AHRI 210 240-2008 Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment (Incorporating Addenda No 1 June 2011 and Addenda No 2 March 2012).pdf
《AHRI 210 240-2008 Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment (Incorporating Addenda No 1 June 2011 and Addenda No 2 March 2012).pdf》由会员分享,可在线阅读,更多相关《AHRI 210 240-2008 Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment (Incorporating Addenda No 1 June 2011 and Addenda No 2 March 2012).pdf(136页珍藏版)》请在麦多课文档分享上搜索。
1、 2008 Standard for Performance Rating of Unitary Air-Conditioning deletions are shown by strikethroughs) into the already published 2008 version of ANSI/AHRI Standard 210/240 with Addendum 1 to avoid confusion: The Integrated Energy Efficiency Ratio (IEER) methodology has been added to the standard
2、for water-cooled and evaporatively-cooled products. It is not intended for air-cooled products which should be rated with SEER. This includes: 1. The addition of 3.4.2 definition of IEER (page 2) 2. The addition of “and in multiples of 0.1 for IEER” to Section 6.1.2 (page 5). 3. The addition of Part
3、-Load IEER Conditions to Test Conditions to Table 12 (page 21) 4. The reinstatement of Note 2 in Table 12 (page 21) 5. New Section 6.2 Part Load Ratings (pages 22-26). This new Section 6.2 is duplicated from Section 6.2 from AHRI Standard 340/360-2007 with addenda 1 and 2. 6. The addition of “plus t
4、he IEER (where applicable),” to Section 6.4 (page 26) 7. The addition of “except IEER which shall not be less than 90% of Published Ratings.” to Section 6.5 (page 26) 8. The addition of “3. Integrated Energy Efficiency Ratio, IEER”, to Section 7.1.b (page 27) ANSI/AHRI STANDARD 210/240-2008 WITH ADD
5、ENDUM 1 Performance Rating of Unitary Air-Conditioning classifications; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of
6、 the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Unitary Air-Conditioners and Air-Source Unitary
7、 Heat Pumps as defined in Section 3. 2.1.1 Energy Source. This standard applies only to electrically operated, vapor compression refrigeration systems. 2.2 Exclusions. 2.2.1 This standard does not apply to the rating and testing of individual assemblies, such as condensing units or coils, for separa
8、te use. 2.2.2 This standard does not apply to heat operated air-conditioning/heat pump equipment, or to packaged terminal air-conditioners/heat pumps, or to room air-conditioners/heat pumps. 2.2.3 This standard does not apply to Unitary Air-Conditioners as defined in AHRI Standard 340/360 with capac
9、ities of 65,000 Btu/h 19,000 W or greater. 2.2.4 This standard does not apply to Air-Source Unitary Heat Pumps as defined in AHRI Standard 340/360 with cooling capacities of 65,000 Btu/h 19,000 W or greater, or to water-source heat pumps, to ground water-source heat pumps, and to ground source close
10、d-loop heat pumps. 2.2.5 This standard does not include water heating heat pumps. 2.2.6 This standard does not apply to rating units equipped with desuperheater/water heating devices in operation. Section 3. Definitions All terms in this document shall follow the standard industry definitions in the
11、 current edition of ASHRAE Terminology of Heating, Ventilation, Air- Conditioning and Refrigeration, unless otherwise defined in this section. Note: Definitions for Small-duct, High-velocity Systems, Space Constrained Products, and Through-the-wall Air Conditioners and Heat Pumps are taken from Titl
12、e 10, Code of Federal Regulations, Part 430, Subparts 430.2 and 430.32 (c). See Appendix C for definitions that apply to the testing and calculation procedures required by Appendix C. ANSI/AHRI STANDARD 210/240-2008_ _ 2 3.1 Air-Source Unitary Heat Pump. One or more factory-made assemblies which nor
13、mally include an indoor conditioning coil(s), compressor(s), and outdoor coil(s), including means to provide a heating function. When such equipment is provided in more than one assembly, the separated assemblies shall be designed to be used together, and the requirements of rating outlined in the s
14、tandard are based upon the use of matched assemblies. 3.1.1 Functions. They shall provide the function of air heating with controlled temperature, and may include the functions of air-cooling, air-circulating, air-cleaning, dehumidifying or humidifying. 3.2 Degradation Coefficient (CD). The measure
15、of the efficiency loss due to the cycling of the units as determined in Appendices C and D. 3.3 Design Heating Requirement (DHR). This is the amount of heating required to maintain a given indoor temperature at a particular outdoor design temperature. 3.4 Energy Efficiency Ratio (EER). A ratio of th
16、e cooling capacity in Btu/h to the power input value in watts at any given set of Rating Conditions expressed in Btu/(Wh). 3.4.1 Standard Energy Efficiency Ratio. A ratio of the capacity to power input value obtained at Standard Rating Conditions. 3.4.2 Integrated Energy Efficiency Ratio (IEER). A s
17、ingle number cooling part-load efficiency figure of merit calculated per the method described in Section 6.2.2 expressed in Btu/(Wh). 3.5 Heating Seasonal Performance Factor (HSPF). The total space heating required during the space heating season, expressed in Btus, divided by the total electrical e
18、nergy consumed by the heat pump system during the same season, expressed in watt-hours. 3.6 Integrated Part-Load Value (IPLV). A single number part-load efficiency figure of merit calculated per the method described in this standard. 3.7 Published Rating. A statement of the assigned values of those
19、performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal capacity and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of al
20、l performance characteristics shown on the unit or published in specifications, advertising, or other literature controlled by the manufacturer, at stated Rating Conditions. 3.7.1 Application Rating. A rating based on tests performed at Application Rating Conditions (other than Standard Rating Condi
21、tions). 3.7.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.8 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.8.1 Standard Rating Conditions. Rating
22、Conditions used as the basis of comparison for performance characteristics. 3.9 Seasonal Energy Efficiency Ratio (SEER). The total heat removed from the conditioned space during the annual cooling season, expressed in Btus, divided by the total electrical energy consumed by the air conditioner or he
23、at pump during the same season, expressed in watt-hours. 3.10 “Shall“ or “Should“. “Shall“ or “should“ shall be interpreted as follows: 3.10.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.10.2 Should.
24、 “Should“ is used to indicate provisions which are not mandatory but which are desirable as good practice. _ _ ANSI/AHRI STANDARD 210/240-2008 3 3.11 Small-duct, High-velocity System. A heating and/or cooling product that contains a blower and indoor coil combination that is designed for, and produc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI2102402008PERFORMANCERATINGOFUNITARYAIRCONDITIONINGAIRSOURCEHEATPUMPEQUIPMENTINCORPORATINGADDENDANO1JUNE2011ANDADDENDANO2MARCH2012PDF

链接地址:http://www.mydoc123.com/p-422508.html