AASHTO M 170-2017 Standard Specification for Reinforced Concrete Culvert Storm Drain and Sewer Pipe.pdf
《AASHTO M 170-2017 Standard Specification for Reinforced Concrete Culvert Storm Drain and Sewer Pipe.pdf》由会员分享,可在线阅读,更多相关《AASHTO M 170-2017 Standard Specification for Reinforced Concrete Culvert Storm Drain and Sewer Pipe.pdf(23页珍藏版)》请在麦多课文档分享上搜索。
1、Standard Specification for Reinforced Concrete Culvert, Storm Drain, and Sewer Pipe AASHTO Designation: M 170-171Technical Section: 4a, Concrete Drainage Structures Release: Group 2 (June 2017) ASTM Designation: C76-16 American Association of State Highway and Transportation Officials 444 North Capi
2、tol Street N.W., Suite 249 Washington, D.C. 20001 TS-4a M 170-1 AASHTO Standard Specification for Reinforced Concrete Culvert, Storm Drain, and Sewer Pipe AASHTO Designation: M 170-171Technical Section: 4a, Concrete Drainage Structures Release: Group 2 (June 2017) ASTM Designation: C76-16 1. SCOPE 1
3、.1. This specification covers reinforced concrete pipe intended to be used for the conveyance of sewage, industrial wastes, and storm water, and for the construction of culverts. 1.2. A complete metric companion to M 170 has been developedM 170M; therefore, no metric equivalents are presented in thi
4、s specification. Note 1This specification is a manufacturing and purchase specification only, and does not include requirements for bedding, backfill, or the relationship between field load condition and the strength classification of pipe. However, experience has shown that the successful performan
5、ce of this product depends on the proper selection of the class of pipe, type of bedding and backfill, and care that installation conforms to the construction specifications. Owners of the reinforced concrete pipe specified herein are cautioned that they must correlate the field requirements with th
6、e class of pipe specified and provide inspection at the construction site. Note 2Attention is called to the specification for reinforced concrete D-load culvert, storm drain, and sewer pipe (M 242M/M 242). 2. REFERENCED DOCUMENTS 2.1. AASHTO Standards: M 6, Fine Aggregate for Hydraulic Cement Concre
7、te M 31M/M 31, Deformed and Plain Carbon and Low-Alloy Steel Bars for Concrete Reinforcement M 32M/M 32, Steel Wire, Plain, for Concrete Reinforcement M 55M/M 55, Steel Welded Wire Reinforcement, Plain, for Concrete M 80, Coarse Aggregate for Hydraulic Cement Concrete M 85, Portland Cement M 86M/M 8
8、6, Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe M 154M/M 154, Air-Entraining Admixtures for Concrete M 157, Ready-Mixed Concrete M 170M, Reinforced Concrete Culvert, Storm Drain, and Sewer Pipe Metric M 194M/M 194, Chemical Admixtures for Concrete M 221M/M 221, Steel Welded Wire Reinf
9、orcement, Deformed, for Concrete 2017 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 170-2 AASHTO M 225M/M 225, Steel Wire, Deformed, for Concrete Reinforcement M 240M/M 240, Blended Hydraulic Cement
10、 M 242M/M 242, Reinforced Concrete D-Load Culvert, Storm Drain, and Sewer Pipe M 262, Concrete Pipe and Related Products M 295, Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete M 302, Slag Cement for Use in Concrete and Mortars T 280, Concrete Pipe, Manhole Sections, or Tile 2.2
11、. ASTM Standards: A36/A36M, Standard Specification for Carbon Structural Steel A706/A706M, Standard Specification for Deformed and Plain Low-Alloy Steel Bars for Concrete Reinforcement C309-03, Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete C1017/C1017M, Standard Sp
12、ecification for Chemical Admixtures for Use in Producing Flowing Concrete C1116/C1116M, Standard Specification for Fiber-Reinforced Concrete 3. TERMINOLOGY 3.1. DefinitionsFor definitions of terms relating to concrete pipe, see M 262. 4. CLASSIFICATION 4.1. Pipe manufactured in accordance with this
13、specification shall be of five classes identified as Class I, Class II, Class III, Class IV, and Class V. The corresponding strength requirements are prescribed in Tables 1 to 5. 2017 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a viol
14、ation of applicable law.TS-4a M 170-3 AASHTO Table 1Design Requirements for Class I Reinforced Concrete PipeaInternal Designated Diameter, in. Reinforcement, in.2/Linear ft of Pipe Wall Wall A Wall B Concrete Strength, 4000 psi Concrete Strength, 4000 psi Wall Thickness, in. Circular ReinforcementbE
15、lliptical ReinforcementcWall Thickness, in. Circular ReinforcementbElliptical ReinforcementcInner Cage Outer Cage Inner Cage Outer Cage 60 5 0.25 0.15 0.28 6 0.21 0.13 0.23 66 51/20.30 0.18 0.33 61/20.25 0.15 0.28 72 6 0.35 0.21 0.39 7 0.29 0.17 0.32 78 61/20.40 0.24 0.44 71/20.32 0.19 0.36 84 7 0.4
16、5 0.27 0.50 8 0.37 0.22 0.41 90 71/20.49 0.29 0.54 81/20.41 0.25 0.46 96 8 0.54 0.32 0.60 9 0.46 0.28 0.51 Concrete Strength, 5000 psi Concrete Strength, 5000 psi 102 81/20.63 0.38 Inner Circular Plus Elliptical 0.25 0.38 91/20.54 0.32 Inner Circular Plus Elliptical 0.22 0.32 108 9 0.68 0.41 Inner C
17、ircular Plus Elliptical 0.27 0.41 10 0.61 0.37 Inner Circular Plus Elliptical 0.24 0.37 114 a a 120 a a 126 a a 132 a a 138 a a 144 a a aFor modified or special designs, see Section 7.2 or, with the permission of the owner, use the provision of M 242M/M 242. Steel areas may be interpolated between t
18、hose shown for variations in diameter, loading, or wall thickness. Pipe more than 96 in. in diameter shall have two circular cages or an inner circular cage plus one elliptical cage. bAs an alternative to design requiring both inner and outer circular cages, the reinforcement may be positioned and p
19、roportioned in one of the following manners: (1) an inner circular cage plus an elliptical cage such that the area of the elliptical cage shall not be less than that specified for the outer cage in the table, and the total area of the inner circular cage plus the elliptical cage shall not be less th
20、an that specified for the inner cage in the table; (2) an inner and outer cage plus quadrant mats in accordance with Figure 1; or (3) an inner and outer cage plus an elliptical cage in accordance with Figure 2. cElliptical and quadrant steel must be held in place by means of holding rods, chairs, or
21、 other positive means throughout the entire casting operation. Note: See Section 5 for basis of acceptance specified by the owner. The strength test requirements in pounds-force per linear foot of pipe under the three-edge-bearing method are listed below as the D-load (test load expressed in pounds-
22、force per linear foot per foot of diameter) to produce a 0.01-in. crack and the ultimate load multiplied by the internal diameter of the pipe in feet. For acceptance testing requirements, see Section 11.3.1. D-load to produce a 0.01-in. crack 800 D-load to produce the ultimate load 1200 2017 by the
23、American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 170-4 AASHTO Table 2Design Requirements for Class II Reinforced Concrete Pipea Internal Designated Diameter, in. Reinforcement, in.2/Linear ft of Pipe Wall Wal
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AASHTOM1702017STANDARDSPECIFICATIONFORREINFORCEDCONCRETECULVERTSTORMDRAINANDSEWERPIPEPDF

链接地址:http://www.mydoc123.com/p-417682.html