AHRI 1230-2010 Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment (Incorporating Addendum 1 March 2011 Addendum 2 June 2014).pdf
《AHRI 1230-2010 Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment (Incorporating Addendum 1 March 2011 Addendum 2 June 2014).pdf》由会员分享,可在线阅读,更多相关《AHRI 1230-2010 Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment (Incorporating Addendum 1 March 2011 Addendum 2 June 2014).pdf(196页珍藏版)》请在麦多课文档分享上搜索。
1、 2010 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment Approved by ANSI on 2 August 2010 ANSI/AHRI Standard 1230 with Addendum 2 ANSI/AHRI STANDARD 1230-2010 WITH ADDENDUM 2, Performance Rating of Variable Refrigerant Flow (VRF)
2、Multi-Split Air-Conditioning and Heat Pump Equipment June 2014 Addendum 2 (dated June 2014) of ANSI/AHRI Standard 1230-2010, changes AHRI Standard 1230-2010 as follows. Changes have been incorporated (additions are shown by shading and deletions are shown by strikethroughs) into the already publishe
3、d version of ANSI/AHRI Standard 1230-2010 with Addendum 1. The changes are to the inside front cover, scope of the VRF certification program, Sections 2.1, 3.23, 5.1, 5.2, 5.3, 6.1, 6.1.7, 6.6, 6.7, 9.1, and D3.4. Important Note: Until AHRI Standard 1230 is approved by DOE,VRF multi-split air-cooled
4、 air conditioners and heat pumps, below 65,000 Btu/h 19,000 W shall be rated in accordance with ARI Standard 210/240-2008. Applicability Integrated Energy Efficiency Ratio (IEER) is effective beginning January 1, 2010. Integrated Part-Load Value is in effect until January 1, 2010. On January 1, 2010
5、, IEER will supersede IPLV. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification Program includes all Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning, and Heat Pump, and Heat Recovery Equipment rated at AHRI Standard Rating Conditions (Cooling). Cer
6、tified Ratings The following Certification Program ratings are verified by test: Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and Heat Pump Equipment a. For VRF Multi-Split Air-Conditioners 0 in H2O Rated Cooling1or Heating2Capacity Minimum External Resistance3,4Small-duct High-veloc
7、ity Systems5 All Other Systems Btu/h kW in H2O Pa in H2O Pa Up through 28,800 6.40 to 8.44 1.10 275 0.10 25 29,000 to 42,500 8.5 to 12.4 1.15 388 0.15 37 43,000 thru 60,000 12.6 thru 19.0 1.20 300 0.20 50 Notes: 1) For air conditioners and heat pumps, the value cited by the manufacturer in published
8、 literature for the units capacity when operated at the A2 Test conditions. 2) For heating-only heat pumps, the value the manufacturer cites in published literature for the units capacity when operated at the H12 Test conditions. 3) For ducted units tested without an air filter installed, increase t
9、he applicable tabular value by 0.08 in H2O 20 Pa. 4) If the manufacturers rated external static pressure is less than 0.10 in H2O (25 Pa), then the indoor unit should be tested at that rated external static pressure. (See Section 5.2.1.2) 5) See Definition 1.35 of Appendix C to determine if the equi
10、pment qualifies as a Small-duct, High-velocity System. 6.6 Test Tolerances (Applies to all products covered by this standard). To comply with this standard, measured test results shall not be less than 95% of Published Ratings for capacities, SEER, HSPF, EER values, and COP values and not less than
11、90%of Published Ratings for IEER and SCHE values. 6.6 Verification Testing Uncertainty. When verifying the ratings by testing a sample unit, there are uncertainties that must be considered. Verification tests, including tests conducted for the AHRI certification program shall be conducted in a labor
12、atory that meets the requirements referenced in this standard and ASHRAE Standard 37 and must demonstrate performance with an allowance for uncertainty. The following make up the uncertainty for products covered by this standard. 6.6.1 Uncertainty of Measurement. When testing a unit, there are varia
