AHRI 1361 SI-2013 Performance Rating of Computer and Data Processing Room Air Conditioners.pdf
《AHRI 1361 SI-2013 Performance Rating of Computer and Data Processing Room Air Conditioners.pdf》由会员分享,可在线阅读,更多相关《AHRI 1361 SI-2013 Performance Rating of Computer and Data Processing Room Air Conditioners.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、 2013 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners AHRI Standard 1361 (SI) Price $15.00 (M) $30.00 (NM) Copyright 2013, by Air-Conditioning Heating and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SA
2、FETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembl
3、ed, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/ guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does no
4、t certify or guarantee that any tests conducted under the standards/guidelines will not be non-hazardous or free from risk. Note: This is a new standard. For I-P ratings, see AHRI Standard 1360 (I-P)-2013. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope .1 Section 3. Definitions
5、.1 Section 4. Classification.3 Section 5. Test Requirements 3 Section 6. Rating Requirements .4 Section 7. Minimum Data Requirements for Published Ratings .8 Section 8. Marking and Nameplate Data .10 Section 9. Conformance .11 TABLES Table 1. Standard Rating Conditions 5 FIGURES Figure 1. Different
6、CDPR Unit Configurations .1 APPENDICES Appendix A. References Normative 12 Appendix B. References Informative 12 AHRI STANDARD 1361 (SI)-2013 1 PERFORMANCE RATING OF COMPUTER AND DATA PROCESSING ROOM AIR CONDITIONERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Co
7、mputer and Data Processing Room Air Conditioners: definitions; classification; test requirements; rating requirements, minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, in
8、cluding manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to floor mounted Computer and Data Processing Room Air Conditioners (CDPR) which
9、 have three types: up-flow air discharge, down-flow air discharge and horizontal free air discharge, as illustrated in Figure 1. 2.2 Exclusions. This standard does not apply to the rating of individual assemblies, such as condensing units or direct expansion fan-coil units, for separate use. Figure
10、1. Different CDPR Unit Configurations. Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Wikipedia website (http:/wiki.ashrae.org/index.php/ASHRAEwiki) unless otherwise defined in this section. 3.1 Computer and Data Processing Room Air Cond
11、itioner (CDPR). A Computer and Data Processing Room Air Conditioner consists of one or more factory-made assemblies, which include a direct expansion evaporator or chilled water cooling coil, an air-moving device and air-filtering devices. The air conditioner may include a compressor, condenser, hum
12、idifier or reheating function. Where direct expansion equipment is provided in more than one assembly and the separate assemblies are to be used together, the requirements of rating outlined in this standard are based upon the use of matched assemblies. The functions of a CDPR air conditioner, eithe
13、r alone or in combination with a cooling and heating plant, are to provide air filtration, circulation, cooling, and optional reheating and humidity control. AHRI STANDARD 1361 (SI)-2013 2 3.2 Computer Room Air Conditioner (CRAC). Computer-room cooling units that utilize dedicated compressors and re
14、frigerant cooling coils rather than chilled-water coils. 3.3 Computer Room Air Handler (CRAH). Computer-room cooling units that utilize chilled-water coils for cooling rather than dedicated compressors. 3.4 Dehumidification Capacity. Dehumidification Capacity shall be stated as the units total laten
15、t removal when in the full dehumidification mode of operation. This value shall be calculated as the difference between Net Total Cooling Capacity and Net Sensible Cooling Capacity when tested per the Standard Rating Conditions. Input ratings shall be the total power input to the unit; included but
16、not limited to fan motor(s), compressor(s), damper(s) and control(s) etc. 3.5 Fluid Economizer. An option available with a CRAC or CRAH system in which a cold fluid is circulated by a pump through an indoor heat exchanger to provide cooling during lower outdoor ambient conditions, in order to reduce
17、 or eliminate compressor operation. The fluid could be chilled water, water/glycol solution, or refrigerant. An external fluid cooler such as a dry cooler, cooling tower, or condenser is utilized for heat rejection. This process is sometimes referred to as free cooling, econ-o-coil, or economizer. 3
18、.6 Humidification Capacity. Humidification Capacity shall be stated as both total and net Humidification Capacity. The total Humidification Capacity reflects the units total humidification output without the mechanical cooling system operating when tested per the manufacturers literature at Standard
19、 Rating Conditions. The net Humidification Capacity shall reflect the units total humidification output when concurrently operating the mechanical cooling system at full capacity and humidification system per manufactures literature at Standard Rating Conditions. Input ratings shall be the total pow
20、er input to the unit; included but not limited to fan motor(s), humidifier(s), compressor(s), damper(s) and control(s) etc. 3.7 Integrated Net Sensible Coefficient of Performance (iNSenCOP). An NSenCOP value that provides a consistent evaluation of the energy efficiency of a unit operated across the
21、 specified range of outdoor ambient temperatures (see Table 1). 3.8 Net Sensible Coefficient of Performance (NSenCOP). A ratio of the Net Sensible Cooling Capacity in watts to the total power input in watts (excluding reheaters and humidifiers) at any given set of rating conditions. 3.9 Net Sensible
22、 Cooling Capacity. The rate, expressed in kW, at which the equipment removes sensible heat from the air passing through it under specified conditions of operation. 3.10 Net Total Cooling Capacity. The rate, expressed in kW, at which the equipment removes heat from the air passing through it under sp
23、ecified conditions of operation. 3.11 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produc
24、ed by the same manufacturer. As used herein, the term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.11.1 Standard Rating. A ratin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1361SI2013PERFORMANCERATINGOFCOMPUTERANDDATAPROCESSINGROOMAIRCONDITIONERSPDF

链接地址:http://www.mydoc123.com/p-422505.html