ANSI ARI 365-2002 Commercial and Industrial Unitary Air-Conditioning Condensing Units《商业与工业用单体空气调节冷凝装置》.pdf
《ANSI ARI 365-2002 Commercial and Industrial Unitary Air-Conditioning Condensing Units《商业与工业用单体空气调节冷凝装置》.pdf》由会员分享,可在线阅读,更多相关《ANSI ARI 365-2002 Commercial and Industrial Unitary Air-Conditioning Condensing Units《商业与工业用单体空气调节冷凝装置》.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、2002 STANDARD for Al R-CON DITION I NG classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, i
2、ncluding manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Commercial and Industrial Unitary Air-conditioning Condensing U
3、nits greater than or equal to 135,000 Btuh 39.6 kW as defined in Section 3. 2.1.1 Energy Source. This standard applies only to electrically-driven, mechanical compression-type condensing units. 2.2 Exclusions. This standard does not apply to the testing and rating of condensing units for refrigerati
4、on purposes, as defined in ARi Standard 520. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the current edition of ASHFAE Terminology of Heating, Ventilation, A il*-Conditioning and Refiigeration unless otherwise defined in this section. 3.1 Comme
5、rcial and Industrial Unitaiy Air-conditioning Condensing Unit. A factory-made assembly of refrigerating components designed to compress and liquefy a specific refrigerant. It consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporative - cooled, andlor water-coole
6、d), condenser fans and motors (where used) and factory-supplied accessories. 3.2 Cooling Capacity. Cooling capacity is the capacity in Btuh W obtained at specific conditions. It is equal to the increase in total enthalpy between the liquid refrigerant entering the expansion valve and superheated ret
7、urn gas multiplied by the mass flow rate of the refrigerant. 3.3 at a specified pressure. Dew Point. Refrigerant vapor saturation temperature 3.4 Energy Efficiency Ratio (EER). A ratio of the Cooling Capacity in Btu/h to the power input values in watts at any given set of Rating Conditions expressed
8、 in Btu/(W.h). 3.5 Integrated Part-Load Value (IPLV). A single number part-load efficiency figure of merit calculated per the method described in this standard and expressed in Btu/( W.h). 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rat
9、ing Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of all performance characteristics shown on the unit o
10、r published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Conditions. 3.6.1 Application Rating. A rating based on tests performed at Application Rating conditions (other than Standard Rating Conditions). 3.6.2 Standard Rating. A rating based on
11、tests performed at Standard Rating Conditions. 3.7 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.1.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for pe
12、rformance characteristics. 3.8 “Shall“ or “Should. I “Shall“ or “should“ shall be interpreted as follows: 3.8.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.8.2 Should. “Should“ is used to indicate pr
13、ovisions which are not mandatory but which are desirable as good practice. 1 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-AR1 STANDARD 365-2002 Designation 3.9 Single Nu
14、mber Rating. The Cooling Capacity and EER determined by averaging the results of the tests at Rating Conditions No. 1 and No. 2 for air-cooled and evaporative-cooled condensing units and at Rating Conditions No. 5 and No. 6 for water-cooled condensing units (Section 6). AN Condenser Arrangement Type
15、 Type i Section 4. Classifications Equipment covered within the scope of this standard shall be classified as shown in Table 1 : Table 1. Classifications of Commercial and Industrial Air-Conditioning Condensing Units Remote Condensing Unit (RCU) wl COMP CON D RCU-E Eva orative I RCU-w I water I I Se
16、ction 5. Test Requirements 5.1 Test Requirements. ,411 Standard Ratings shall be verified by tests conducted in accordance with ANSUASHM Standard 23 and with the test methods and procedures as described in this standard. 5.1.1 An alternate method of verification may be used by tests conducted in acc
17、ordance with ANSUASHM Standard 37 provided that the suction Dew Point temperature and the return gas temperature are determined from the procedures in this standard. Section 6. Rating Requirements 6.1 Standard Ratings. Published Ratings shall be obtained at one or more of the Standard Rating Conditi
18、ons as shown in Table 2. Power input shall be the total power input to the compressor(s), fan(s), controls, and any other components included as part of the condensing unit. 6.1.1 Values of Standard Cooling CapaciS, Ratings. These ratings shall be expressed only in terms of thousands of Btu/h W in m
19、ultiples of2,000 Btu/h 600 W for units with Standard Ratings of 400,000 Btu/h 117,000 W and under. For units with Standard Ratings of over 400,000 Btu/h i 17,000 W, the ratings shall be expressed in multiples of 5,000 Btu/h 1,500 W. .6.1.2 Values of Standard Efficiency Ratings. EER, in Btu/(W.h), an
20、d IPLV shall be expressed in multiples of O. 1. 6.1.3 Single Number. Ratings. The reported values shall be determined by averaging the results obtained at Rating Conditions No. 1 and No. 2 or at Rating Conditions No. 5 and No. 6. 6.1.4 Electrical Conditions. Standard Rating tests shall be performed
21、at the nameplate rated voltage(s) and frequency. For condensing units with dual nameplate voltage ratings, Standard Rating tests shall be performed at both voltages, or at the lower of the two voltages, if only a single Standard Rating is to be published. 6.1.5 Condenser Air Quantity. All Standard R
22、atings for condensing units shall be determined at the condenser air quantity specified by the manufacturer where the fan drive is adjustable. Where the fan drive is direct-connected, Standard Ratings shall be determined at the condenser air quantity established when the condensing unit is operated
23、with all of the associated inlet louvers and any duct work and attachments considered by the manufacturer as normal installation practice. Once established, the condenser air circulation of the condensing unit shall remain unchanged throughout all tests prescribed herein, except as altered by automa
24、tic controls. 6.2 Part-Load Rating. Condensing units which are capable of capacity reduction shall be rated at 100% and at each step of capacity reduction provided by the condensing unit as published by the manufacturer. These rating points shall be used to calculate the IPLV (6.2.2). 6.2.1 Part-Loa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIARI3652002COMMERCIALANDINDUSTRIALUNITARYAIRCONDITIONINGCONDENSINGUNITS 商业 工业 单体 空气调节 冷凝 装置 PDF

链接地址:http://www.mydoc123.com/p-431078.html