AHRI 710 I-P-2009 Performance Rating of Liquid-Line Driers.pdf
《AHRI 710 I-P-2009 Performance Rating of Liquid-Line Driers.pdf》由会员分享,可在线阅读,更多相关《AHRI 710 I-P-2009 Performance Rating of Liquid-Line Driers.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、 AHRI Standard 710 (I-P)2009 Standard for Performance Rating of Liquid-Line Driers Price $12.50 (M) $25.00 (NM) Printed in U.S.A. Copyright 2009, by Air-Conditioning, Heating, and Refrigeration Institute Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not s
2、et safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in a
3、ccordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any
4、tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard 710-2004. For SI ratings, see AHRI Standard 711 (SI)-2009. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose1 Section 2. Scope.1 Section 3. Definitions.2 Section 4. Tes
5、t Requirements 3 Section 5. Rating Requirements.3 Section 6. Minimum Data Requirements for Published Ratings .5 Section 7. Marking and Nameplate Data .5 Section 8. Conformance Conditions 5 TABLES Table 1. Applicable Refrigerant Systems .1 Table 2. Published Ratings3 Table 3. Maximum Range for Duplic
6、ate EPD Determination4 Table 4. Flow Rate per Ton of Refrigeration at 86F Liquid and 5.0F Saturated Vapor5 FIGURES Figure 1. Example of Water Capacity Rating Calculation for Refrigerant 134a at 75F 6 Appendix A. References Normative.7 Appendix B. References Informative.7 Appendix C. Guide for Select
7、ing a Liquid-line Drier Informative 8 AHRI Standard 710 (I-P)-2009 1 PERFORMANCE RATING OF LIQUID-LINE DRIERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Liquid-line Driers: definitions; test requirements; rating requirements; minimum data requirements for Publis
8、hed Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as techno
9、logy advances. Section 2. Scope 2.1 Scope. This standard applies to Liquid-line Driers utilizing solid Desiccants designed for use in the liquid line of all types of refrigeration and air-conditioning systems. 2.2 Applicability. This standard applies to Liquid-line Driers for use in refrigerant syst
10、ems employing the halocarbon refrigerants listed in Table 1, as described in ANSI/ASHRAE Standard 34:Table 1. Applicable Refrigerant Systems Refrigerant Number Chemical Name Chemical Formula R-12 dichlorodifluoromethane CC12F2R-22 monochlorodifluoromethane CHC1F2R-134a 1,1,1,2-tetrafluoroethane CH2F
11、CF3R-245fa 1,1,1,3,3-pentafluoropropane CHF2CH2CF3R-404A Refrigerants 125/143a/134a 44.0/52.0/4.0 % wt. CHF2CF3/ CH3CF3/ CH2FCF3R-407C Refrigerants 32/125/134a 23.0/25.0/52.0 % wt. CH2F2/ CHF2CF3/ CH2FCF3R-410A Refrigerants 32/125 50.0/50.0 % wt. CH2F2/ CHF2CF3R-502 Refrigerants 22/115 48.8/51.2 % w
12、t. CHC1F2/ CC1F2CF3R-507A Refrigerants 125/143a 50.0/50.0 % wt. CHF2CF3/ CH3CF32.3 Exclusions. This standard does not apply to liquid anti-freeze solution Desiccants or driers used in the suction line or low side of refrigeration and air-conditioning systems. 2.4 Limitations. This standard provides
13、a means of determining Water Capacity and Refrigerant Flow Capacity of a Liquid-line Drier at specified conditions. This standard does not attempt to reflect the performance of a Liquid-line Drier over the entire range of possible applications. Therefore, acid and particulate removal are not conside
14、red here. 2.4.1 Acid Removal. It is known that acid in a refrigeration system causes harmful corrosion. Many Liquid-line Driers will remove acids. However, there is no knowledge at the present time as to what concentration of various acids is allowable, nor how to test a liquid-line driers ability t
15、o remove these acids. Therefore, while noting its importance, no consideration of acid removal is given in this standard at this time. AHRI Standard 710 (I-P)-2009 2 2.4.2 Particulate Removal. Although many commercial Liquid-line Driers have filtering media, the subject of filtration is separate and
16、 distinct from the considerations of this standard. Therefore, the rating of a Liquid-line Drier is on the premise of a clean Liquid-line Drier and clean refrigerant. Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminolo
17、gy of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section.3.1 “As Received” Condition. This specifies the Liquid-line Drier as removed from the manufacturers packaging, without further reactivation or preparation. (Note: If information is desired with re
18、spect to the reactivation of a Liquid-line Drier, the user should consult the manufacturer for recommended reactivation procedure.) 3.2 Desiccant. A material that will collect and hold water. 3.3 Equilibrium Point Dryness (EPD). The lowest possible water content of liquid refrigerant attainable by a
19、 specific Liquid-line Drier. This is achieved at a specific temperature after it has collected a specific quantity of water when the two have been in contact until an equilibrium between the water in the refrigerant and the water in the Liquid-line Drier has been reached. EPD is expressed in parts p
20、er million (ppm) by weight. 3.4 Liquid-line Drier. A manufactured device for use in the liquid line of refrigeration and air-conditioning systems. The primary purpose is to collect and hold, at its location, water which is in excess of the amount which can be tolerated in the system. 3.5 Pressure Dr
21、op. The pressure difference between the inlet and the outlet of a Liquid-line Drier, including its connections. 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These v
22、alues apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer
23、, at stated Rating Conditions. 3.6.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions). 3.6.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.7 Rating Conditions. Any set of operating con
24、ditions under which a single level of performance results and which causes only that level of performance to occur. 3.7.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics.3.8 Refrigerant Flow Capacity. The refrigerating capacity for a flow
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI710IP2009PERFORMANCERATINGOFLIQUIDLINEDRIERSPDF

链接地址:http://www.mydoc123.com/p-422567.html