ARI 210 240-2008 Performance Rating of Unitary Air-Conditioning& Air-Source Heat Pump Equipment.pdf
《ARI 210 240-2008 Performance Rating of Unitary Air-Conditioning& Air-Source Heat Pump Equipment.pdf》由会员分享,可在线阅读,更多相关《ARI 210 240-2008 Performance Rating of Unitary Air-Conditioning& Air-Source Heat Pump Equipment.pdf(131页珍藏版)》请在麦多课文档分享上搜索。
1、 2008 Standard for Performance Rating of Unitary Air-Conditioning classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the
2、guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Unitary Air-Conditioners and Air-Sou
3、rce Unitary Heat Pumps as defined in Section 3. 2.1.1 Energy Source. This standard applies only to electrically operated, vapor compression refrigeration systems. 2.2 Exclusions. 2.2.1 This standard does not apply to the rating and testing of individual assemblies, such as condensing units or coils,
4、 for separate use. 2.2.2 This standard does not apply to heat operated air-conditioning/heat pump equipment, or to packaged terminal air-conditioners/heat pumps, or to room air-conditioners/heat pumps. 2.2.3 This standard does not apply to Unitary Air-Conditioners as defined in ARI Standard 340/360
5、with capacities of 65,000 Btu/h 19,000 W or greater. 2.2.4 This standard does not apply to Air-Source Unitary Heat Pumps as defined in ARI Standard 340/360 with cooling capacities of 65,000 Btu/h 19,000 W or greater, or to water-source heat pumps, to ground water-source heat pumps, and to ground sou
6、rce closed-loop heat pumps. 2.2.5 This standard does not include water heating heat pumps. 2.2.6 This standard does not apply to rating units equipped with desuperheater/water heating devices in operation. Section 3. Definitions All terms in this document shall follow the standard industry definitio
7、ns in the current edition of ASHRAE Terminology of Heating, Ventilation, Air- Conditioning and Refrigeration, unless otherwise defined in this section. Note: Definitions for Small-duct, High-velocity Systems, Space Constrained Products, and Through-the-wall Air Conditioners and Heat Pumps are taken
8、from Title 10, Code of Federal Regulations, Part 430, Subparts 430.2 and 430.32 (c). See Appendix C for definitions that apply to the testing and calculation procedures required by Appendix C. Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not
9、for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 210/240-2008_ 2 3.1 Air-Source Unitary Heat Pump. One or more factory-made assemblies which normally include an indoor conditioning coil(s), compressor(s), and outdoor coil(s), including means to provide a he
10、ating function. When such equipment is provided in more than one assembly, the separated assemblies shall be designed to be used together, and the requirements of rating outlined in the standard are based upon the use of matched assemblies. 3.1.1 Functions. They shall provide the function of air hea
11、ting with controlled temperature, and may include the functions of air-cooling, air-circulating, air-cleaning, dehumidifying or humidifying. 3.2 Degradation Coefficient (CD). The measure of the efficiency loss due to the cycling of the units as determined in Appendices C and D. 3.3 Design Heating Re
12、quirement (DHR). This is the amount of heating required to maintain a given indoor temperature at a particular outdoor design temperature. 3.4 Energy Efficiency Ratio (EER). A ratio of the cooling capacity in Btu/h to the power input value in watts at any given set of Rating Conditions expressed in
13、Btu/(Wh). 3.4.1 Standard Energy Efficiency Ratio. A ratio of the capacity to power input value obtained at Standard Rating Conditions. 3.5 Heating Seasonal Performance Factor (HSPF). The total space heating required during the space heating season, expressed in Btus, divided by the total electrical
14、energy consumed by the heat pump system during the same season, expressed in watt-hours. 3.6 Integrated Part-Load Value (IPLV). A single number part-load efficiency figure of merit calculated per the method described in this standard. 3.7 Published Rating. A statement of the assigned values of those
15、 performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal capacity and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of a
16、ll performance characteristics shown on the unit or published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Conditions. 3.7.1 Application Rating. A rating based on tests performed at Application Rating Conditions (other than Standard Rating Cond
17、itions). 3.7.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.8 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.8.1 Standard Rating Conditions. Rating
18、 Conditions used as the basis of comparison for performance characteristics. 3.9 Seasonal Energy Efficiency Ratio (SEER). The total heat removed from the conditioned space during the annual cooling season, expressed in Btus, divided by the total electrical energy consumed by the air conditioner or h
19、eat pump during the same season, expressed in watt-hours. 3.10 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as follows: 3.10.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.10.2 Should
20、. “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-_ARI S
21、TANDARD 210/240-2008 3 3.11 Small-duct, High-velocity System. A heating and/or cooling product that contains a blower and indoor coil combination that is designed for, and produces, at least 1.2 in H2O 300 Pa of external static pressure when operated at the certified air volume rate of 220-350 cfm 0
22、.104 0.165 m3/s per rated ton 12,000 Btu/h of cooling. When applied in the field, small-duct products use high-velocity room outlets (i.e., generally greater than 1,000 fpm 5 m/s) having less than 6.0 in2 3,900 mm2 of free area. 3.12 Space Constrained Product. A central air conditioner or heat pump:
23、 a. that has rated cooling capacities no greater than 30,000 Btu/h 8,800 W; b. that has an outdoor or indoor unit having at least two overall exterior dimensions or an overall displacement that: 1. is substantially smaller than those of other units that are: a. currently usually installed in site bu
24、ilt single family homes; and b. of a similar cooling, and, if a heat pump, heating capacity; and 2. if increased, would certainly result in a considerable increase in the usual cost of installation or would certainly result in a significant loss in the utility of the product to the consumer; and c.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI2102402008PERFORMANCERATINGOFUNITARYAIRCONDITIONINGAIRSOURCEHEATPUMPEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-429425.html