressure drop not to exceed the published pressure drop by more than 10%, or 1.0 ft of fluid 0.3 m of fluid, whichever is greater, was added. Air-Conditioning and Refrigeration Institute 4100 N. Fairfax Drive, Suite 200 Arling
4、ton, VA 22203 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 400-2001 WITH ADDENDUM 1, Liquid to Liquid Heat Exchangers June 2003 ARI Standard 400-2001 with
5、Addendum 1, Liquid to Liquid Heat Exchangers, is comprised of only the shaded portions shown. The June 2003 Addendum 1 has been incorporated into the already published 2001 version of ARI Standard 400 to avoid confusion. Particular additions (shown shaded in the standard), deletions (shown with a st
6、rikethrough and shaded in the standard), and corrections (shown shaded in the standard) are as follows: 1. In Table 1, units of measurement for minimum and maximum pressure drop were corrected. 3. In Table 1, the SI equivalents for minimum and maximum pressure drop were corrected. 4. In Appendix A,
7、the current edition of ANSI/ASHRAE Standard 41.1 is ANSI/ASHRAE Standard 41.1-1986 (RA 2001). 5. In Appendix A, references to ASME MFC-5M, ASME MFC-6M, ASME MFC-16M, and ASME PTC 19.2 were deleted. 6. C4. Instruments and Test Apparatus (and associated subsections) was deleted. 7. C4. Test Measuring
8、Instruments (and associated subsections) was added. Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-4301 NORTH FAIRFAX DRIVE ARLINGTON, VIRGINIA 22203 2001 STANDARD for LI
9、QUID TO LIQUID HEAT EXCHANGERS Standard 400 with Addendum 2 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Price $10.00 (M) $20.00 (NM) Copyright 2001, by Air-Conditionin
10、g and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in acc
11、ordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best ef
12、forts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supercedes ARI Standard 400 with Addendum 1. Copyri
13、ght Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope .1 Section 3. Definitions .1 Section 4. Test Requirements.2
14、Section 5. Rating Requirements .2 Section 6. Minimum Data Requirements for Published Ratings2 Section 7. Marking and Nameplate Data3 Section 8. Conformance Conditions.3 TABLES Table 1. Limits of Mapped Rating Conditions2 APPENDICES Appendix A. References - Normative.4 Appendix B. References - Inform
15、ative .4 Appendix C. Method of Test of Liquid to Liquid Heat Exchangers - Normative5 Appendix D. Method of Simulating Field Fouling Allowance Informative9 FIGURES FOR APPENDICES Figure D1. Counter Flow.9 Figure D2. Parallel Flow9 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS
16、 under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-_ARI STANDARD 40
17、0-2001 WITH ADDENDUM 2 1 LIQUID TO LIQUID HEAT EXCHANGERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Liquid to Liquid Heat Exchangers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate dat
18、a; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Sc
19、ope. This standard applies to Liquid to Liquid Heat Exchangers as defined in Section 3, which includes the following types of heat exchangers: a. Plate Heat Exchangers b. Shell-and-Tube Heat Exchangers, Shell-and-U-Tube Heat Exchangers, and Shell-and-Coil Heat Exchangers c. Counter flow Shell-and-Tu
20、be Heat Exchangers 2.2 Exclusions. This standard does not apply to heat exchangers used for change of phase or non-liquid heat transfer applications. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the current edition of ASHRAE Terminology of Heati
21、ng, Ventilation, Air Conditioning and Refrigeration, unless otherwise defined in this section. 3.1 Clean Capacity. The total heat transfer rate of the heat exchanger with clean heat exchanger surfaces. 3.2 Cold Stream. The liquid stream with the lower inlet temperature. 3.3 Counter Flow Shell-and-Tu
22、be Heat Exchanger. A baffled shell and tube heat exchanger, circuited such that the shellside and tubeside liquids flow countercurrent to one another. 3.4 Field Fouling Allowance. Provision for anticipated fouling during use. 3.4.1 Fouling Factor. The thermal resistance due to fouling accumulated on
23、 the heat transfer surface. 3.5 Hot Stream. The liquid stream with the higher inlet temperature. 3.6 Liquid to Liquid Heat Exchanger. A heat transfer device used to exchange heat between two liquid streams that are single phase fluids. 3.7 Number of Transfer Units (NTU). A dimensionless coefficient
24、representing the magnitude of thermal demand. The equation for NTU is given in Appendix C. 3.8 Plate Heat Exchanger. Heat transfer device that typically utilizes corrugated metal plates in a bolted frame. An alternate technique is for the plates to have elastomer gaskets that seal the unit and direc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIARI4002001LIQUIDTOLIQUIDHEATEXCHANGERS 液体 热交换器 PDF

链接地址:http://www.mydoc123.com/p-431080.html