ARI 260-2001 Sound Rating of Ducted Air Moving and Conditioning Equipment Addendum August 2002《输送空气移动和条件设备附录声音等级级别附录 2002年8月》.pdf
《ARI 260-2001 Sound Rating of Ducted Air Moving and Conditioning Equipment Addendum August 2002《输送空气移动和条件设备附录声音等级级别附录 2002年8月》.pdf》由会员分享,可在线阅读,更多相关《ARI 260-2001 Sound Rating of Ducted Air Moving and Conditioning Equipment Addendum August 2002《输送空气移动和条件设备附录声音等级级别附录 2002年8月》.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、ADDENDUM TO ARI STANDARD 260-2001 (ISSUED AUGUST 2002) A. Replace Equation 5 of Section 5.3.1 of ARI Standard 260-2001 with the following: Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without licens
2、e from IHS-,-,-2001 STANDARD for AIR-CONDITIONING requirements for acquiring mapped sound data; Sound Power Level calculations and ratings; minimum data requirements for published sound ratings; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, inc
3、luding manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to all ducted air moving and conditioning equipment containing fans as defined in
4、 Section 3 of this standard. Examples of such equipment when ducted are: a. b. C. d. e. Unitary Air-Conditioners, as defiied in ARI Standard 2101240 and ARI Standard 3401360 ARI-Source Unitary Heat Pumps, as defined in ARI Standard 3401360 Water-Source Heat Pumps, as defiied in IS0 Fan-Coil Air-Cond
5、itioners, as defiied in ARI Standard 440 Central-Station Air-Handling Units, as defiied in ARI Standard 430 13256-1 2.2 Exclusions. This standard does not apply to: a. b. C. d. e. Air Control and Distribution Devices, which are covered by ARI Standard 880 Packaged Terminal Air-Conditioners , which a
6、re covered by ANSIIARI Standard 300 Outdoor sound fiom outdoor portions of Ducted Equipment that would be covered under ARI Standards 270 and 370 The sound radiated fiom ductwork attached to the fan andor equipment when such ductwork is not offered by the manufacturer as a standard part of the equip
7、ment The casing (base pan) radiated sound component for rooftop or down draft products Section 3. Definitions Ail terms in this document shall follow the standard industry defiiitions established in the current edition of ASHRAE Terminology of Heating, Ventilation, Air-Conditioning and Refrigeration
8、, unless otherwise defiied in this section. 3.1 Acoustic Test Duct. The duct used to convey the sound of the unit configuration under test to the reverberation room during a ducted discharge or the ducted inlet sound component test. A Duct End Correction (E) must be added to the sound data measured
9、in the reverberation room to account for the presence of an open-ended duct terminating in the reverberation room. 3.2 Acoustic Test Duct Elbow. An elbow added to the Acoustic Test Duct during a reverberation room test to facilitate testing. An adjustment must be made (in addition to the Duct End Co
10、rrection) to the sound data to account for the presence of the Acoustic Test Duct Elbow. Appendix D of this standard defines the Atkins sound attenuation adjustments. 3.3 Base Unit. A factory-made encased assembly consisting of one or more fans meant to be connected to a duct and other necessary equ
11、ipment to perform one or more of the functions of circulating, cleaning, heating, cooling, humidifying, and mixing of air, but which does not always include a source of heating or cooling. 3.3.1 for purposes of control, isolation, safety, static pressure regain, wear etc. Appurtenance. An addition t
12、o a Base Unit Examples of Appurtenances include: a. b. d. e. f. g- h. C. 1. Coil) 1. Cooling coil 2. Cooling and dehumidifying coil 3. Water spray (wetted coil) 4. Heating coil Electric heater( s) Air filter Dampers Moisture eliminator Fan-motor drive Gas heat exchangers Inlet or discharge plenums M
13、odulating devices in the fan inietldischarge 1 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-AR1 STANDARD 260-2001 j. Application duct geometries (such as duct elbow conf
14、igurations) 3.4 Comparison Method. A method of determining Sound Power Level of a source under test in a reverberation roomby comparing the average Sound Pressure Level ofthat source to the average Sound Pressure Level of a Reference Sound Source of known Sound Power Level output. The difference in
15、Sound Power Level is equal to the difference in Sound Pressure Level when conditions in the room are the same for both sets of measurements. 3.5 Duct End Correction, E. Accounts for the acoustic energy in an Acoustic Test Duct that is reflected back towards the source. A method for computing E is de
16、fiied in 5.2.1 of this standard. 3.6 Ducted Equipment. Heating, ventilating and air- conditioning equipment having one or more supply fans. The equipment may be configured with either: a. Free inlet(s) with ducted discharge(s) b. Ducted inlet(s) with free discharge(s) c. Ducted iniet(s) and ducted d
17、ischarge(s) This equipment may be ducted in various configurations horizontally and vertically, and may incorporate multiple inlets and outlets. 3.7 Effective Diameter, D. Diameter of an Acoustic Test Duct and is equal to either the diameter, ft m, of a circular duct or the Effective Diameter, ft m,
18、 of a rectangular duct. D is given by the following expression: where: AREA = Cross-sectional area of the duct, ft2 m2 3.8 second. Hertz (Hz). A unit of frequency equal to one cycle per 3.9 (50,63 and 80 Hz One-Third Octave Bands). Low Frequency Data. Data in the 63 Hz Octave Band 3.10 Mapped Sound
19、Rating. A rating based upon tests performed across the range of operating conditions typically defined for the product supply fan map, in the Base Unit, and as defiied by the product manufacturer. These products include: a. Belt-driven products with or without variable frequency drives b. Direct-dri
20、ve products with variable frequency drives c. Direct-drive products with discrete speed taps Note: Special case -when a supply fan is used in conjunction with a return fan in the Base Unit (See Appendix E of this standard). 3.11 Octave Band. A band of sound covering a range of frequencies such that
21、the highest is twice the lowest. The Octave Bands used in this standard are those defined in ANSI Standard S 1.1 1. 3.12 One-Third Octave Band. A band of sound covering a range of frequencies such that the highest frequency is the cube root of two times the lowest. The One-Third Octave Bands used in
22、 this standard are those defiied in ANSI Standard S 1.1 1. 3.13 Reference Sound Source (RSS). A portable, aerodynamic sound source that produces a known stable broad band sound power output. 3.14 Reverberation Room Technique. A technique used to derive the Sound Power Level of Ducted Equipment Sound
23、 Components. The technique utilizes an Acoustic Test Duct coupled to a reverberation room to measure the ducted inlet or ducted discharge sound. Other setup configurations allow the testing of the casing radiated or free inlet (or free discharge) combined with the casing radiated Sound Components. T
24、his technique is incorporated in AMCA Standard 300. 3.15 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as follows: 3.15.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.15.2 Should. “Sho
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI2602001SOUNDRATINGOFDUCTEDAIRMOVINGANDCONDITIONINGEQUIPMENTADDENDUMAUGUST2002 输送 空气 移动 条件 设备 附录 声音

链接地址:http://www.mydoc123.com/p-429427.html