AHRI 110-2016 Air-conditioning Heating and Refrigerating Equipment Nameplate Voltages.pdf
《AHRI 110-2016 Air-conditioning Heating and Refrigerating Equipment Nameplate Voltages.pdf》由会员分享,可在线阅读,更多相关《AHRI 110-2016 Air-conditioning Heating and Refrigerating Equipment Nameplate Voltages.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、 2016 Standard for Air-conditioning, Heating and Refrigerating Equipment Nameplate Voltages AHRI Standard 110 Price $10.00 (M) $20.00 (NM) Copyright 2016, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY
2、 RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with nationally recognized safety requirements appropriate for products covered by this standard. AHRI, as a manufacturers trade association, uses its best efforts to develop
3、standards employing state-of-the-art and accepted industry practices. However, AHRI does not certify or guarantee safety of any products, components or systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted under its standards will be no
4、n-hazardous or free from risk. Note: This standard supersedes ANSI/AHRI Standard 110-2012. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope . 1 Section 3. Definitions. 1 Section 4. Voltage Rating Requirements . 3 Section 5. Equipment Performance Requirements . 8 Section 6. Confor
5、mance Conditions 8 TABLES Table 1. Low Voltage 60 Hz Systems in the USA5 Table 2. Medium Voltage 60 Hz Systems in the USA. 6 Table 3. Standard Nominal System Voltages for 50Hz and 60Hz Systems (Non-USA Systems) 7 Table 4. AC Three Phase Systems with Nominal Voltage Above 1kV and not Exceeding 35kV a
6、t 50Hz and 60Hz (For Non- USA Systems Only) . 8 FIGURES Figure 1. Three-phase Three-wire Voltage Source Ungrounded- Wye. 2 Figure 2. Three-phase Four-wire Voltage Source 2 Figure 3. Three-phase Three-wire Voltage Source - Delta 3 Figure 4. Corner-grounded Voltage Source. . 3 Figure 5. High-leg Volta
7、ge Source . 3 APPENDICES Appendix A. References - Normative 9 Appendix B. References - Informative . 9 AHRI STANDARD 110-2016 1 AIR-CONDITIONING, HEATING AND REFRIGERATING EQUIPMENT NAMEPLATE VOLTAGES Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for air-conditioning,
8、 heating and refrigerating equipment: definitions; voltage rating requirements; equipment performance requirements; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors, and users. 1.1.2 Revi
9、ew and Amendment. This standard is subject to review and amendment as technology advances. 1.2 The provisions herein are recommendations intended for implementation only through reference by other authoritative documents. Section 2. Scope 2.1 Scope. This standard applies to 50 Hz and 60 Hz electrica
10、l voltage ratings and operating limits as applied to air-conditioning, heating and refrigerating equipment, heat pumps, and electric furnaces as well as components. 2.1.1 Exclusions. Voltages less than 100V AC are not included in this standard. Section 3. Definitions All terms in this document will
11、follow the standard industry definitions in the ASHRAE Terminology website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Delta. A three-phase transformer coil configuration that is commonly abbreviated by the Greek lett
12、er . 3.2 “Shall“ or “Should.“ “Shall“ or “should“ shall be interpreted as follows: 3.3.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.3.2 Should. “Should“ is used to indicate provisions which are not
13、mandatory but which are desirable as good practice. 3.3 Voltages. 3.3.1 Equipment Nameplate Voltage Rating. The nominal Utilization Voltage marked on the equipment nameplate by the manufacturer (Tables 1 and 2). 3.3.2 Low Voltage. The Nominal System Voltage with the range between 100V and 1kV AC acc
14、ording to ANSI C84.1. 3.3.3 Medium Voltage. The Nominal System Voltage with the range between 1kV and 35kV AC according to IEEE 1585. Note: For the purposes of this standard, 1kV is included under Medium Voltage. 3.3.4 Nominal System Voltage. A nominal value assigned to the electric power supply sys
15、tem for the purpose of conveniently designating its voltage class. AHRI STANDARD 110-2016_ 2 3.3.5 Service Voltage. The voltage at the point where the electric systems of the supplier and the user are connected. 3.3.6 Utilization Voltage. The voltage at the line terminals of the utilization equipmen
16、t. 3.4 Three-phase Systems. 3.4.1 Wye. A three-phase transformer coil configuration that is commonly abbreviated by the letter Y. If a neutral conductor is supplied then it is connected to the center point of the transformer (see Figure 1). Figure 1. Three-phase Three-wire Voltage Source Ungrounded
17、- Wye 3.4.2 Three-phase Four-wire System. A symmetrical voltage source which provides a grounded neutral conductor for connection of loads. The phase-to-neutral voltage amplitudes are 0.577 times the phase-to-phase amplitudes. Four-wire systems in Table 1 are designated by the phase-to-phase voltage
18、, followed by the letter Y, which defines the transformer coil configuration, a slant line, and the phase-to-neutral voltage (see Figure 2). Figure 2. Three-phase Four-wire Voltage Source 3.4.3 Three-phase Three-wire System. A voltage source which only provides three phase conductors to the loads. T
19、he source may be derived from symmetrical, grounded or ungrounded transformer connections (see Figure 3). AHRI STANDARD 110-2016 3 Figure 3. Three-phase Three-wire Voltage Source - Delta 3.4.4 Corner-grounded System. An asymmetrical three-wire voltage source in which one conductor is grounded. For t
20、he remaining phases the phase-to-neutral voltage amplitudes and the phase-to-phase amplitudes are the same (see Figure 4). Figure 4. Corner-grounded Voltage Source 3.4.5 High-leg System. An asymmetrical three-wire voltage source in which a center-tap of one transformer coil is grounded. The phase-to
21、-neutral voltage amplitude of two phases is 0.5 times the phase-to-phase amplitude. The high leg phase amplitude is 0.865 times the phase-to-phase amplitudes (see Figure 5). Figure 5. High-leg Voltage Source Section 4. Voltage Rating Requirements 4.1 Standard System Voltage Relationships. Tables 1,
22、2, and 3 present the basic relationships between standard Nominal System Voltages and Utilization Voltages for air-conditioning, heating and refrigeration equipment and components. (Data derived from ANSI C84.1). AHRI STANDARD 110-2016_ 4 4.2 Application of Voltage Ranges. (See ANSI C84.1). 4.2.1 Ra
23、nge A-Service Voltage. Electric supply systems are designed and operated so that most Service Voltages are within the limits specified for this range. The occurrence of Service Voltages outside of these limits should be infrequent and should be handled as a special occurrence. 4.2.2 Range A-Utilizat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1102016AIRCONDITIONINGHEATINGANDREFRIGERATINGEQUIPMENTNAMEPLATEVOLTAGESPDF

链接地址:http://www.mydoc123.com/p-422474.html