AASHTO M 201-2015 Standard Specification for Mixing Rooms Moist Cabinets Moist Rooms and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes.pdf
《AASHTO M 201-2015 Standard Specification for Mixing Rooms Moist Cabinets Moist Rooms and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes.pdf》由会员分享,可在线阅读,更多相关《AASHTO M 201-2015 Standard Specification for Mixing Rooms Moist Cabinets Moist Rooms and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Standard Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes AASHTO Designation: M 201-15 ASTM Designation: C511-13 American Association of State Highway and Transportation Officials 444 North Capitol Street N.W.
2、, Suite 249 Washington, D.C. 20001 TS-3a M 201-1 AASHTO Standard Specification for Mixing Rooms, Moist Cabinets, Moist Rooms, and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes AASHTO Designation: M 201-15 ASTM Designation: C511-13 1. SCOPE 1.1. This specification include
3、s requirements for mixing rooms, where paste and mortar specimens are prepared, and for moist cabinets, moist rooms, and water storage tanks, where paste, mortar, and concrete test specimens are stored. 1.2. The values stated in SI units are to be regarded as standard. No other units of measurement
4、are included in this standard. Values in SI units shall be obtained by measurement in SI units or by appropriate conversion, using the Rules for Conversion and rounding given in Standard IEEE/ASTM SI 10, of measurements made in other units. 1.3. This standard does not purport to address all of the s
5、afety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. 2. REFERENCED DOCUMENTS 2.1. ASTM Standards: C51, Standard Terminology R
6、elating to Lime and Limestone (as used by the Industry) E77, Standard Test Method for Inspection and Verification of Thermometers 2.2. IEEE/ASTM Standard: SI10, American National Standard for Metric Practice 3. TERMINOLOGY 3.1. Definitions: 3.1.1. mixing room, na room with controlled temperature and
7、 relative humidity where cement paste and mortar specimens are prepared. 3.1.2. moist cabinet, na compartmented storage facility of moderate dimensions with controlled temperature and relative humidity. 3.1.3. moist room, na walk-in storage facility with controlled temperature and relative humidity,
8、 commonly called a “fog room” when the prescribed relative humidity is achieved by the atomization of water. 2016 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-3a M 201-2 AASHTO 4. REQUIREMENTS FOR CEMEN
9、T MIXING ROOMS 4.1. The temperature of the air in the vicinity of the mixing slab, molds, and baseplates shall be maintained at 23.0 4.0C and at a relative humidity of not less than 50 percent. 4.2. The temperature of the mixing water used to prepare cement paste and mortar specimens shall be 23.0 2
10、.0C. 5. TEMPERATURE MEASURING DEVICES 5.1. Reference Temperature Measuring DevicesUsed to verify the temperature recorder, must be accurate and readable to 0.5C. A copy of the certificate or report that verifies the accuracy shall be available in the laboratory. Note 1The ice-point method described
11、in ASTM E77 may be used to ensure that no damage to the reference thermometer has occurred during shipping. 5.2. Temperature RecorderShall record temperatures every 15 min or less and shall be accurate and readable to 1C. The data from the recorder shall be evaluated at a minimum of once each week.
12、A record of this evaluation documenting the date checked, a confirmation that the data are within the required temperature range, and the name of the individual performing this evaluation shall be maintained in the laboratory. (See Note 2.) Note 2This requirement may be satisfied by an initialed and
13、 dated temperature recorder chart. Brief changes in the temperature due to door openings should be ignored. 5.2.1. The temperature recorder shall be verified at least every 6 months or whenever there is a question of accuracy. 5.2.1.1. For moist cabinets and rooms, position the reference temperature
14、 measuring device in a readable position in air as near as practical to the temperature recorder probe. Keep the door closed for at least 5 min prior to taking readings. Record the temperature readings of both the temperature recorder and the reference temperature measuring device. When taking these
15、 readings, the reference temperature measuring device shall remain in the moist cabinet or room and be read immediately upon opening the door. 5.2.1.2. For water storage tanks, position the reference temperature measuring device in a readable position in water as near as practical to the temperature
16、 recorder probe. Without removing the reference temperature measuring device from the water, record the temperature readings of both the temperature recorder and the reference temperature measuring device after the temperatures have stabilized. 5.2.1.3. Verify the accuracy of the temperature recorde
17、r by comparing the reading of the temperature recorder with that of the reference temperature measuring device during the normal operation of the moist cabinet, moist room, or water storage tanks. If the difference between the temperature readings is greater than 1C, the temperature recorder shall b
18、e adjusted to within 0.5C of the reference temperature measuring device. 6. REQUIREMENTS FOR MOIST CABINETS AND MOIST ROOMS 6.1. GeneralExcept during those times when specimens are being placed into or removed from storage, maintain the atmosphere in a moist cabinet or moist room at a temperature of
19、 23.0 2.0C and a relative humidity of not less than 95 percent. Maintain atmospheric conditions within a moist cabinet or moist room such that test specimens in storage are saturated with moisture to the degree needed to ensure that the exposed surfaces of all specimens in storage both look moist 20
20、16 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-3a M 201-3 AASHTO and feel moist (see Note 5). Equip all moist cabinets and moist rooms with a temperature recorder. The use of humidity recording devices
21、 is optional. Keep shelves on which fresh specimens are placed level. 6.1.1. The air temperature inside the moist cabinet or moist room shall be controlled with provisions made for heating or cooling, or both, as may be necessary. This shall be accomplished in one of two ways: 6.1.1.1. Thermostatica
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AASHTOM2012015STANDARDSPECIFICATIONFORMIXINGROOMSMOISTCABINETSMOISTROOMSANDWATERSTORAGETANKSUSEDINTHETESTINGOFHYDRAULICCEMENTSANDCONCRETESPDF

链接地址:http://www.mydoc123.com/p-417701.html