AHRI 1210 I-P-2011 Performance Rating of Variable Frequency Drives.pdf
《AHRI 1210 I-P-2011 Performance Rating of Variable Frequency Drives.pdf》由会员分享,可在线阅读,更多相关《AHRI 1210 I-P-2011 Performance Rating of Variable Frequency Drives.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 2011 Standard for Performance Rating of Variable Frequency Drives AHRI Standard 1210 (I-P) Price $10.00 (M) $20.00 (NM) Printed in U.S.A. Copyright 2011, by Air-Conditioning, Heating and Refrigeration Institute Registered United States Patent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI do
2、es not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and opera
3、ted in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee t
4、hat any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This is a new standard. This standard seeks to provide an uniform method of measuring and comparing Variable Frequency Drives by establishing testing and rating requirements; specifically data requi
5、rements for Drive System Efficiency, Power Line Harmonics and Motor Insulation Stress. For SI ratings, see AHRI Standard 1211 (SI)-2011TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions . 1 Section 4. Classifications . 2 Section 5. General Test Requiremen
6、ts . 3 Section 6. Rating Requirements . 6 Section 7. Minimum Data Requirements for Published Requirements 6 Section 8. Marking and Nameplate Data 7 Section 9. Conformance Conditions. 7 TABLES Table 1A. Voltage Classes . 3 Table 1B. Power Classifications 3 Table 2. Speed/Torque Test Points for Drive
7、System Efficiency and Motor Stress Insulation Tests 4 Table 3. Speed/Torque Test Points for Powerline Harmonics Test. 4 Table 4. VFD to Motor Conductor Sizes 5 Table 5. Reported Harmonic Current 6 APPENDICES Appendix A. References Normative 8 Appendix B. References Informative 9 Appendix C. Methods
8、of Testing Rating Variable Frequency Drives - Normative 10 FIGURES FOR APPENDICES Figure C1. Test Set-up for Drive System Efficiency and Powerline Harmonics Test Methods 11 AHRI STANDARD 1210 (I-P)-2011 1 PERFORMANCE RATING OF VARIABLE FREQUENCY DRIVES Section 1. Purpose 1.1 Purpose. The purpose of
9、this standard is to establish for Variable Frequency Drives (VFDs): definitions; classifications; general test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the g
10、uidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies, within the heating, ventilating, air-conditioning an
11、d refrigeration (HVACR) context, to VFDs used in the control of asynchronous induction motors. The range includes all those found within a building including: low voltage ( 600 V) and drives that are stand alone, not mechanically integrated into motors. 2.2 Exclusions. This standard does not apply t
12、o VFDs applied to motors other than those listed above. Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning, and Refrigeration unless otherwise defined in this section. 3.1 C
13、arrier Switching Frequency. The frequency at which the power output devices of a VFD are switched on and off. 3.2 Constant Torque (CT). Applications where the torque requirement of the driven load remains constant or nearly so over the normal speed range of use. Positive-displacement pumps and recip
14、rocating compressors are examples of constant-torque loads. 3.3 Drive System Efficiency. Ratio of the output power from the motor to the input power of the VFD including motor and VFD losses. 3.4 Equipment Under Test (EUT). Test sample. 3.5 Motor Insulation Stress. The voltage stress placed on a mot
15、ors insulation due to high Peak Voltages and short-rise times that occur when the motor is driven by a VFD. 3.6 Motor Thermal Equilibrium. When the observed temperature rise of the motor winding does not vary more than 2F over a period of 30 minutes, or when the observed motor frame or core temperat
16、ure rise does not vary more than 2F over a period of 60 minutes. 3.7 Peak Voltage. The maximum instantaneous voltage measured at a motors terminals when operated from a VFD. 3.8 Percent Speed. The percentage of rated motor rpm as measured. 3.9 Percent Torque. The percentage of the motor rated Full L
17、oad torque. AHRI STANDARD 1210 (I-P)-2011 2 3.10 Power Line Harmonics. Components of the power line voltage and current at the input of the VFD that are integer multiples of the fundamental sinusoidal frequency of the power source (example 60 Hz). 3.11 Published Rating. A rating of the assigned valu
18、es of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rati
19、ng of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.11.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rati
20、ng Conditions). 3.11.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.12 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur (e.g. line voltage, ambient temp
21、erature). 3.12.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.13 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.13.1 Shall. Where “shall“ or “shall not“ is used for a provision, that provision is mandato
22、ry if compliance with the standard is claimed. 3.13.2 Should. “Should“ is used to indicate provisions which are not mandatory but are desirable as good practice. 3.14 Short Circuit Ratio (RSCE). The short-circuit power at the point of common coupling (PCC), divided by the rated apparent power of the
23、 drive and as defined in IEC Standard 61000-3-12, Section 3.14 Subsection C. 3.15 Supply Voltage (Vs). The line to line input voltage to the equipment at time of testing. 3.16 System Loss. The combination of electrical and mechanical losses represented by the difference between input power to the dr
24、ive and output power from the motor. 3.17 Total Harmonic Distortion. A measure of power line distortion that sums the contributions of the individual harmonics. VFDs typically only contribute odd numbered harmonics with a decreasing impact of the higher order harmonics. 3.18 Variable Frequency Drive
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1210IP2011PERFORMANCERATINGOFVARIABLEFREQUENCYDRIVESPDF

链接地址:http://www.mydoc123.com/p-422483.html