VA FED H-08-1 SEC 16480-2005 MOTOR CONTROL CENTERS《电动机控制中心》.pdf
《VA FED H-08-1 SEC 16480-2005 MOTOR CONTROL CENTERS《电动机控制中心》.pdf》由会员分享,可在线阅读,更多相关《VA FED H-08-1 SEC 16480-2005 MOTOR CONTROL CENTERS《电动机控制中心》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、12-05M 16480-1 SECTION 16480 MOTOR CONTROL CENTERS SPEC WRITE NOTE: Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, complete ins
2、tallation, and connection of the motor control centers. 1.2 RELATED WORK A. Section 13081, SEISMIC RESTRAINT FOR NON-STRUCTURAL COMPONENTS: Seismic requirements for non-structural equipment. B. Section 16050, BASIC METHODS AND REQUIREMENTS (ELECTRICAL): General electrical requirements and items that
3、 is common to more than one section of Division 16. C. Section 16051, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY.D. Section 16127, CABLES, LOW VOLTAGE (600 Volts and below): Cables and wiring. E. Section 16155, MOTOR STARTERS: Control and protection of motors. F. Section 16430, METERING, G. Section 1
4、6450, GROUNDING: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. 1.3 SUBMITTALS A. Submit in accordance with Section 16050, BASIC METHODS AND REQUIREMENTS (ELECTRICAL). B. Catalog Data: 1. Submit Catalog Data and information as required to de
5、monstrate that materials conform to the specification requirements. Data shall include features, characteristics, ratings and settings of all adjustable components. C. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specificati
6、ons. 2. Include electrical ratings, enclosure type, dimensions, weights, mounting details, front view, side view, equipment and device arrangement, running overcurrent protection, branch circuit overcurrent protection, wiring diagrams, materials, connection diagrams for each motor control center, an
7、d nameplate schedule. 3. For starters: a list of overload sizes for each motor, and / circuit breakers / fuse / sizes. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-05M 16480-2 D. Manuals: Two weeks prior to the final inspection, submit four cop
8、ies of the following to the Resident Engineer: 1. Complete maintenance, operating and testing manuals including wiring diagrams, technical data sheets, including load current, overload relay and settings of adjustable relays, and information for ordering replacement parts: a. Include complete “As In
9、stalled“ diagrams, which indicate all items of equipment and their interconnecting wiring. b. Include complete diagrams of the internal wiring for each of the items of equipment, including “As Installed“ revisions of the diagrams. c. The wiring diagrams shall identify the terminals to facilitate ins
10、tallation, maintenance, operation and testing. d. Instructions for testing and adjusting overcurrent protective devices. E. Certification: Two weeks prior to final inspection, submit four copies of the following to the / Resident Engineer / COTR /: SPEC WRITER NOTE: Refer to VA Handbook H-18-8 for S
11、eismic Design Requirements. Specify Region of Seismicity, based on location of the equipment so motor control center manufacturers can check/design seismic strength of their equipment. Delete the following paragraph if the motor control center(s) is located outside the seismic zone. 1. Certification
12、 from the manufacturer that the motor control center(s), accessories, and components will withstand the seismic forces and that the unit will be fully operational after the seismic event at the project site. 2. Certification by the manufacturer that the motor control centers conform to the requireme
13、nts of the drawings and specifications. 3. Certification by the Contractor that the motor control centers have been properly installed, adjusted, and tested. 1.4 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of thi
14、s specification to the extent referenced. Publications are referenced in the text by the basic designation only. B. National Electrical Manufacturers Association (NEMA): ICS 1-05Industrial Control and Systems: General Requirements Provided by IHSNot for ResaleNo reproduction or networking permitted
15、without license from IHS-,-,-12-05M 16480-3 ICS 2-05Industrial Control and Systems: Controllers, Contactors, and Overhead Relays, Rated 600 volts ICS 6-01Industrial Control and Systems: Enclosures FU 1-02.Low-Voltage Cartridge Fuses 250-03Enclosures for Electrical Equipment (1000 Volts Maximum) C. N
16、ational Fire Protection Association (NFPA): 70-05.National Electrical Code (NEC) D. Underwriters Laboratories, Inc. (UL): 486A-04.Wire Connectors and Soldering Lugs for Use with Copper Conductors 845-04Motor Control Centers PART 2 - PRODUCTS 2.1 MOTOR CONTROL CENTERS A. Factory-assembled and wired m
17、otor control centers shall comply with NEC, NEMA, and UL, and as shown on the drawings. B. Motor control centers shall be complete, floor-mounted, dead-front metal-enclosed, free-standing, grounded, indoor type. C. Wiring: The motor control centers shall be NEMA Standard, Class / 1 / 2 /, Type / A /
18、 B / C /. SPEC WRITER NOTE: Larger projects will require a study as part of the construction contract requirements. The Engineer shall coordinate with the VA. D. Ratings: Ratings shall be not less than shown on the drawings. Interrupting ratings shall be not less than the maximum short circuit curre
19、nts available at motor control center location as shown on the drawings / or as calculated as part of the Section 16051, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY./ E. Shall conform to the arrangements and details of the drawings and to the spaces designated for installation. F. Motor control center
20、s shall be able to withstand the mechanical stresses caused by rough handling during shipment in addition to the normal electrical and mechanical stresses, which will occur during operation of the centers. G. The components and the control wiring shall conform to the approved shop drawings as furnis
21、hed for the various applicable electrical and mechanical sections of the specifications. H. All Steel parts shall be factory phosphatized and painted with primer and baked enamel or lacquer finishes except for ground connections. The Provided by IHSNot for ResaleNo reproduction or networking permitt
22、ed without license from IHS-,-,-12-05M 16480-4 paint and finish shall withstand a minimum of 1000 hours salt spray test. I. Vertical Sections: 1. Approximately 2.25 m (90 inches) high, front and rear line-up, dead-front assembly and fabricated by a single manufacturer. Unit shall be designed to perm
23、it future additions or rearrangement of units. 2. Rugged steel assemblies with bracing, reinforcing gussets and jig-welding to assure rectangular-rigidity. The sections shall be completely metal-enclosed, including the base and capable of being bolted together to form a single assembly. 3. The struc
24、ture shall be NEMA Type rated (Type 1, Type 3R or Type 12) as indicated on the drawings or as required to suit the environment. 4. Spaces within the sections shall be suitable and adequately sized for starters and accessories as indicated on the drawings. 5. Mount the sections on adequate structural
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VAFEDH081SEC164802005MOTORCONTROLCENTERS 电动机 控制中心 PDF

链接地址:http://www.mydoc123.com/p-1075044.html