1、 INCH-POUND MIL-DTL-24643/63 1 March 2007 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, 1000 VOLTS, TYPE LSYSGU This specification is approved for use by all Departments and Agencies of the Department of Defense. The requirements for acquiring the product described herein shall consist of this speci
2、fication sheet and MIL-DTL-24643. This cable type is specifically designed for single circuit (see Figure 1), three-phase, wye connected (with neutral wire), 60 or 400 Hertz, electrical power distribution. The designation Y represents the wye connection. Using two conductors per phase reduces the se
3、ries inductance to 50 percent of the single conductor per phase value. In addition, the symmetrical spacing of the phase conductors from the neutral wire provides for balanced voltage drop when three-phase loads are applied. REQUIREMENTS: Qualification Required. Construction (Watertight with Circuit
4、 Integrity)First - Copper conductor, uncoated (see Table I for size). Second - Separator may be used at the manufacturers option to ensure that the insulation is easily stripped off of the conductor. Third - Extruded silicone rubber, or silicone rubber-glass tape insulation at the manufacturers opti
5、on (see Table I for diameter). Refer to Table II for identification code. Fourth - Seven conductors cabled together with a left-hand lay of six conductors around the center conductor (see Figure 2 for cross-sectional view). The length of lay shall not exceed 24 times the pitch diameter. Fillers shal
6、l be employed to obtain a well-rounded assembly. Fifth - Optional binder tape applied helically with overlap. Sixth - Cross-linked polyolefin jacket (see Table I for thickness). AMSC N/A 6145 Source: http:/ - Downloaded: 2008-02-14T01:33ZCheck the source to verify that this is the current version be
7、fore use.MIL-DTL-24643/63 TABLE I. LSYSGU sizes and characteristics. Conductor Cable Amps per Phase(2 conductors) Military Part No. M24643/63 AWG Circular MILS Stranding Diameter Over Insulation (min.) 40 C ambient50 C ambient/1000 ft 25 C (max.) Jacket Thickness (min.) Overall Diameter (max.) Weigh
8、t (lbs/ft)-01UN 16 2580 7 X 0.0192 0.125 18 16 4.300 0.040 0.535 0.188 -02UN 14 4110 7 X 0.0242 0.140 29 27 2.680 0.040 0.580 0.255 -03UN 12 6530 7 X 0.0305 0.160 39 36 1.900 0.040 0.640 0.314 -04UN 10 10380 7 X 0.0385 0.187 62 58 1.125 0.040 0.730 0.420 -05UN 8 16510 19 X 0.0295 0.275 84 77 0.790 0
9、.050 1.000 0.725 -06UN 4 41740 19 X 0.0469 0.325 145 133 0.287 0.050 1.170 1.400 -07UN 2 66360 19 X 0.0591 0.365 193 178 0.203 0.060 1.310 2.000 -08UN 1 83690 37 X 0.0476 0.407 237 218 0.145 0.060 1.450 2.400 -09UN 0 105600 61 X 0.0416 0.453 272 254 0.120 0.060 1.600 3.000 -10UN 00 133100 61 X 0.046
10、7 0.510 320 294 0.0888 0.065 1.780 3.750 -11UN 000 167800 61 X 0.0524 0.560 376 346 0.0674 0.065 1.880 4.500 Note: All dimensions are in inches unless otherwise specified. FIGURE 1. LSYSGU single circuit user diagram. 2 Source: http:/ - Downloaded: 2008-02-14T01:33ZCheck the source to verify that th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- MIL DTL 24643.63 2007 CABLE ELECTRICAL 1000 VOLTS TYPE LSYSGU

链接地址:http://www.mydoc123.com/p-115541.html