1、2008 Standard forRequirements for theQualification of ReverberationRooms in the 63 Hz Octave BandARI Standard 280Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-P
2、rice $10.00 (M) $20.00 (NM) Copyright 2008, by Air-Conditioning, Heating, and Refrigeration InstitutePrinted in U.S.A. Registered United States Patent and Trademark OfficeIMPORTANTSAFETY DISCLAIMERAHRI does not set safety standards and does not certify or guarantee the safety of any products, compon
3、ents orsystems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is stronglyrecommended that products be designed, constructed, assembled, installed and operated in accordance withnationally recognized safety standards and code requirements appropriate for
4、 products covered by thisstandard/guideline.AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industrypractices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk.Note:Th
5、is standard differs from the 1995 version in that it requires the use of a Reference Sound Source meeting therequirements of and calibrated per ARI Standard 250.Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or net
6、working permitted without license from IHS-,-,-TABLE OF CONTENTSPAGESection 1. Purpose1Section 2. Scope.1Section 3. Definitions.1Section 4. Reverberation Room Qualification and Testing Procedures.2Section 5. Conformance Conditions 3TABLESTable 1. Broadband Standard Deviation Limits2Table 2. Pure Ton
7、e Standard Deviation 2APPENDICESAppendix A. References Normative .4Appendix B. References Informative4Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD
8、 280-20081REQUIREMENTS FOR THE QUALIFICATION OFREVERBERATION ROOMS IN THE 63 HZ OCTAVE BANDSection 1. Purpose1.1 Purpose. The purpose of this standard is to establish a method of qualifying reverberation rooms in the 63 Hz Octave Band(50, 63 and 80 Hz One-Third Octave Bands).1.1.1 Intent. This stand
9、ard is intended for the guidance of the industry, including manufacturers, engineers, installers,contractors and users.1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances.Section 2. Scope2.1 Scope. This standard applies to products rated in the 63 Hz O
10、ctave Band (50, 63 and 80 Hz One-Third Octave Bands)where the sound power is determined from measurements made in a reverberation room by using the comparison method asspecified per ANSI Standard S12.51/ISO: 3741.Section 3. DefinitionsDefinitions. All terms in this document will follow the standard
11、industry definitions in the current edition of ASHRAETerminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section.3.1 Broadband Sound. Sound that is random in nature with frequency components distributed over a broad frequency band.Typically pure t
12、ones or periodic disturbances will not be distinguishable in this type of sound spectrum.3.2 Comparison Method. A method used to determine Sound Power Level by comparing the Sound Pressure Level of thesource under test to the average Sound Pressure Level produced in the room by a Reference Sound Sou
13、rce of known sound powerlevel output. The difference in Sound Power Level is equal to the difference in Sound Pressure Level when conditions in the roomare the same for both sets of measurements.3.3 Discrete Frequency Component. A component of the sound field having an instantaneous sound pressure t
14、hat variesessentially as a simple sinusoidal function of time.3.4 Hertz (Hz). A unit of frequency equal to one cycle per second3.5 Low Frequency Data. Low frequency data for purposes of this standard is the 63 Hz Octave Band (50, 63 and 80 HZ One-Third Octave Bands).3.6 Octave Band. A band of sound
15、covering a range of frequencies such that the highest is twice the lowest. The Octave Bandsused in this standard are those defined in ANSI Standard S1.11.3.7 One-Third Octave Band. A band of sound covering a range of frequencies such that the highest frequency is the cube rootof two times the lowest
16、 frequency. The One-Third Octave Bands used in this standard are those defined in ANSI Standard S1.11.3.8 Reference Sound Source (RSS). A portable, aerodynamic sound source that produces a known stable Broadband Sound.3.9 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows:Copyr
17、ight Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 280-200823.9.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is ma
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI2802008REQUIREMENTSFORTHEQUALIFICATIONOFREVERBERATIONROOMSINTHE63HZOCTAVEBANDPDF

链接地址:http://www.mydoc123.com/p-429430.html