1、07-02M 15819-1 SECTION 15819 ENERGY RECOVERY EQUIPMENT SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. DESIGNER NOTES: 1. This specification has links connected to other documents in
2、 VA “Technical Information Library (TIL).” These links are to facilitate designers to look into related documents while edited this specification. These links must be deleted before the specification is finalized for a particular project. To delete these links make sure macros are installed on your
3、system, and if not do the following: Click on Tools. Go to Macro and click on Security. Check the Medium Security Level. Close the specification, if open. Open the specification (again) and follow the prompts on the screen. Click on Enable Macros when first prompt appears. Delete the links only if s
4、pecification is ready to be included in the project. 2. Coordinate VA Standard Details with this spec section and show them on the drawings as applicable: 3. HVAC Pumps Schedule Detail No.15140-3.DWG. 4. Typical Piping Connections to In-Line Water Pumps, Detail no. 15705-11.DWG. 5. Energy Recovery,
5、Run around Water Coil Schedule, Detail No.15819-1.DWG. 6. Air to Air Plate Heat Exchanger Schedule, Detail No. 15819-2.DWG. 7. Rotary Air to Air Heat Exchanger Schedule, Detail No. 15819-3.DWG. 8. See CD-54 for wind velocity requirements in coastal areas. Equipment installed outdoor shall withstand
6、wind forces stated in CD-54. 9. Follow manufacturers written instructions carefully for ductwork layout required for heat recovery equipment 10. VA normally does not recommend use of Rotary Air-to Air Heat Exchangers. Provided by IHSNot for ResaleNo reproduction or networking permitted without licen
7、se from IHS-,-,-07-02M 15819-2 Discuss its use with VA before specifying it. PART 1 - GENERAL 1.1 DESCRIPTION A. Air-to-Air Heat Pipe Heat Exchanger: Unit transfers assembled heat via heat pipes without any moving parts. B. Rotary Air-to-Air Heat Exchanger: Unit transfers sensible and latent heat. T
8、his exchanger, popularly called a heat wheel, is a revolving cylinder, filled with an air permeable medium with a large internal surface area for intimate contact with the air passing through it. C. Air-to-Air Plate Heat Exchanger: Unit transfers sensible heat via metal plates without any moving par
9、ts. D. Run around Heat Exchangers. 1.2 RELATED WORK A. Section 01010, GENERAL REQUIREMENTS: Requirements for pre-test of equipment. B. Section 13081, SEISMIC RESTRAINT REQUIREMENTS FOR NON STRUCTURAL COMPONENTS: Seismic requirements for non-structural equipment. C. Section 15050, BASIC METHODS AND R
10、EQUIREMENTS (MECHANICAL): General mechanical requirements and items, which are common to more than one section of Division 15. D. Section 15140, PUMPS (HVAC): Requirements for pumping equipment. E. Section 15250, INSULATION: Requirements for piping insulation. F. Section 15705, HVAC PIPING SYSTEMS:
11、Requirements for piping for expansion tanks. G. Section 15750, HEATING AND COOLING COILS: Requirements for run-around system coils. H. Section 15840, DUCTWORK AND ACCESSORIES: Requirements for sheet metal ducts and fittings. I. Section 15885, AIR FILTERS: Requirements for filters used before heat re
12、covery coils. J. Section 15902, CONTROLS AND INSTRUMENTATION (DDC): Requirements for controls and instrumentation. K. Section 15980, TESTING, ADJUSTING AND BALANCING: Requirements for testing, adjusting and balancing of HVAC system. Provided by IHSNot for ResaleNo reproduction or networking permitte
13、d without license from IHS-,-,-07-02M 15819-3 1.3 QUALITY ASSURANCE A. Refer to paragraph, GUARANTEE in specification Section 01001, GENERAL CONDITIONS. B. Refer to specification Section 01010, GENERAL REQUIREMENTS for performance tests and instructions to VA personnel. C. Refer to paragraph QUALITY
14、 ASSURANCE in specification Section 15050 BASIC METHODS AND REQUIREMENTS (MECHANICAL D. Performance Criteria: Heat recovery equipment shall be provided by a manufacturer who has been manufacturing such equipment and the equipment has a good track record for at least 5 years. E. Performance Test: In
15、accordance with PART 3. 1.4 SUBMITTALS A. Submit in accordance with Section 01340, SAMPLES AND SHOP DRAWINGS. B. Manufacturers Literature and Data: 1. Heat Pipe Heat Exchanger 2. Rotary Heat Exchanger 3. Plate Heat Exchanger 4. Run-Around Energy Recovery System C. Certificate: Submit, simultaneously
16、 with shop drawings, an evidence of satisfactory service of the equipment on three similar installations. D. Submit type, size, arrangement and performance details. Present application ratings in the form of tables, charts or curves. E. Provide installation, operating and maintenance instructions, i
17、n accordance with Article, INSTRUCTIONS, in Section 01010, GENERAL REQUIREMENTS. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. Air Conditioning and
18、 Refrigeration Institute (ARI) ARI 1060-2001.Rating Air-to-Air Energy Recovery Ventilator Equipment C. American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE): 84-91.Method of Testing Air-to-Air Heat Exchanges including Addenda to year 2001 Provided by IHSNot for ResaleNo
19、reproduction or networking permitted without license from IHS-,-,-07-02M 15819-4 15-94.Safety Code for Mechanical Refrigeration D. American Society for Testing and materials (ASTM) D635-98.Standard Test Method for Rate of Burning and/ or Extent and Time of Burning of Plastics in a Horizontal Positio
20、n E84-01Standard Test method for Surface Burning Characteristics of Building Materials E. Underwriters Laboratories, Inc (UL) 1812-95.UL Standard for Safety Ducted Heat Recovery Ventilators 1815-95.UL Standard for Safety Non-Ducted Heat Recovery Ventilators PART 2 - PRODUCTS 2.1 AIR-TO-AIR HEAT PIPE
21、 HEAT EXCHANGERS A. Comply with UL Standards B. Thermal recovery units shall be capable of operating at temperatures ranging from a minimum of -29 degrees C (-20 degrees F) to a maximum of 49 degrees C (120 degrees F). The heat transfer between air streams shall take place in a counterflow arrangeme
22、nt. The unit shall have no moving part and shall be one piece construction. C. Tube core shall be either 18-mm (5/8 inch) or 25-mm (1 inch) OD seamless aluminum tubing permanently expanded into the fins to form a firm, rigid and complete metal pressure contact between the tube and fin collar of all
23、operating conditions. Provide copper tubes and copper fins for corrosive air streams. D. Secondary surfaces shall be of continuous plate type aluminum fins, 0.18 mm (0.007 inch) thick, and of corrugated design to produce maximum heat transfer efficiencies. E. Basic capillary wick shall be an integra
24、l part of the inner wall of the tube and provide a completely wetted surface for maximum heat pipe capacity with minimum heat transfer resistance. F. Refrigerants used shall be approved by EPA. G. Provide a vertical partition to isolate the exhaust and supply airstreams from each other, so that ther
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VAFEDH081SEC158192002ENERGYRECOVERYEQUIPMENT 能量 回收 设备 PDF

链接地址:http://www.mydoc123.com/p-1075043.html