13、tions that result from instrumentation and measurements of temperatures, pressure, and flow rates. 6.6.2 Uncertainty of Test Rooms. A unit tested in multiple rooms will not yield the same performance due to setup variations. 6.6.3 Variation due to Manufacturing. During the manufacturing of units, th
14、ere are variations due to manufacturing production tolerances that will impact the performance of a unit. 6.6.4 Uncertainty of Performance Simulation Tools. Due to the large complexity of options, use of performance prediction tools like an AEDM has some uncertainties. 6.7 To comply with this standa
15、rd, verification tests shall meet the performance metrics shown in Table 13 with an uncertainty allowance not greater than the following: Table 13. Uncertainty Allowances Performance Metric Uncertainty Allowance Acceptance Criteria1 Cooling Capacity 5% 95% SEER2 5% 95%EER 5% 95% IEER3 10% 90% SCHE4
16、10% 90% Heating Capacity5 5% 95% COP3,5 5% 95% HSPF2 5% 95% Notes: 1) Must be (1 uncertainty allowance). 2) Applies only to systems 0 in H20 17 Table 9 Operating Conditions for Standard Rating and Performance Operating Tests for Systems 65,000 Btu/h 19,000W 19 Table 10 Test Conditions for the Determ
17、ination of Cooling Capacity for Systems that Use a Water Source for Heat Rejection 21 Table 11 Test Conditions for the Determination of Heating Capacity for Systems that Use a Water Source for Heat Rejection 22 Table 12 IEER Part-Load Rating Conditions 23 Table 13 Uncertainty Allowances 27 Table 14
18、Maximum Cooling Test Conditions for Systems that Use a Water Source for Heat Rejection .33 Table 15 Maximum Heating Test Conditions for Systems that Use a Water Source for Heat Rejection .34 Table 16 Minimum Cooling Test Conditions for Systems that Use a Water Source for Heat Rejection .34 Table 17
19、Minimum Heating Test Conditions for Systems that Use a Water Source for Heat Rejection .35 Table 18 Enclosure Sweat and Condensate Test Conditions for Systems that Use a Water Source for Heat Rejection 35 Table 19 Uncertainties of Measurement for Indicated Values 36 Table 20 Variations Allowed in Ca
20、pacity Test Readings 37 Table 21 Variations Allowed in Performance Test Readings 37 Table 22 Simultaneous Heating and Cooling Test Conditions 38 LIST OF FIGURES FIGURE PAGE Figure 1 Test Room Layout.14 APPENDICES APPENDIX PAGE Appendix A References Normative 40 Appendix B References Informative 40 A
21、ppendix C Uniform Test Method for Measuring the Energy Consumption of Central Air Conditioners and Heat Pumps Normative 41 Appendix M to Subpart B of Part 430 Uniform Test Method for Measuring the Energy Consumption of Central Air Conditioners and Heat Pumps 41 Appendix D Test Requirements Normative
22、 .128 Appendix E Heat Recovery Test Method Normative 151 Appendix F Individual Indoor Unit Capacity Tests Normative .163 Appendix G Prescriptive Methodology for the Cyclic Testing Of Ducted Systems Normative 171 Appendix H Integrated Part-Load Values (IPLV) Normative176 TABLES FOR APPENDICES TABLE P
23、AGE Table D1 Sizes of Calorimeter 134 Table D2 Variations Allowed During Steady State Cooling and Heating Capacity Tests That Only Apply When Using the Indoor Air Enthalpy Method .140 Table D3 Variations Allowed During the Transient Heating Tests That Only Apply When Using The Indoor Air Enthalpy Te
24、st Method .140 Table E1 Simultaneous Heating and Cooling Test Conditions 151 Table E2 Variations Allowed During Steady State Cooling And Heating Capacity Tests That Only Apply When Using The Indoor Air Enthalpy Method .153 Table E3 Variations Allowed During The Transient Heating Tests That Only Appl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI12302010PERFORMANCERATINGOFVARIABLEREFRIGERANTFLOWVRFMULTISPLITAIRCONDITIONINGANDHEATPUMPEQUIPMENTINCORPORATINGADDENDUM1MARCH2011ADDENDUM2JUNE2014PDF

链接地址:http://www.mydoc123.com/p-422485.html