AHRI 1061 SI-2014 Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment.pdf
《AHRI 1061 SI-2014 Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment.pdf》由会员分享,可在线阅读,更多相关《AHRI 1061 SI-2014 Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、 AHRI Standard 1061 (SI) 2014 Standard for Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation EquipmentPrice $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning, Heating and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office
2、 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constru
3、cted, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices.
4、AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 1061-2013 (SI). For I-P ratings, see AHRI Standard 1060 (I-P)-2014.TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Sect
5、ion 2. Scope . 1 Section 3. Definitions. 1 Section 4. Test Requirements 3 Section 5. Rating Requirements . 5 Section 6. Minimum Data Requirements for Published Ratings . 6 Section 7. Marking and Nameplate Data . 7 Section 8. Conformance Conditions 8 TABLES Table 1. Standard Rating Conditions 4 Table
6、 2. Multiples for Rated Airflow 7 FIGURES Figure 1. Scheme of Airflows for Exchangers . 2 APPENDICES Appendix A. References - Normative 9 Appendix B. References - Informative. 9 Appendix C. Calculation of Effectiveness - Normative . 10AHRI STANDARD 1061 (SI)-2014 1 PERFORMANCE RATING OF AIR-TO-AIR E
7、XCHANGERS FOR ENERGY RECOVERY VENTILATION EQUIPMENT Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Air-to-Air Heat Exchangers intended for use in Air-to-Air Energy Recovery Ventilation Equipment: definitions; test requirements; rating requirements; minimum data requ
8、irements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, designers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and
9、amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made Air-to-Air Exchangers for use in Air-to-Air Energy Recovery Ventilation Equipment as defined in Section 3. 2.2 Exclusions. This standard does not apply to the rating and testing of heat exchangers joi
10、ned by circulated heat transfer medium (run-around loop). A run-around loop employs liquid-containing coils connected in a closed loop and placed in each of two or more airstreams. Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Terminolo
11、gy website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Air-to-Air Energy Recovery Ventilation Equipment (AAERVE). Energy recovery components and packaged energy recovery ventilation units which employ Air-to-Air Excha
12、ngers to recover energy from exhaust air for the purpose of pre-conditioning outdoor air prior to supplying the conditioned air to the space, either directly or as part of an air-conditioning (to include air heating, air cooling, air circulating, air cleaning, humidifying and dehumidifying) system.
13、3.2 Air-to-Air Exchanger (hereinafter, “Exchanger”). A device that transfers heat from an exhaust airstream to a separated supply airstream. Air-to-Air Exchangers are also referred to as energy recovery components. 3.2.1 Heat Pipe Heat Exchanger. A device employing tubes charged with a fluid for the
14、 purpose of transferring sensible energy from one airstream to another. Heat transfer takes place through the vaporization of the fluid exposed to the warmer airstream and condensation of the fluid in the cooler airstream. 3.2.2 Plate Heat Exchanger. A device for the purpose of transferring energy (
15、sensible or total) from one airstream to another with no moving parts. The design may incorporate parallel, cross or counter flow construction or a combination of these to achieve the energy transfer. 3.2.3 Rotary Heat Exchanger. A device incorporating a rotating cylinder or wheel for the purpose of
16、 transferring energy (sensible or total) from one airstream to the other. It incorporates heat transfer material, a drive mechanism, a casing or frame, and includes any seals which are provided to retard the bypassing and leakage of air from one airstream to the other. 3.3 Airflow. 3.3.1 Entering Su
17、pply Airflow (OA). The supply airstream (outdoor air) before passing through the exchanger indicated in Figure 1 as Station 1. Sometimes referred to as the outdoor Airflow. 3.3.2 Leaving Supply Airflow (SA). The supply airstream (outdoor air) after passing through the exchanger, AHRI STANDARD 1061 (
18、SI)-2014 2 indicated in Figure 1 as Station 2. Sometimes referred to as the supply Airflow. 3.3.3 Entering Exhaust Airflow (RA). The exhaust airstream (indoor air) before passing through the exchanger, indicated in Figure 1 as Station 3. Sometimes referred to as the return Airflow. 3.3.4 Leaving Exh
19、aust Airflow (EA). The exhaust airstream (indoor air) after passing through the exchanger, indicated in Figure 1 as Station 4. Sometimes referred to as the exhaust Airflow. Figure 1. Scheme of Airflows for Exchangers 3.4 Capacity Rate. The quantity of energy an airstream at a specific mass flow rate
20、 is able to absorb or release per unit time per unit change in temperature, humidity content, or enthalpy content. 3.5 Effectiveness. A ratio of the actual energy transfer (sensible, latent, or total) to the product of the minimum energy capacity rate and the maximum difference in temperature, humid
21、ity ratio, or enthalpy. The equation for determining Effectiveness is Equation C1 in Appendix C. Effectiveness is not adjusted to account for that portion of the psychrometric change in the Leaving Supply Airflow that is the result of leakage of Entering Exhaust Airflow rather than exchange of heat
22、or moisture between the airstreams. 3.5.1 Sensible Effectiveness. The Effectiveness determined in Section 3.5 using only measured dry bulb temperature differences, specific heat capacities and mass airflow rates. 3.5.2 Latent Effectiveness. The Effectiveness determined in Section 3.5 using only meas
23、ured humidity ratios, heat of vaporization values and mass airflow rates. 3.5.3 Total Effectiveness. The Effectiveness determined in Section 3.5 using only measured enthalpies and mass airflow rates. 3.5.4 Net Effectiveness. The Effectiveness adjusted to account for that portion of the psychrometric
24、 change in the Leaving Supply Airflow that is the result of leakage of Entering Exhaust Airflow rather than exchange of heat or moisture between the airstreams. The derivation of Net Effectiveness is given in Appendix C. 3.6 Exhaust Air Transfer Ratio (EATR). The tracer gas concentration difference
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1061SI2014PERFORMANCERATINGOFAIRTOAIREXCHANGERSFORENERGYRECOVERYVENTILATIONEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-422472.html