VA FED H-08-1 SEC 16510-2003 BUILDING LIGHTING INTERIOR《建筑照明 室内装饰》.pdf
《VA FED H-08-1 SEC 16510-2003 BUILDING LIGHTING INTERIOR《建筑照明 室内装饰》.pdf》由会员分享,可在线阅读,更多相关《VA FED H-08-1 SEC 16510-2003 BUILDING LIGHTING INTERIOR《建筑照明 室内装饰》.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、03-03M 16510-1 SECTION 16510 BUILDING LIGHTING, INTERIOR SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. Coordinate with drawing schedules. PART 1 - GENERAL 1.1 DESCRIPTION This sect
2、ion specifies the furnishing, installation and connection of the interior lighting systems. 1.2 RELATED WORK A. Section 16050, BASIC METHODS AND REQUIREMENTS (ELECTRICAL): General requirements that are common to more than one section of Division 16. B. Section 16127, CABLES, LOW VOLTAGE (600 VOLTS A
3、ND BELOW): Cables and wiring. C. Section 16140, WIRING DEVICES: Wiring devices used as part of the lighting systems. D. Section 16450, GROUNDING: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents. 1.3 QUALITY ASSURANCE A. Refer to Para
4、graph, QUALIFICATIONS, in Section 16050, BASIC METHODS AND REQUIREMENTS (ELECTRICAL). B. Refer to Paragraph, GUARANTY, in Section 01001, GENERAL CONDITIONS. 1.4 SUBMITTALS A. In accordance with Section 16050, BASIC METHODS AND REQUIREMENTS (ELECTRICAL), submit the following: B. Shop Drawings: 1. Suf
5、ficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, materials, required clearances, terminations, wiring and connection diagrams, photometric data, ballasts, lenses, louvers,
6、lamps, and controls. 3. When catalog data and/or shop drawings for fluorescent fixtures are submitted for approval, photometric data from an independent testing Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-03M 16510-2 laboratory shall be includ
7、ed with the submittal, indicating average brightness and efficiency of the fixture, as specified in specification or as shown on the drawings. Coefficient of utilization data will not be considered a suitable substitute. C. Samples: SPEC WRITER NOTE: Include the following where the total quantity of
8、 designated lighting fixtures exceed 100. 1. Simultaneously with the shop drawing and catalog cut submittal, deliver to the Resident Engineer a sample of each lighting fixture types: _, _, _ for approval. The approved samples shall be installed in the location directed by the Resident Engineer and s
9、hall be removed, repackaged and turned over to the Resident Engineer after final inspection. D. Manuals: 1. Submit, simultaneously with the shop drawings companion copies of complete maintenance and operating manuals including technical data sheets, and information for ordering replacement parts. 2.
10、 Two weeks prior to the final inspection, submit four copies of the final updated maintenance and operating manuals, including any changes, to the Resident Engineer. E. Certifications: 1. Two weeks prior to final inspection, submit four copies of the following certifications to the Resident Engineer
11、: a. Certification by the Contractor that the equipment has been properly installed, adjusted, and tested. b. Include with shop drawings, certification from the manufacturers that all electronic high-frequency ballasts meet the transient protection required by IEEE C62.41, Cat. A. Include with initi
12、al shop drawing submittal. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. Provided by IHSNot for Resa
13、leNo reproduction or networking permitted without license from IHS-,-,-03-03M 16510-3 B. American National Standards Institute (ANSI): C78.1-91Fluorescent Lamps - Rapid-Start Types - Dimensional and Electrical Characteristics C78.2-91Fluorescent Lamps - Preheat-Start Types - Dimensional and Electric
14、al Characteristics C78.3-91Fluorescent Lamps - Instart Start and Cold-Cathode Types - Dimensional and Electrical Characteristics C78.376-91Chromaticity of Fluorescent Lamps (ANSI/NEMA C78/376-96) C. Certified Ballast Manufacturers Association (CBM): Requirements for Ballast Certification. D. Institu
15、te of Electrical and Electronic Engineers (IEEE): C62.41-91.Recommended Practice on Surge Voltage in Low Voltage AC Power Circuits E. National Fire Protection Association (NFPA): 70-02.National Electrical Code (NEC) 101-00Life Safety Code F. National Electrical Manufacturers Association (NEMA) C82.1
16、-97Ballasts for Fluorescent Lamps - Specifications C82.2-02Method of Measurement of Fluorescent Lamp Ballasts C82.4-02Ballasts for High-Intensity-Discharge and Low-Pressure Sodium Lamps C82.11-02.High Frequency Fluorescent Lamp Ballasts G. Underwriters Laboratories, Inc. (UL): 496-96Edison-Base Lamp
17、holders 542-99Lampholders, Starters, and Starter Holders for Fluorescent Lamps 844-95Electric Lighting Fixtures for Use in Hazardous (Classified) Locations 924-95Emergency Lighting and Power Equipment 935-01Fluorescent-Lamp Ballasts 1029-94.High-Intensity-Discharge Lamp Ballasts 1598-00.Luminaires H
18、. Federal Communications Commission (FCC): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-03M 16510-4 Code of Federal Regulations (CFR), Title 47, Part 18 PART 2 - PRODUCTS 2.1 LIGHTING FIXTURES (LUMINAIRES) A. Shall be in accordance with NFPA 70
19、, UL 1598 and shall be as shown on drawings and as specified. B. Sheet Metal: 1. Shall be formed to prevent warping and sagging. Housing, trim and lens frame shall be true, straight (unless intentionally curved) and parallel to each other as designed. 2. Wireways and fittings shall be free of burrs
20、and sharp edges and shall accommodate internal and branch circuit wiring without damage to the wiring. 3. Where lighting fixtures are detailed with minimum 20 gauge housing, minimum 22 gauge housings will be acceptable provided they have strengthening embossed rib and break formations, which give th
21、e equivalent rigidity of a 20 gauge housing. 4. When installed, any exposed fixture housing surface, trim frame, door frame and lens frame shall be free of light leaks; lens doors shall close in a light tight manner. 5. Hinged door closure frames shall operate smoothly without binding when the fixtu
22、re is in the installed position, and latches shall function easily by finger action without the use of tools. C. Ballasts shall be serviceable while the fixture is in its normally installed position, and shall not be mounted to removable reflectors or wireway covers unless so specified. D. Lamp Sock
23、ets: 1. Fluorescent: Lampholder contacts shall be the biting edge type or phosphorous-bronze with silver flash contact surface type and shall conform to the applicable requirements of UL 542. Contacts for recessed double contact lampholders and for slimline lampholders shall be silver plated. Lampho
24、lders for bi-pin lamps, with the exception of those for “U“ type lamps, shall be of the telescoping compression type, or of the single slot entry type requiring a one-quarter turn of the lamp after insertion. 2. Incandescent: Shall have porcelain enclosures and conform to the applicable requirements
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VAFEDH081SEC165102003BUILDINGLIGHTINGINTERIOR 建筑 照明 室内装饰 PDF

链接地址:http://www.mydoc123.com/p-1075045.html